Contronics DZR-45 User manual

24-02-2016 version 1.6
CONTROLLER
USER MANUAL
DZR-45

DZR-45
2
Contronics Engineering B.V., Ambachtsweg 8, 5492 NJ Sint-Oedenrode, The Netherlands,
hereby declares that the product DZR-45, produced and delivered by Contronics Engineering
B.V., are in accordance with the following CE directives:
EMC-Directive : 2014/30/EU
Directive for low-voltage
electrical installation : 2014/35/EU

3
DZR-45
Table of content
1. PREFACE ��������������������������������������������������������������������������������������������������������� 4
2. INTRODUCTION ��������������������������������������������������������������������������������������������� 4
3. CONTENT OF THE DELIVERY �������������������������������������������������������������������� 4
4. DESCRIPTION OF THE CONTROLLER ���������������������������������������������������� 5
5. WALL-MOUNTING OF THE CONTROLLER��������������������������������������������� 6
6. CONNECTIONS����������������������������������������������������������������������������������������������� 7
7. OPERATION����������������������������������������������������������������������������������������������������� 8
8. SCREEN SETTING����������������������������������������������������������������������������������������� 9
9. TECHNICAL DATA ��������������������������������������������������������������������������������������� 14
10. MENU OVERVIEW ������������������������������������������������������������������������������������� 15
11. FACTORY SETTING AND RANGE���������������������������������������������������������� 16
12. OPTION DZR-45NET ��������������������������������������������������������������������������������� 21

DZR-45
4
1. PREFACE
This user manual contains the operating and installation instructions for the DZR-45
model controller.
2. INTRODUCTION
The DZR-45 is a hygrostat used to accurately regulate air humidity in rooms.
The DZR-45 is tted with the following as standard:
- Graphic readout screen (multi-lingual).
- LED bar readout of the proportional control.
- LED indicators for humidication and dehumidication.
- Main switch 230V.
- Touch key operation.
- Bandwidth setting.
- Dead zone setting.
- Maximum/minimum setting.
- Offset for the sensors.
- Hygrostat function (2x).
- Thermostat function (2x).
- Capacity control.
- Proportional control (2x) 0-10 Volt.
- Relay control (4x).
- Connection for 2 humidity/temperature sensors.
3. CONTENT OF THE DELIVERY
When you receive the controller, the package must contain the following items:
DZR-45 controller
2 M16 screws
2 M20 screws
User manual

5
DZR-45
4. DESCRIPTION OF THE CONTROLLER
Figure 1. Description and connections
A Readout window
B Indication LEDs
C Pushbuttons
D Securing screw for the upper cover
E On/Off switch
F Holes for wall mounting
G Perforated plate
H Mounting screws for perforated plate (M4 x 8mm)
I Screws for the connection compartment cover (M4 x 8mm)
J Connection compartment cover
SET
Hygrozone DZR-45 Made in Holland
E
B
AC
F
D
G
H
I
J

DZR-45
6
5. WALL-MOUNTING OF THE CONTROLLER
Figure 2. Installation of the controller
The controller must be mounted on an interior wall, preferably in a clean room where
the humidity level is not excessive. Do not mount the controller above a heating system
or the like. When installing, ensure that the display is located at eye level and that the
perforated plate (Fig. 1, item G) is facing downwards. Keep an area of up to 26 cm free
to the left of the controller to ensure that the cover can be opened (see Fig.2).
Open the cover of the controller by removing the screw from the upper cover (see
Fig. 1, item D). Remove the cover from the connection compartment (Fig. 1, item J)
by removing the two retaining screws. There are 4 mounting holes: 2 in the top corners
of the housing, and 2 at the bottom (Fig. 1, item F). M4 or M5 screws can be used for
these holes. You will nd the hole pattern in the diagram below:
Figure 3. Mounting holes pattern.
At least 26 cm.
Object or
wall
SET
Hygrozone DZR-45 Made in Holland
Eye level
222 mm
193 mm
IMPORTANT
If you wish to make holes in the perforated plate (Fig. 1, item G), please ensure
that the cover (J) of the connection compartment is positioned correctly. Then
carefully make the required number of holes using a hammer.

7
DZR-45
6. CONNECTIONS
Figure 4. Connections
HS-91 connections
Connection Colour Description
1 Brown Sensor 2 – HS-91 +12V
2 Grey Sensor 2 – HS-91 RH
3 Yellow Sensor 2 – HS-91 temperature
4 Green Sensor 2 – HS-91 0V
5 Brown Sensor 1 – HS-91 +12V
6 Grey Sensor 1 – HS-91 RH
7 Not used
8 Yellow Sensor 1 – HS-91 temperature
9 Green Sensor 1 – HS-91 0V
HS-10 connections
Connection Colour Description
5 Brown Sensor 1 – HS-10 +12V
7 White Sensor 1 – HS-10 RH
9 Green Sensor 1 – HS-10 0V
HK-01 connections
Connection Colour Description
10 White 0-10V dehumidication output
11 Brown 0V
12 White 0-10V humidication output (HK-01)
13 Brown 0V
1 2 98765
4
3 13121110 CCCC
NO NO
NO
NC NC NO L’ LN
Relay 4 Relay 3 Relay 2 Relay 1

DZR-45
8
LED indication humidication
switched on
LED indication dehumidication
switched on
Indication 0-10 Volt level
Readout window
On/Off switch
Pushbuttons
LED indication humidication
relay switched on
LED indication dehumidication
relay switched on
Relais connections
Relay Function
1Humidication
2Dehumidication or humidication 2
3 Thermostat
4 Alarm
230V connection
Connect the incoming mains voltage to terminals L and N. When the main switch is set
to ‘On’, L will be connected through to L’.
It is then possible to connect, a humidier to L’, for example.
Optimization of energy and water consumption.
A humidier also uses energy (10 Watt) and water (rinse program) in the stand-by posi-
tion (230V switched on, no humidity generation).
You can reduce this by switching off the humidication completely if the RH is 10%
higher than desired. The dehumidication relay is used for the connection. The
dehumidication bandwidth must thereby be set to 10%. Up to and including the HU-85,
the humidier can be connected directly to the relay. If an HU-245 humidier is
installed, an auxiliary relay must be used. See the connection diagram on page 20.
7. OPERATION
Figure 5. Operation.
IMPORTANT
- Ensure that all the connections are soldered when lengthening a cable.
- In order to prevent interference, ensure that low-voltage cables (0-10V) are
never installed parallel to high-voltage lines (230V).
- Sensor wiring must cross electricity lines at a 90˚ angle.

9
DZR-45
Press SET to go to the menu.
Select the desired menu item using the or button.
Press SET to conrm the selected item.
Select <<<< and press SET to leave a (sub)menu.
If no buttons are operated for 1 minute, the menu screen will switch off.
8. SCREEN SETTING
Main screen and sensor screen
The main screen is displayed as standard. The screen displays the measured and set
relative humidity. The sensor screen displays all the values measured at the connected
sensors.
Press the button in order to display the sensor screen, and also use the button to
return to the main screen.
Figure 6. Main screen. Figure 7. sensor screen.
Language setting
Press SET
Scroll to System using the or button.
Press SET
Scroll to Language using the or button.
Press SET
Select the language using the or button.
Press SET
Scroll to <<<< using the or button.
Press SET to leave the menu.
Basic conguration for DZR-45
The DZR-45 has 3 different congurations, which can be selected via this menu.
Single hygrostat
Single hygrostat with 1 humidity sensor, 1 humidication output and
1 dehumidication output. For more data, see General Hygrostat Operation.
IMPORTANT
Some of the menus are hidden from the user if they have no inuence on the
operation of the controller.
For example: In a single hygrostat conguration, the menu for hygrostat 2 is
not visible.

DZR-45
10
Hygrostat with max.
This hygrostat operates in the same manner as the single hygrostat, but with an
additional sensor for maximum humidication. The additional sensor can be
placed in an air channel in order to limit the maximum humidity.
The sensor can be selected as follows:
Hygrostat -> maximum humidication -> sensor selection.
This will limit the humidication as soon as the measured relative humidity has
reached the set maximum value.
The set maximum value can be adjusted as follows:
Hygrostat -> maximum humidity -> humidity set point.
The setting for the bandwidth can be found under:
Hygrostat -> maximum humidity -> bandwidth.
Figuur 8. Hygrostat with maximun control.
Double hygrostat
In principle, this is the same as 2 single hygrostats. The regulation of
dehumidication is hereby not possible.
The output of hygrostat 2 uses the dehumidication output.
Two hygrostat submenus are available in the main menu.
In this way, 2 areas can be monitored with one controller.
Block mode
In block mode, the regulator is divided into several blocks with settings. Each
block can be activated based on time and/or an external signal. This makes it
possible for the conguration to operate during the day with a variety of settings.
It is also possible to indicate a uid type for each block. This feature allows the
regulator to supply R.O. water or another uid to the humidier.
For comprehensive information, please refer to chapter X Block conguration
HK-01
0-10 Volt
Ca. 500 cm
HS/91 in room (Sensor 1)
DZR-45
HS/91 in duct (Sensor 2)

11
DZR-45
Block conguration
The block conguration becomes active if Block mode is selected under DZR
Conguration. This conguration makes it possible to use time or another external
signal to operate the regulator in another manner. Firstly, the correct time needs to be
set. System -> Setting the time. The start screen will now be as follows:
All available blocks can be seen under Block settings. The rst block is the Standard
block. This features all settings that are active if none of the other blocks are active.
The other blocks (1 to 10) will only be active if the stipulated conditions have been met.
This could involve being within a certain time or could require a certain external control
signal to be present.
Block settings
Settings in the standard block mainly resemble those of the single hygrostat, but without
de-humidication. The Start time and Stop time setting is used to indicate the time within
which the block will be active. The Fluid type setting can, as an option, be used to
switch between different uids via an electrical valve.
Overview of congured blocks
An overview of congured blocks can be found by pressing twice on the [UP} key
in the main screen. The rst 4 blocks are shown. Blocks 5 to 8 will appear if the
[UP] key is pressed once again. Blocks 9 and 10 are located in the nal screen.
If several blocks are subject to overlapping times, then the block with the highest
number will be given priority over other blocks.
Rinsing
Block mode makes it possible to switch between two uids. In this case, it may be
important to rinse the humidier during the change process. This means old uid will
no longer be sprayed after the change, but only the newly selected uid. It would be
wise to measure how long it takes for the humidier to become empty and how long it
takes to ll it. These times can be entered under Emptying time and Filling time in the
Rinsing menu.

DZR-45
12
Sensor settings
Two HS-91 humidity sensors can be connected to the DZR-45. It is also possible to
connect 1 HS-10 humidity sensor to sensor input 1, instead of an HS-91.
Select the correct type of sensor as follows:
Sensor settings menu -> sensor 1 -> sensor type setting.
If desired, an offset can be dened for the sensors.
Sensor settings menu -> sensor 1 and sensor settings menu -> sensor 2.
Sensor selection: Select the sensor (1/2) that controls each hygrostat (1/2).
Hygrostat (1/2) -> Sensor selection.
General hygrostat operation
The hygrostat uses a sensor to measure current air humidity in an area. The measured
value and the congured air humidity will be used by the hygrostat to implement a
humidier or de-humidier so the required value can be achieved.
The hygrostat features various settings. Firstly, the appropriate hygrostat mode
must be selected for the application in question, after which the other settings can
be congured.
Sub-conguration
Mode Hygrostat: Standard hygrostat function with set value.
Hygrostat 1/2 -> humidity set point.
Capacity: Provides a xed output value.
Hygrostat 1/2 -> Capacity.
Hygrostat / Capacity: The output will act as a hygrostat below a set
temperature. Above this set value, the output will
be dened by the capacity value.
Hygrostat (1/2) -> Temperature. Selection.
Capacity / Hygrostat: The output will act as a hygrostat above a set
temperature. Below this set temperature, the
output will be dened by the capacity value. The
temperature setting can be adjusted as follows:
Hygrostat (1/2) -> Temperature. Selection.
Dead zone: A dead zone is an inactive, neutral area.
A dead zone of 2% and a humidity setting of 50% results in a neutral area
of 49 – 51%. The dead zone is often used to prevent oscillations.
Bandwidth: The bandwidth can be set in:
Hygrostat (1/2) -> (De)humidication -> (De)humidication bandwidth.
The bandwidth monitors the reaction speed of a humidier between
1 and 20% around the setpoint.
Minimum: A minimum can be set for any output. This can be set as follows:
Hygrostat (1/2) -> (De)humidication -> Minimum (de)humidication
settings (0-99%).

13
DZR-45
Maximum: A maximum can be set for any output. This can be set as follows:
Hygrostat (1/2) -> (De)humidication -> Maximum (de)humidication
settings (0-99%).
Figuur 9. General hygrostat operation.
Output
The hygrostat generates a 0-100% signal that corresponds to a 0-10V signal at the
outputs of the DZR-45. Relay 1 switches on if Output 1 reaches 100% (10V), it switches
off when Output 1 is below 95% (9.5V) again.
Relay 2 has the same function, but corresponds to the Output 2 level.
Thermostat
The DZR-45 is tted with a built-in thermostat for heating or cooling.
All settings for this function can be found in the Thermostat submenu.
- Set point: The desired temperature.
- Sensor selection: The sensor used (sensor 1 or sensor 2).
- Mode: Cooling: Relay 3 will be activated if the current temperature is
above the set value.
Heating: Relay 3 will be activated if the current temperature is
below the set value.
- Hysteresis: The range within which the thermostat will not change the
output.
Alarm
Every sensor readout can be activated with the DZR alarm function. It is possible to
adjust the settings in the submenus Alarm -> Sensor 1 and Alarm -> Sensor 2.
Alarm relay (4) will be activated if one or more readouts reach their minimum or
maximum values. Alarm -> Alarm delay. The alarm relay will immediately turn off if the
value falls below the set alarm level again.
Set value
0V
Maximum
Dehumidification
Humidification
Maximum
10V
10V
Dead zone
Relay 2 On/Off
Relay 1 On/Off
Bandwidth
RH
Humidification
Dehumidification
Output

DZR-45
14
System
- Language: English / German / Dutch / French.
- LED readout*: Which hygrostat is using the LED bar:
Hygrostat 1 / Hygrostat 2.
- LCD contrast: Adjust the LCD contrast.
- LCD background light: Time setting for background lighting.
- Factory default: Reset all settings to factory settings.
- Software version: Internal DZR software version.
- Factory service: Special menu, not accessible.
* Only available in double hygrostat conguration
9. TECHNICAL DATA
Supply voltage: 230V ± 10% 50/60 Hz
Maximum relay load: 8A, 250 VAC
Proportional outputs: 0-10V (2x)
General accuracy 20% tot 95%
With humidity sensor HS-91: ± 2% (2x)
With humidity sensor HS-10: ± 5% (1x)
Power consumption: ≤ 5 W
Permissible ambient temperature: 0 - 50 °C
Dimensions: L 267 x W 225 x H 104 mm
Housing protection class: IP-54 with closed cover.
Accessories:
HS-10: Relative humidity sensor ± 5%.
HS-91: Relative humidity sensor ± 2%.
HK-01: Connection cable for Contronics humidier.

15
DZR-45
10. MENU OVERVIEW
Main screen
Blok 1 Switch on
Block settings 1
Maximum humidification
Minimum humidification
Dead zone
Humidity setpoint 2
Mode
Hygrostat 5, 7
Hygrostat 1 6Humidity set point 2
Capacity 4
Humidity set point 2
<<<---
<<<---
<<<---
Start time
End time
Standard block
Capacity 4
Temperature set point 3
Emptying time
Filling time
Rinsing 1
<<<---
Set point
Sensor selection
Modus
Thermostat
Hysterese
Sensor 1 Minimum humidification
Sensor 2 5
Alarm
Maximum humidification
Sensor 1
Sensor settings Sensor type
<<<---
Humidity correction
Block 2 to 10 are the same as block 1
Temperature setpoint 3
Maximum humidification
Minimum humidification
Dead zone
Humidity set point 2
Mode
<<<---
Capacity 4
Temperature set point 3
<<<---
Fluid type
Fluid type
DZR configuration Single hygrostat
Hygrostat with max
Double hygrostat
Block mode
Temperature set point 3
Capacity 4
Dead zone
Humidification Humidification bandwidth
Maximum humidification
Minimum humidification
<<<---
Dehumidification Humidification bandwidth
Maximum humidification
Minimum humidification
<<<---
Sensor selection
Maximum humidification
Sensor selection
Bandwidth
<<<---
Modus
Dead zone
Humidification Humidification bandwidth
Maximum humidification
Minimum humidification
<<<---
Sensor selection
Modus
Capacity 4
<<<---
Temperature set point 3
Dead zone
Humidification Humidification bandwidth
Maximum humidification
Minimum humidification
<<<---
Sensor selection
Modus
Humidity set point 2
Hygrostat 2 6
Minimum temperature
Maximum temperature
<<<---
Minimum humidification
Maximum humidification
Maximum temperature
<<<---
Minimum temperature
Temperature correction
<<<---
Sensor 2 5Humidity correction
Temperature correction
<<<---
System Language
<<<---
Clock settings 1
LED readdout 6
LCD contrast
LCD lighting
Factory settings
<<<---
Software version
Factory service 8
1. Only in block configuration
2. Only in hygrostat or hygrostat/capacity mode
3. Only in hygrostat/capacity mode
4. Only in capacity or hygrostat/capacity mode
5. Not in block mode
6. Only in double hygrostat configuration
7. Not in double hygrostat configuration
8. Only accessible with the manufacturer’s access code.
Humidity set point
Solution guard 1
Alarm delay
Alarm output

DZR-45
16
11. FACTORY SETTING AND RANGE
Para-
meter
Min. Max. Factory setting Own
setting
Conguration Single hygrostat
Hygrostat with max.
Double hygrostat
Block mode
Single hygrostat
Hygrostat
(1/2) / block X
Humidity set point 1 99 50 %
Dead zone 0,0 10,0 2,0 ˚C
Humidication
bandwidth
1 20 3 %
Minimum
humidication
0 100 0 %
Maximum
humidication
0 100 100 %
Dehumidication
bandwidth
1 20 3 %
Minimum
dehumidication
0 100 0 %
Maximum
dehumidication
0 100 100 %
Maximum
humidication
set point
10 100 80 %
Maximum
humidication
bandwidth
1 20 4 %
Maximum
humidication
sensor selection
Sensor 1
Sensor 2
Sensor 1* %
Mode Hygrostat
Capacity
Hygro/Capacity
Capacity/Hygro
Hygrostat
Fluid type R.O
Solution
R.O.

17
DZR-45
Para-
meter
Min. Max. Factory setting Own
setting
Flush Idle time 0 300 Default 2 min
Filling time 0 300 Default 30 sec
Thermostat Set point -40 70 25 ˚C
Sensor selection Sensor 1
Sensor 2
Mode Off
Cooling
Heating
Hysteresis 0,4 2,0 1,0 K
Alarm Minimum humidity Off
5 94
Off %
Maximum humidity Off
6
95 Off %
Minimum
Temperature
Off
-39
121 Off ˚C
Maximum
Temperature
Off
-38 122
Off ˚C
Alarm delay 0 240 0 min
Sensor set-
tings
Sensor type
Humidity correction -50 50 0 %
Temperature cor-
rection
-50 50 0 ˚C
System Language English
German
Dutch
French
English
LCD contrast 10 100 50 %
LCD Lighting 10
Off
60
On
10 sec
* In double hygrostat conguration is sensor 2 the standard setting at hygrostat 2.

DZR-45
18
Electrical distribution
board
1 2 98765
4
3 13121110 CCCC
NO NO NO
NC NC NO L’ LN
Relais 4 Relais 3 Relais 2 Relais 1
HS-91
HK-01
Network cable
Figure 10. Connection diagram single hygrostat.
Electrical distribution
board
1 2 98765
4
3 13121110 CCCC
NO NO NO
NC NC NO L’ LN
Relais 4 Relais 3 Relais 2 Relais 1
HS-91
HK-01
Network cable
(Sensor 1)
HS-91
(Sensor 2)
HK-01
HUMIDIFIER 1
HUMIDIFIER 2
Figure 11. Connection diagram double hygrostat.

19
DZR-45
Electrical distribution
board
1 2 98765
4
3 13121110 CCCC
NO NO NO
NC NC NO L’ LN
Relais 4 Relais 3 Relais 2 Relais 1
HS-91
HK-01
Network cable
(Sensor 1)
HS-91
(Sensor 2)
Figure 12. Connection diagram hygrostat with maximun control.
Electrical distribution
board
1 2 98765
4
3 13121110 CCCC
NO NO NO
NC NC NO L’ LN
Relais 4 Relais 3 Relais 2 Relais 1
HS-91
HK-01
External input
Valve Solution Valve
R.O.
Network cable
Figure 13. Connection diagram block mode.

DZR-45
20
Electrical distribution
board
1 2 98765
4
3 13121110 CCCC
NO NO NO
NC NO NC L’ LN
Relais 4 Relais 3 Relais 2 Relais 1
HS-91
HK-01
Network cable
Figure 14. Connection diagram for optimization of energy and water consumption.
Table of contents
Other Contronics Controllers manuals
Popular Controllers manuals by other brands

Emerson
Emerson Vilter MicroVission Operation and service manual

Alpha
Alpha AC219 installation manual

GIDROLOCK
GIDROLOCK WINNER Installation and operating instructions

Mitsubishi Electric
Mitsubishi Electric MELSEC iQ-R Series Safety function block reference

ProMinent
ProMinent DULCOMETER Assembly and operating instructions

Emerson
Emerson Bettis Q series Reference manual