Converteam LV7000 User manual

Ethernet Option Board
LV7000
Order No. 700.002 735
Issue 06/08 AE01
Operating Manual

Safety and Operating Instructions
for Frequency Converters
according to Low Voltage Directive 73/23/EEC
1. General
During operation, frequency converters can have live,
rotating or moving parts and their surfaces may become hot,
depending on the protection class involved.
There is a risk of severe physical injury or material damage
if any of the covers are removed or the unit is installed, used
or operated incorrectly.
Further details are given in the documentation.
All system design, transport, installation, commissioning and
maintenance work must be carried out by qualified specialist
personnel (according to IEC 60364, CENELEC HD 384 or
DIN VDE 0100 and IEC 60664 or DIN VDE 0110 and
national safety regulations).
Qualified specialist personnel in the sense of these safety
instructions are persons who are experienced in the system
design, installation, erection, commissioning and operation
of the product and have the qualifications required for such
work.
2. Correct use
Converters are intended for installation in electrical plant or
machinery.
When installed in machines the converter may not be
commissioned (i.e. operation of the converter may not be
started) until it is evident that the machine complies with EC
directive 98/37/EC (Machine Directive) (formerly
89/392/EEC). Also EN 60204 must be observed.
Commissioning (i.e. operation) is only permitted in
compliance with the EMC directive (89/336/EEC).
Our converters satisfy the requirements of low voltage
directive 73/23/EEC. The standards of the series EN 50178 /
DIN VDE 0160 in conjunction with EN 60439-1 / VDE 0660
Part 500 and EN 60146 / VDE 0558 are applicable to drive
converters.
The technical data and the connection conditions are shown
on the rating plate and in the documentation. They must be
observed.
3. Transport and storage
The instructions for transport, storage and correct handling
must be observed.
Climatic conditions are to be maintained according to
EN 50178.
4. Installation
The installation and cooling must be in accordance with the relevant
documentation.
All converters must be protected against undue mechanical shocks
or stress. In particular no components may be bent and/or no
insulation spacing may be altered during transport and handling. Do
not touch electronic components or contacts.
Converters contain components susceptible to electrostatic
discharge (ESD), which are easily damaged by static electricity or
incorrect handling. Do not damage mechanically or destroy electrical
components (health hazard possible).
5. Electrical connection
The appropriate national safety regulations (e.g. BGV A3) must be
observed when working on converters, which are connected, to the
electricity supply.
The electrical installation must be executed in accordance with the
relevant regulations (e.g. cable cross-sections, fuses, earthing).
Additional instructions are given in the documentation.
Instructions on EMC compliant installation, such as screening,
earthing, filters and cable routing, are also given in the converters
documentation. These also apply to converters bearing the CE mark.
Compliance with the limits specified in EMC legislation is the
responsibility of the plant or the machinery manufacturer.
6. Operation
If necessary, plant or machinery in which converters are fitted must
be equipped with additional monitoring and safety facilities in
accordance with the relevant regulations, e.g. the law on technical
equipment, the appropriate safety regulations etc.
Do not touch any parts of the equipment which may be live or any
power connections even after the converter has been isolated from
the electricity supply, as capacitors may remain charged. Follow the
instructions given on warning labels.
All covers and doors must be kept closed during operation.
7. Service and maintenance
All instructions given in the documentation must be observed.
KEEP THESE SAFETY INSTRUCTIONS IN A SAFE PLACE

Ethernet Option Board /
700.002 735 AE01
ABOUT THE ETHERNET OPTION BOARD MANUAL
Congratulations for choosing the Smooth Control provided by LV7000 Frequency Converters!
The Operating manual will provide you with the necessary information about the installation, commissioning
and operation of Converteam Frequency Converters. We recommend that you carefully study these
instructions before powering up the frequency converter for the first time.

Ethernet Option Board /
700.002 735 AE01
Using the manuals
•The manuals contain descriptions of the software/hardware functions of the LV7000 rather than
descriptions of the plant into which the unit is integrated at a mechanical and/or functional level.
•The manuals are designed for users who design or configure applications involving the unit, who
commission equipment, and who perform maintenance work on the units or any other activity in
conjunction therewith.
•The specifications and information in the manuals and the other pertinent documentation cover the most
common applications. In view of the large number of possible applications of the LV7000 frequency
converter, it is, however, not possible to describe all conceivable applications and to provide exhaustive
information and guidance for engineering, configuration, commissioning, etc. Should you have any
questions concerning Converteam frequency converters or should you need any assistance, we hence
recommend that you contact our drive specialists.
•Expressions used
Note:
Notes separate important information from the text and give additional information.
WARNING
Important!
Important means that the relevant instruction must be followed exactly to avoid loss of
data or damage.
Warning!
Warning means that the operator may be injured if the instructions are not
followed.
HOT SURFACE
Hot surface – Risk of burn
•Converteam reserves the right to modify contents and product specifications of the manuals without
any obligation to explicitly inform its customers of any such changes.

Ethernet Option Board /
700.002 735 AE01
Applications and risks
Units from the LV7000 series are designed for the speed control of three-phase standard induction motors,
taking the technical motor and unit specifications into consideration.
In addition, LV7000-3 units may control also synchronous motors with permanent magnets.
The integration of the unit into plants or drive systems is not within the sphere of product responsibility of
Converteam.
This concerns the functions and operating safety of the entire system, as well as repercussions, if any, on
other facilities and systems.
The user of the unit is hence responsible for ensuring that the applicable technical standards and rules,
statutory requirements and codes in force at the place of installation are adhered to in conjunction with the
engineering and installation of the overall system.
The following information is to help to assess the risks related to the use of the unit. It is the user’s
responsibility to take any measures suitable to address these risks.
•Under incorrect or unwanted conditions, the motor can work
- at an incorrect speed
- at a high overspeed
- and / or in the wrong direction.
•An excessive supply voltage drop or an interruption of the supply voltage causes an immediate shutdown.
The motor connected is then no longer controlled by the converter.
The user of the unit must take suitable measures in order to master these cases (such as mechanical
protection devices, additional peripheral electrical monitoring and safety equipment, redundant configuration)
in order to avoid personal injury and damage to property, as well as to minimize interference with the ongoing
process based on a risk analysis to be carried out by the user.

Ethernet Option Board /
700.002 735 AE01
Note
Without our prior approval, this document shall not be copied or disclosed to any third party in any manner
whatsoever. The recipient hereof or any third party shall not use this document for any improper purpose
whatsoever. Translation to any foreign language is not permitted. Any data, dimensions, weights, illustrations
and other technical information shall be subject to change without notice, particularly in the interest of further
perfecting our equipment. The data and specifications agreed to in the event of an order shall be generally
deemed as being the binding basis.
Limitation of liability
Claims to any modification whatsoever of units previously supplied cannot be asserted by data, illustrations
and descriptions contained in the manuals.
In the event of any software (firmware) modifications and updates, we are not obliged to make such
modifications and updates available to customers on a retroactive basis.
The contents of the manuals were developed and revised with utmost care. However, Converteam does not
accept any liability for any damages, which might result from any defects in the documentation.
The user is to be solely responsible for the proper and correct use of the LV7000 frequency converters.
Converteam disclaims any liability whatsoever for improper or incorrect handling.
Process information and circuit details contained in the manuals shall be deemed as being suggestions only,
which shall be subject to verification by the user with regard to their suitability for the given application.
Converteam disclaims any warranty or liability for the suitability of such process information and circuit
suggestions with regard to the given application.
Data, illustrations, modifications
Data and illustrations and descriptions shall not be deemed as being warranted properties in the legal
meaning but being descriptions of the characteristic of state.
We reserve the right to make modifications in the interest of technical progress.
Please let us know if you have any suggestions for improvement or modification of the documentation.
Customer Support and Training
Converteam provides comprehensive telephone technical support, application planning, service and customer
training.
Contact Converteam at the address or telephone number shown at the end of this manual, or visit our website
www.converteam.com.
© 2008 Converteam

Contents
Ethernet Option Board /
700.002 735 AE01
Contents
1
Introduction ....................................................................................................................................1-1
2
Ethernet Board Technical Data.....................................................................................................2-1
2.1
Overview..........................................................................................................................................2-1
2.2
OPT-CI card.....................................................................................................................................2-1
2.3
Ethernet, introduction.......................................................................................................................2-2
2.4
Ethernet............................................................................................................................................2-2
2.5
Connections and Wiring...................................................................................................................2-3
3
Installation ......................................................................................................................................3-1
3.1
Installing the Ethernet Option Board in a Converteam LV7000 Unit ...............................................3-1
3.2
IP Tool NCIP Config.........................................................................................................................3-3
3.2.1
Update OPT-CI Option Board program with the NCIP Config Tool.................................................3-4
4
Modbus/TCP...................................................................................................................................4-1
4.1
MODBUS/TCP vs. MODBUS RTU..................................................................................................4-2
4.2
Ethernet Option Board's Modbus Addresses...................................................................................4-2
4.3
Coil (0x01) Register .........................................................................................................................4-2
4.3.1
0001 –00016 Control Word (Read / Write)......................................................................................4-2
4.3.2
0017 – 00018 Counters (Read Only)...............................................................................................4-3
4.4
Input Discrete (1x)............................................................................................................................4-4
4.4.1
10001 – 1008, Status Word (Read Only).........................................................................................4-4
4.5
Holding Registers (400001 - 410633)..............................................................................................4-5
4.5.1
400001 – 402000 and 402200 – 410000, Application ID ................................................................4-5
4.5.2
10501 – 10533, 10601 – 10633, ID MAP ........................................................................................4-6
4.5.3
10001 – 10033, 10101 – 10133, Index MAP...................................................................................4-7
4.5.4
402200 – 410000, FB Process Data Out (Read).............................................................................4-7
4.5.5
402200 – 410000, FB Process Data In (Read / Write)....................................................................4-7
4.5.6
10301 – 10333 Measurement Table................................................................................................4-8
4.6
Input Registers (3x)..........................................................................................................................4-8
4.6.1
Operation Day Counter 30001 – 30007...........................................................................................4-8
4.6.2
Reset table Operation Day Counter 30101 – 30107........................................................................4-8
4.6.3
Energy Counter 30201 – 30203.......................................................................................................4-9
4.6.4
Reset table Energy Counter 30301 – 30303 ...................................................................................4-9
4.6.5
Error History 30401 – 30417............................................................................................................4-9
5
Start-up Test...................................................................................................................................5-1
5.1
Frequency Converter Settings.........................................................................................................5-1
5.2
Master Unit Programming................................................................................................................5-1
6
Error Codes and Errors.................................................................................................................6-1
6.1
Frequency Converter Error Codes...................................................................................................6-1
6.2
Modbus TCP....................................................................................................................................6-1
7
Appendix.........................................................................................................................................7-1
Issue: 20.06.08
Converteam, the logo Converteam and their frameworks are trademarks and service trademark applications of
Converteam. The other names mentioned, registered or not, are the property of their respective companies.

Contents
Ethernet Option Board /
700.002 735 AE01

1 Introduction
Ethernet Option Board /
700.002 735 AE01
1-1
1 Introduction
Converteam LV7000 frequency converters can be connected to Ethernet using an Ethernet fieldbus board
OPT-CI.
The OPT-CI can be installed in the card slots D or E.
Every appliance connected to an Ethernet network has two identifiers; a MAC address and an IP address. The
MAC address (Address format: xx:xx:xx:xx:xx:xx ) is unique to the appliance and cannot be changed. The
Ethernet board's MAC address can be found on the sticker attached to the board or by using the Converteam
IP tool software NCIP Config.
In a local network, the user can define IP addresses as long as all units connected to the network are given
the same network portion of the address. For more information about IP addresses, contact your Network
Administrator. Overlapping IP addresses cause conflicts between appliances. For more information about
setting IP addresses, see Section 3, Installation.
Internal components and circuit boards are at high potential when the frequency
converter is connected to the power source. This voltage is extremely dangerous and
may cause death or severe injury if you come into contact with it.

1 Introduction
1-2 Ethernet Option Board /
700.002 735 AE01

2 Ethernet Board Technical Data
Ethernet Option Board /
700.002 735 AE01
2-1
2 Ethernet Board Technical Data
2.1 Overview
General Card Name OPT-CI
Ethernet Connections Interface RJ-45 connector
Transfer cable Foiled CAT5e
Speed 10 / 100 Mb
Duplex half / full
Communications
Default IP-address 192.168.0.10
Protocols Modbus / TCP
Ambient operating
temperature –10°C…50°C
Storing temperature –40°C…70°C
Humidity <95%, no condensation allowed
Altitude Max. 1000 m
Environment
Vibration 0.5 G at 9…200 Hz
Safety Fulfils EN50178 standard
Table 2-1: Ethernet Board Technical Data
2.2 OPT-CI card
Figure 2-1: OPT-CI card

2 Ethernet Board Technical Data
2-2 Ethernet Option Board /
700.002 735 AE01
2.3 Ethernet, introduction
The Ethernet consist of different layers shown in the picture below. Due to the modular structure of Ethernet it
is easy to add new protocols such as fieldbus or user interfaces to the Converteam Ethernet option board in
the future.
Figure 2-2: Ethernet layer structure
2.4 Ethernet
Common use-cases of Ethernet – devices are ‘human to machine’ and ‘machine to machine’. Basic features
of these two use-cases are presented in the pictures below.
1. Human to machine (Graphical User interface, relatively slow communication)
Figure 2-3: HMI communication
1
Physical
2 Data
Link
3
Network
4
Transport
5
Session
6
Presentatio
7
Applicatio
Ethernet Physical
Layer
Ethernet Data Link
Layer
IP
TCP
UDP
Protocol
Layer
(HTTP, DHCP , Modbus/TCP, Ethernet /
IP, etc)
1
Physical
2 Data
Link
3
Network
4
Transport
5
Session
6
Presentatio
7
Applicatio
Ethernet Physical
Layer
Ethernet Data Link
Layer
IP
TCP
UDP
Protocol
Layer
(HTTP, DHCP , Modbus/TCP, Ethernet /
IP, etc)
Ethernet Physical
Layer
Ethernet Data Link
Layer
IP
TCP
UDP
Protocol
Layer
(HTTP, DHCP , Modbus/TCP, Ethernet /
IP, etc)

2 Ethernet Board Technical Data
Ethernet Option Board /
700.002 735 AE01
2-3
2. Machine to machine (Industrial environment, fast communication)
Figure 2-4: Fast communication
2.5 Connections and Wiring
The Ethernet board supports 10/100Mb speeds in both Full and Half-duplex modes. The boards must be
connected to the Ethernet network with a shielded CAT-5e cable. Use a so-called crossover cable if you want
to connect the Ethernet option board directly to the master appliance.
Use only industrial standard components in the network and avoid complex structures to minimize the length
of response time and the amount of incorrect dispatches.

2 Ethernet Board Technical Data
2-4 Ethernet Option Board /
700.002 735 AE01

3 Installation
Ethernet Option Board /
700.002 735 AE01
3-1
3 Installation
3.1 Installing the Ethernet Option Board in a Converteam LV7000 Unit
Note: MAKE SURE THAT THE FREQUENCY CONVERTER IS SWITCHED OFF BEFORE AN
OPTION OR FIELDBUS BOARD IS CHANGED OR ADDED!
A
Converteam LV7000 frequency converter.
B
Remove the cable cover.
C
Open the cover of the control unit.

3 Installation
3-2 Ethernet Option Board /
700.002 735 AE01
D
Install Ethernet option board in slot D or E
on the control board of the frequency
converter. Make sure that the grounding
plate (see below) fits tightly in the clamp.
E
Make a sufficiently wide opening for your
cable by cutting the grid as wide as
necessary.
F
Close the cover of the control unit and the
cable cover.

3 Installation
Ethernet Option Board /
700.002 735 AE01
3-3
3.2 IP Tool NCIP Config
To begin using the Converteam Ethernet board, you need to set an IP address. The factory default IP address
is 192.168.0.10. Before connecting the board to the network, its IP addresses must be set according to the
network. For more information about IP addresses, contact your Network Administrator.
Once the program is installed successfully, you can launch it by selecting it in the 'Windows' 'Start' menu.
Follow these instructions to set the IP addresses. Select 'Help' 'Manual' if you want more information about
the software features.
Step 1. Scan network nodes. Select 'Scan' 'Configuration' and wait until the devices connected to the bus
in the tree structure are displayed on the left of the screen.
Note: Some switches block broadcast messages, and in that case, each network node must be
scanned separately.
Step 2. Set IP addresses. Change the node’s IP settings according to the network IP settings. The program
will report conflicts with a red color in a table cell.

3 Installation
3-4 Ethernet Option Board /
700.002 735 AE01
Step 3. Send configuration to boards. In the table view, check the boxes for boards whose configuration
you want to send and select 'Configuration', then 'Configure'. Your changes are sent to the network and will
be valid immediately.
3.2.1 Update OPT-CI Option Board program with the NCIP Config Tool
In some cases it may be necessary to update the option board's firmware. Differing from other Converteam
option boards, the Ethernet option board's firmware is updated with the NCIP Config software.
To start the firmware update, scan the nodes in the network according to the instructions in section 3.2. Once
you can see all nodes in the view, you can update the new firmware by clicking the 'VCN Packet' field in
NCIPCONFIG 's right table view.
Click

3 Installation
Ethernet Option Board /
700.002 735 AE01
3-5
After clicking the 'VCN Packet' field, a file open window from where you can choose a new firmware packet is
displayed.
Send the new firmware packet to the option board by checking its box in the 'VCN Packet' field at the right
corner of the table view. After selecting all nodes to be updated by checking the boxes, send the new firmware
to the board by selecting 'Configuration' then 'Configure'.
2
1

3 Installation
3-6 Ethernet Option Board /
700.002 735 AE01
This manual suits for next models
1
Table of contents
Popular Media Converter manuals by other brands

Digital Watchdog
Digital Watchdog DWC-GPLT quick start guide

OBSIDIAN CONTROL SYSTEMS
OBSIDIAN CONTROL SYSTEMS Netron RDM6XL installation guide

Lika
Lika LINEPULS SMI2 Series Mounting instructions

Edimax
Edimax ET-920MCR Specifications

LS
LS iS7 EtherNet/IP user manual

CTC Union
CTC Union FRM220-1000ES-2F user guide