Carel EASY COOL User manual

EASY COOL (PZD*S*P***):electronic controllers for normal temperature static refrigeration units
+050004121 - rel. 1.1 - 28.07.2011
NO POWER
& SIGNAL
CABLES
TOGETHER
READ CAREFULLY IN THE TEXT!
Description
PJEZ* represents a range of electronic microprocessor controllers with LED display developed for the manage-
ment of refrigerating units, display cabinets and showcases; are designed for the management of static refrigera-
ting units (no fan on the evaporator) operating at temperatures above 0°C.
Technical specifications
• Electronic controllers for normal temperature static refrigeration units
• Power supply 115Vac or 230Vac
• Ambient probe NTC
• Compressor relay 16A
Display and functions
During normal operation, the controller displays the value of the temperature read by probe. In addition, the
display has LED that indicate the activation of the control functions (see Tab. 1), while the 3 buttons can be used
to activate/deactivate some of the functions (see Tab. 2).
Compressor LED signals
icon function normal operation start up
ON OFF blink
compressor status on off ON request in
progress
ON
Tab. 1
Table of functions activated by the buttons
button normal operation start up
pressing the button alone pressed together
up
ON/OFF
more than 3 s:
toggle ON/OFF
Pressed together start/
stop
continuous cycle
-
down
defrost
more than 3 s:
start/stop defrost
for 1 s display firmware
vers. code
set mute - 1 s.: display/set the set point
- more than 3 s: access
parameter setting menu
(enter password ‘22’)
- for 1 s RESET current
EY set
Tab. 2
Setting the setpoint (desired temperature)
Step Action Effect Meaning
1Keep SET button pressed
for 2 s
After 1 sec currently setpoint value will
flash on display
It’s regulation setpoint
currently active
2Press UP or DOWN
buttons
Setpoint value will chang Set desired value
3Press SET button Controller will visualize temperature read
by probes again
setpoint is modified and
saved
Tab. 3
Accessing and setting the parameters
Step Action Effect Meaning
1Keep SET button
pressed for 3 s
After 3 s display will visualize “PS” Password is requested
2Press SET button again Display will visualize “0” blinking
3Press UP or DOWN button Visualized value on display will change Insert password “22”
4Press SET button After 5 s the first parameter, “/5”, will be
visualized on display
It’s the name of the first
parameter
5Press UP or DOWN button Parameter list will be scrolled on display
(refer to Table of parameters)
Select desired parameter
6Press SET button Display will visualize value of the selec-
ted parameter
It’s the currently parameter
value
7Press UP or DOWN button Parameter value visualized on display
will change
Set desired value
8Press SET button Display will visualize parameter name
again
Attention: parameters
updating is not yet active
9Repeat steps 5, 6, 7and 8for
all desired parameters
10 Keep SET button
pressed for 5 s
Controller will visualize temperature
read by probes again
Attention: now parameters
updating will be active
Tab. 4
Dimensions (mm)
38,29
31
28.5
10
3
71x29
36
81
74
33
PZD0SNP0E1
PZD4S0P001
PZD4S0P101
10
3
58
65,29
28.5
Panel mounting
max 2,5
123
Pozidriv type
Do not tighten
excessively
Front (with 2 screws ø 2,5x12 mm)
Rear (with 2 quick-fit side brackets) If necessary, remove the covers to simplify wiring
12
PUSH
PZD0SNP0E1
Fig.4
12
PUSH
PZD4S0P001, PZD4S0P101
Fig. 3
Electrical connections
230 Vac
345 67
9 10 118
L
L N
115V~
Use copper conductors only
Ref. C614A215/R0
EN60730-1 12(2)A
UL 873 12A 5FLA 30LRA
AMB. T.
NTC
PROBES
SERIAL
CONV
PROG.
KEY
-10T50
DI / NTC
250 Vac
3 4 5 6 7
9 10 118
L
L N
230V~
Use copper conductors only
Ref. C614A198/R0
EN60730-1 12(2)A
UL 873 12A 5FLA 30LRA
AMB. T.
NTC
PROBES
SERIAL
CONV
PROG.
KEY
-10T50
250 Vac
Fig.1
Fig.2
Fig.5
PZD0SNP0E1
PZD4S0P101
PZD4S0P001
+050004121 - rel. 1.1 - 28.07.2011
CAREL INDUSTRIES HQs
Via dell’Industria, 11 - 35020 Brugine - Padova (Italy)
Tel. (+39) 0499716611 – Fax (+39) 0499716600 – http://www.carel.com – e-mail: [email protected]
CAREL reserves the right to modify the features of its products without prior notice.
Disposal of the product
The appliance (or the product) must be disposed of separately in accordance with the local waste disposal
legislation in force.
WARNING: separate as much as possible the probe and digital input signal cables from the
cables carrying inductive loads and power cables to avoid possible electromagnetic disturbance.
Never run power cables (including the electrical panel wiring) and signal cables in the same
conduits.
NO POWER
& SIGNAL
CABLES
TOGETHER
READ CAREFULLY IN THE TEXT!
Table of parameters
Parameter Min. Max. Def. UOM
PS PASSWORD 09922-
/ PROBE PARAMETERS
/5 Select °C / °F ( 0 = °C; 1 = °F) 0 1 0 -
/6 Disable decimal point (1 = disabled) 0 1 0 -
/C1 Probe calibration (OFFSET) -50.0 50.0 0.0 °C/°F
r CONTROL PARAMETERS
St Setpoint (control temperature) -50.0 90.0 3.0 °C/°F
rd Control differential (hysteresis) 0.0 19.0 2.0 °C/°F
c COMPRESSOR PARAMETERS
c0 Comp. and fan start delay after start-up 0 100 0 min
c1 Min. time between successive comp. starts 0 100 1 min
c4 Compressor safety (duty setting) 0 100 15 min
d DEFROST PARAMETERS
d0 Type of defrost (0 and 1= defrost by temperature; 2, 3 and
4= defrost by time)
04 2-
dI Interval between defrosts 0 199 6 h/min
dP Max. or effective defrost duration 1 199 20 min/s
d4 Defrost when the instrument is switched on (1= activated) 0 1 0 -
d6 Disable temperature display during defrost (1= display disabled) 0 1 1 -
A ALARM PARAMETERS
A0 Alarm differential -20.0 20.0 -2.0 °C/°F
AL Low temperature alarm threshold/deviation -50.0 250.0 -5.0 °C/°F
AH High temperature alarm threshold/deviation -50.0 250.0 15.0 °C/°F
Ad Low and high temperature alarm delay 0 199 0 min
H OTHER SETTINGS
H2 Enable keypad
0= keypad disabled
1= keypad enabled
2= keypad enabled except for ON/OFF function
02 1-
EY Restore the Default settings 0 1 0 -
Tab. 5
Table of alarms
Alarm code Description Parameters involved
E0 probe 1 error= control -
LO low temperature alarm [AL] [Ad]
HI high temperature alarm [AH] [Ad]
EE unit parameter error -
EF operating parameter error -
dF defrost running [d6=0]
Pd defrost awaiting execution -
Tab. 6
How to restore the Default settings (refer to table of parameters in this
sheet)
1) Access parameter EY (entering password 22 and scroll parameter list).
2) Select the desired configuration:
• EY = 0 No changes;
• EY = 1 Restore of default settings (refer to Table of parameters in this sheet);
3) Exit the setting procedure (holding SET button for more than 3 s).
4) Power off the device and then power it on again while holding SET button.
5) The display shows “CE” to indicate that the configuration has been restored.
Switching the device ON/OFF
Press UP for more than 3 s. The control and defrost algorithms are now disabled and the
instrument displays the message “OFF” alternating with the temperature read by the set probe.
Manual defrost
Press DOWN for more than 3 s (the defrost starts only if the temperature conditions are valid).
Continuous cycle
Press UP and DOWN together for more than 3 s.
Technical specifications
power supply 115 Vac +10 / -15% 50/60 Hz
230 Vac -10% +15% 50/60 Hz
rated power 3 W
input NTC probe
relay output 16 A relay UL: 12 A resistive 5 FLA, 30 LRA 240 Vac 30,000 cycles
EN60730-1: 12(2)A or 10(4)A (N.O. only) 250 Vac 100000 cycles;
type of probe Std CAREL NTC 10 Kat 25 °C
power supply/
relay output
connector
- screw terminals pitch 5mm for cables with cross-sect. from 0.5 mm2to 1.5 mm2;
12 A max;
probe connector screw terminals:
- 2-pin pitch 5mm for models with 1 probe (cable cross-section from 0.5 mm2to 1.5
mm2); 12 A max;
assembly using screws from the front or with brackets at the rear
display LED display, 2 digits plus sign, decimal point and compressor icon
keypad 3 buttons with membrane
operating conditions -10T50 °C - humidity <90% rH non-condensing
storage conditions -20T70 °C - humidity <90% rH non-condensing
range of measurement -50T90 °C (-58T194 °F) - resolution 0.1 °C/°F
front panel index of protection panel installation with IP65 type 1
case plastic terminal, 81x36x38 mm
classification according to protection
against electric shock
Class II
environmental pollution II
PTI of the insulating material 250 V
period of stress across the insulating parts long
category of resistance to heat and fire category D (UL94 - V0)
immunity against voltage surges category 1
type of action and disconnection micro-disconnection 1C
no. of relay automatic operating cycles EN60730-1: 100,000 cycles
UL: 30,000 cycles (250 Vac)
software class and structure Class A
cleaning the instrument Only use neutral detergents and water
cable max. lenght serial: 1 km
probes: 30 m
relay: 10 m
Tab. 7
Note: do not run the power cable less than 3 cm from the bottom part of the device or from the probes; for
the connections only use copper wires.
Safety standards
compliant with the relevant European standards. Installation precautions:
• the connection cables must guarantee insulation up to 90 °C;
• ensure a space of at least 10 mm between the case and the nearby conductive parts;
• digital and analogue input connections less than 30 m away; adopt suitable measures for separating the
cables so as to ensure compliance with the immunity standards;
Secure the connection cables of the outputs so as to avoid contact with very low voltage parts.
IMPORTANT WARNINGS
The CAREL product is a state-of-the-art device, whose operation is specified in the technical documentation
supplied with the product or can be downloaded, even prior to purchase, from the website www.carel.com.
The customer (manufacturer, developer or installer of the final equipment) accepts all liability and risk relating
to the configuration of the product in order to reach the expected results in relation to the specific final instal-
lation and/or equipment. The failure to complete such phase, which is required/indicated in the user manual,
may cause the final product to malfunction; CAREL accepts no liability in such cases. The customer must use
the product only in the manner described in the documentation relating to the product. The liability of CAREL
in relation to its products is specified in the CAREL general contract conditions, available on the website www.
carel.com and/or by specific agreements with customers.

This manual suits for next models

3

Other Carel Controllers manuals

Carel ir33 smart User manual

Carel

Carel ir33 smart User manual

Carel ir33 Universale Guide

Carel

Carel ir33 Universale Guide

Carel EVD mini User manual

Carel

Carel EVD mini User manual

Carel FCPM0420A0 User manual

Carel

Carel FCPM0420A0 User manual

Carel pRack pR300 User manual

Carel

Carel pRack pR300 User manual

Carel pCO1 series User manual

Carel

Carel pCO1 series User manual

Carel kVent User manual

Carel

Carel kVent User manual

Carel pRack PR100 User manual

Carel

Carel pRack PR100 User manual

Carel PCOXS User manual

Carel

Carel PCOXS User manual

Carel thTx User manual

Carel

Carel thTx User manual

Carel easy way aria User manual

Carel

Carel easy way aria User manual

Carel pCO3 series Manual

Carel

Carel pCO3 series Manual

Carel pRack pR300T User manual

Carel

Carel pRack pR300T User manual

Carel k.Air User manual

Carel

Carel k.Air User manual

Carel FCR3 User manual

Carel

Carel FCR3 User manual

Carel FSC Series User manual

Carel

Carel FSC Series User manual

Carel mPCII User manual

Carel

Carel mPCII User manual

Carel CR72 Series User manual

Carel

Carel CR72 Series User manual

Carel FCS Series User manual

Carel

Carel FCS Series User manual

Carel ACC User manual

Carel

Carel ACC User manual

Carel AT-th Tune Series User manual

Carel

Carel AT-th Tune Series User manual

Carel ir33 platform User manual

Carel

Carel ir33 platform User manual

Carel pCO1 series User manual

Carel

Carel pCO1 series User manual

Carel HYPA3 Series User manual

Carel

Carel HYPA3 Series User manual

Popular Controllers manuals by other brands

Siemens SSC161.05UT manual

Siemens

Siemens SSC161.05UT manual

White Rodgers 1131 installation instructions

White Rodgers

White Rodgers 1131 installation instructions

Yamaha CEmarking RCX221 user manual

Yamaha

Yamaha CEmarking RCX221 user manual

Flycolor Raptor S-Tower F4-20A user manual

Flycolor

Flycolor Raptor S-Tower F4-20A user manual

ComAp InteliLite NT AMF Series reference guide

ComAp

ComAp InteliLite NT AMF Series reference guide

Emerson Fisher FIELDVUE DVC6200 SIS quick start guide

Emerson

Emerson Fisher FIELDVUE DVC6200 SIS quick start guide

Siemens FC18 Series operating manual

Siemens

Siemens FC18 Series operating manual

P.L.LIGHT SYSTEMS P.L.LIGHT IQ user manual

P.L.LIGHT SYSTEMS

P.L.LIGHT SYSTEMS P.L.LIGHT IQ user manual

Koganei ZL1 Series manual

Koganei

Koganei ZL1 Series manual

Agilent Technologies 11896A User's and service guide

Agilent Technologies

Agilent Technologies 11896A User's and service guide

Linak BusLink LA25 quick start guide

Linak

Linak BusLink LA25 quick start guide

Harmonic Drive LAH-80 Series Operation manual

Harmonic Drive

Harmonic Drive LAH-80 Series Operation manual

Omron CS1W-RPT01 Operation manual

Omron

Omron CS1W-RPT01 Operation manual

Siemens RDE-MZ6 operating instructions

Siemens

Siemens RDE-MZ6 operating instructions

SMSC USB2512A datasheet

SMSC

SMSC USB2512A datasheet

Santerno ASA 4.0 Advanced user manual

Santerno

Santerno ASA 4.0 Advanced user manual

Satel ACU-280 manual

Satel

Satel ACU-280 manual

Xylem hydrovar instruction manual

Xylem

Xylem hydrovar instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.