CoolAutomation SMT-131 User manual

SMT - 131
Manual
Ver 2.6
1/6/18

Page 2
Revision History
Version 1 Original Document
Version 1.1 Added Mode select in Modbus
Version 2.0 Based on version 2 Hardware (Firmware 3.0+)
Version 2.1 Added temperature calibration, DI logic and High fan limit.
Version 2.2 Added default daily start temperature (Firmware 3.03+).
Version 2.3 Corrected manual for register 40022 &40023. Added service O/ride on/off
Version 2.4 Added enhancements found in version 3.03 Firmware
Version 2.5 Added Fan Relay lock to 0-10 outputs function. Firmware Version 40.2+.
Version 2.6 Added Sensor Speed response & Sensor Calibration Firmware 40.4+
Index
Index 2
Introduction 3
Thermostat operation 3
Installation - HVAC Control 4
DIP Switch Settings 5
Wiring –HVAC Control 5
Terminal Designations 5
0-10v Outputs 7
Belimo ™ 6 Way Valve 8
2 Pipe Mode 8
Ancillary Functions 9
Occupancy Detection 9
Fault Indication 10
Doorbell 12
Outside Door Station 12
Automatic Day Set Temperature 13
Modbus Wiring 13
Remote Temperature sensors 14
Installer Options Menu 14
Specifications 18

Page 3
Introduction
The Smart Temp SMT-131 thermostat has been designed for use in hotel rooms, guest
accommodation and locations where the user will require a thermostat that is simple to use.
Further, given the nature of the hospitality industry in general it is important that the thermostat
be robust, flexible in function and attractive. The SMT-131 thermostat has been designed with
these important goals is mind.
The SMT-131 also offers advanced energy conservation features such as set point limit control,
automatic un-occupied heating and cooling settings as well as Modbus RTU communications for
integration with the “Building Automation System” (BAS) or “Hotel Check In”system. Additionally,
the SMT-131 seamlessly interfaces with the Smart Temp OC-3D occupancy detection system and
HOT-242 “Door Station” system for added functionality.
Thermostat operation
The SMT-131 is an extremely simple
thermostat to operate and has been
designed to not require a user manual.
The diagram to the left shows all LCD
elements and the 7 buttons (Up / Down /
Make Up Room / Do Not Disturb / On –Off
(mode) / Fan Mode / Deg C-F Select.
Depending on switch and installer menu
settings not all LCD segments or buttons
maybe shown.
On/Off (Mode)
Tap the On/Off button to turn the thermostat On or Off and if permitted to select heat only or cool
only mode. (To ensure the simplest user operation on/off only Mode is set as default).
Note - for simplicity - If the thermostat is OFF by simply touching the thermostat display will turn it
on.
Set Temperature
Adjust the target temperature with the Up or Down button. The range of temperature adjustment
can be limited with the installer setting “heat and cool limit setting”. (See page 15)
Fan
Single fan speed mode (Sw1= Off) (See Dip switch settings page 5)
Tap the fan button to cycle between auto fan and continuous fan mode.
Three fan speed mode (Sw1= On) (See Dip switch settings page 5)
Tap the fan button to cycle between low, medium, high and auto fan speeds. Press and hold the
fan button to turn the fan on continuously.

Page 4
Note. Option 16 in the installer menu (See page 16)permits you to set the SMT-131 to
automatically reset the indoor fan to Automatic Mode (cycle on and off with heating and cooling)
every time the thermostat is turned off and then back on if desired.
If Auto Fan mode is selected, then when the heating and cooling stops, so will the fan (after any
purge periods have expired if set- see page 15)
If Fan On mode is selected, then the fan will continue to run after the heating and cooling stops to
maintain ventilation.
Ventilation Mode
If permitted by DIP Sw7, (See page 5) the user can run the indoor fan only (Ventilation Mode) when
the SMT-131 is off by tapping the fan button. Each tap of the fan button will cycle between all
available fan speeds.
“Make up Room” & “Do Not Disturb” Buttons
When enabled by DIP Sw8, (See page 5) pressing these buttons will activate relevant LCD segments
and backlight colour on the optional outside door station as well as write data to Modbus for
monitoring by a BAS system.
Note - you do not need the outside door stations to be fitted if you simply wish this data to be
presented to Modbus.
Installation - HVAC Control
System Design
Great effort has been taken to make the SMT-131 system intuitive,
reliable and easy to install. Using a common-sense approach to the
installation will ensure this product is installed easily and to the
customer’s satisfaction. Please read and understand this instruction
manual so that installation, testing and commissioning process is
undertaken in an effective and efficient manner.
Opening Wall Controller
Open the SMT-131 wall controller by placing a flat blade screwdriver
or coin in the slot on the bottom of the thermostat case (1) and gently
twist (2) to release the case locking clip. Gently pry the two case halves apart at the base taking
care not to twist the case as this may crack the LCD.
Mounting wall Controller
The SMT-131 should be mounted in a convenient location at approximately 1.2 to 1.5 meters from
the ground. It should be located in a “typical” location where it will sense the accurate room
temperature and not be affected by direct sunlight or drafts.
It is highly recommended that any penetrations in the wall where wiring may pass for example be
sealed to prevent drafts from entering the rear of the thermostat and effecting the room
temperature sensor accuracy.

Page 5
Take care to ensure excess wiring is not trapped between the cases half’s when closing - push
excess wires into the wall cavity. Never press on the LCD when closing the SMT-131 as it may crack.
Always press on the SMT-131 plastic case only.
DIP Switch Settings
Switch
Function
On
Off
Sw1
Indoor Fan Mode
3 Fan Speed
1 Fan Speed
Sw2
Equipment Type
Heat Pump
Heat Cool
Sw3
HP Mode (Sw2= ON)
HC Mode (Sw2=OFF)
Rev Valve Heat (B)
HE –Fan With Heat
Rev Valve Cool (O)
HG –No Fan In Heat
Sw4
2 / 4 pipe mode
2 pipe mode
4 pipe Mode
Sw5
Comp Protection Delay
5 Min Anti Cycle
Immediate Comp start
Sw6
Klixon (Ricardo) Mode
On
Off
Sw7
Ventilation Mode
Permitted
Not Permitted
Sw8
Door Station (Optional)
Fitted
Door Station Not Used
Note: The SMT-131 reads the switch settings on power up only. If you change any DIP switch
settings you must power cycle before these changes will take effect.
It is expected that only qualified people will make adjustment to these dip switch settings.
Knowledge of the HVAC system under the control of the SMT-131 is essential prior to making
adjustment to these DIP switch settings.
Caution Incorrect adjustment of these DIP switch settings could cause HVAC equipment
damage. This would NOT be covered by warranty.
Wiring –HVAC Control
Terminal Designations
Terminal
Function
C
24V Neutral
R
24V Active - This voltage is switched back through the relays
Hi
Indoor Fan High Speed (NOT Used in Single fan speed mode - Sw 1 = OFF)
Med
Indoor Fan Medium Speed (NOT Used in Single fan speed mode - Sw 1 = OFF)
Low
Indoor Fan Low Speed (Used in single & three fan speed mode)
Y
Compressor or Cool - (Based on Sw 2 setting)
W - O/B
Reversing Valve or Heat - (Based on Sw 2 setting)
A1 –Cool
0-10V Output for Cooling (Typically used to control modulating valves)
A2 –Heat
0-10V Output for Heating (Typically used to control modulating valves)
A3 –Fan
0-10V Modulating Output for Indoor DC Fan
Com –0V
0V terminal - Used for 0-10V, sensor or digital inputs ground reference
A
Modbus Data A
B
Modbus Data B
SI
Remote temperature sensor input (Remote / average / Modbus data use)
DI
Digital (Switched input) for forced un-occupied or initiate doorbell function
WC
Window Contact - Forces SMT-131 OFF if window open > 5 min (Adjustable)
DS
Door Switch –Monitors room door status for occupancy detection (see page 11)
PIR
PIR (Movement sensor) input for occupancy detection (see page 11)

Page 6
The SMT-131 is powered by 24VAC and requires the 24VAC
active and neutral to be connected to the “R” (active) and “C”
(Neutral) terminals for the SMT-131 to function. The 24VAC
applied to the SMT-131 “R” terminal is switch back through the
2A relays to the equipment. Note the drawing provided here.
Caution - Although the SMT-131 is a robust device, wiring errors can potentially
damage the thermostat. Warranty does NOT cover this damage. Take care when wiring
24V near sensor inputs or the Modbus communications terminals.

Page 7
Note - When the SMT-131 calls heating or cooling the SMT-131 will drive both the relays and the
0-10V outputs simultaneously. This way the SMT-131 can call a circulating water pump via the
relays as it controls room temperature with valves if needed.
0-10v Outputs
To permit the control of modulating heating and cooling valves as well as variable speed DC fan
motors or variable capacity HVAC systems the SMT-131 has been fitted with 3 x 0-10V outputs.
The 0-10V outputs in the SMT-131 are PI (Proportional Integral) controlled. This control method
provides the most accurate and cost effective way to control heating and cooling valves by ensuring
set temperate are reached as quickly and efficiently as possible while reducing temperature
overshoot.
As the SMT-131 is fitted with both relays as well as 0-10V outputs to control HVAC systems there
may be some slight disparity between the thermostat display and the 0-10V outputs actions. The
SMT-131 displays the relay actions more than the actions of the 0-10V outputs on the LCD. In most
cases these are very closely matched however as the 0-10v outputs have the capability of providing
finer control than do the ON/OFF relays the heating and cooling calls may have started slightly
before indicated on the thermostat display. This is true of the fan also.
A1 –Cool
This output is used to control a cooling valve.
A2 –Heat
This output is used to control a heating valve.
A3 –Fan
This output is used to control a variable speed
fan or a variable capacity AC system. If the fan
mode is set to Auto speed the 0-10V output will
vary between these two values based on
calculated demand. If the user selects LOW
speed, the 0-10V output will be fixed at 3.3VDC, when Medium speed is selected the 0-10V output
will be fixed at 6.6VDC. High speed is set to 10VDC
The installer menu provides the following settings for the control of the three 0-10V outputs.
Span
This is the value where the output is at maximum value. It sets how aggressive the 0-10V will move
for a given temperature change. Range is 0-5C
Time Interval
Time interval sets the running average calculation time. The smaller the number the faster the 0-
10V output will respond to room temperature changes. Range is 10 –300 seconds.
Direction
Forward action 0V = 0% open and 10V = 100% open; reverse action sets 0V = 100% open and 10V
= 0% open.
Minimum Value
Rather than start the output at 0V, when the output is called it will immediately jump to this value.
It will then vary the output to maximum. When approaching set point the value will drop from the

Page 8
minimum value to 0v in 1 step. This setting is particularly useful for fan control as it will not permit
the fan to run too slowly when close to set point.
Maximum Value (Fan A3) output only
When controlling 0-10V fans sometimes it is necessary to limit the fan speed to reduce noise or to
protect ducting. The fan output has a high voltage limit setting so regardless of the user selected
speed (High, Medium or Low) or thermostat selected auto speed the 0-10V output will not exceed
this pre-set high limit.
These settings can be found in the installer menu (starting on page 15)
Belimo ™ 6 Way Valve
Belimo™manufactures an actuator that is in full cooling at 2V, off at 6V and full heating at 10V. To
use this type of actuator with the Smart Temp SMT-131 you must enter the installer menu and set
valve type to “Belimo™ Mode”.
The heating 0-10v output only is used
in this mode
Information on the installer menu can
be found on page 14 of this manual.
As with normal valves, the 0-10V
heating and cooling span settings in
the installer menu scale the heating and cooling outputs. Factory default is full heating and full
cooling 1°C from set point. The heating and cooling span can be adjusted independently to a
maximum of full heating and full cooling 3°C from set point. The output is linear.
Note When using “Belimo” ™ mode, both the A1 “cool” and the A2 “Heat” 0-10 output are used.
Both will provide the same output to the value. (The A3 “fan” output will remain unchanged and
can be used to control a DC fan or other devices).
2 Pipe Mode
The SMT-131 can measure water temperature via a sensor strapped to the water pipe and wired
into the SMT-131 Sensor input terminals (SI and Com 0-10 input). Based on the pipe temperature,
the room temperature and the set point the SMT-131 will control either the heating or the cooling
outputs to maintain guest comfort.
When 2 pipe is mode is used, the SMT-131 will occasionally open the water valve to allow water
flow within the pipe so the SMT-131 can sample pipe temperature to determine / confirm
operation mode.
If mode selection is permitted, the SMT-131 will only permit the appropriate mode to be selected
based on the pipe temperature.
To use the SMT-131 in 2 pipe mode set DIP 2 OFF and DIP 4 to the ON position. Set Installer menu
option 26 “Si & Com 0-V” to option “3” – 2 Pipe Mode. (See page 16)
The pipe sensor needed for 2 pipe mode is the RS-1d sensor - available as an optional part from
Smart Temp or an authorised distributor.

Page 9
Ancillary Functions
The SMT-131 has a number of additional capabilities such as communications with Building
Automation systems via its Modbus communications port. The SMT-131 will automatically control
temperature set points based on occupancy of the room when a suitable door switch and
movement sensor is fitted. The SMT-131 can even automatically shut down the air conditioning
system if balcony doors or windows are left open when the optional door / window switch are
fitted.
When you wish indication of the room status and an integrated doorbell from the hall way outside
the room, the SMT-131 can be fitted with the optional “HOT-243” hall panel.
Complete System Overview
The SMT-131 is the hub of a
compressive room comfort and
energy control system. As shown in
the picture the SMT-131 accepts
door, window and PIR contact inputs
to automatically control
temperature set points. The HOT
243 wall controller mounted in the
hallway outside of the room
provides feedback of the guests
needs to housekeeping plus
provides a convenient button to
activate the SMT-131 internal door
bell.
Regardless of the need to control conferential HVAC systems, 2 or 4 pipe fan coils with modulating
valves the SMT-131 has the necessary outputs to achieve your control needs.
Occupancy Detection
The SMT-131 has sophisticated logic
that when connected to your choice
of movement sensors, door and
window switches will automatically
control the set point and mode of the
SMT-131.
Using part or all the functions
described below are completely
optional. The SMT-131 will function
perfectly as a HVAC controller without the door, window or occupancy detection logic enabled.
There are two types of occupancy detection modes provided by the SMT-131, see latched
occupancy detection on page 11 or PIR only occupancy detection on page 12 of this manual.
DO NOT APPLY EXTERNAL VOLTAGES TO THESE INPUTS

Page 10
Window Contact
The window contact input (WC) is used to automatically disable the HVAC system if a window is left
open. This is done to prevent energy waste by trying to heat or cool an open room.
The SMT-131 window input can be set for a Normally Open (switch open when window is closed)
or normally closed logic (switch closed when window is closed). When the window is left open for
longer than the pre-set time (0 to 300 seconds) the SMT-131 will automatically turn OFF. The text
“OFF” will flash in the LCD to indicate that the remote window (or door switch) is holding the SMT-
131 in off mode. The wall controller will prohibit all changes.
The SMT-131 will automatically restart once the window is closed.
The Installer menu option 28 “Window Input Logic” and option 29 “Window Input Delay” (page16)
sets the window detection logic in the SMT-131.
Fault Indication
The SMT-131 can display the text “FLt” alternating with the temperature should you wish to alert
the user of an external fault with the heating or cooling system.
To enable this function, enter the installer menu and set the Window contact input setting 31 to
option 3. (See page 16 for this setting).
When the WC terminal and the Com-0V terminal are joined the SMT-131 will alternate “FLt” with
the current room temperature.
Register 32 will permit a time delay to be set after the fault signal is received if necessary to reduce
false trips.
The fault indication has NO effect on thermostat function
Door Switch
The Door switch input (DS) is used by the SMT-131 for 3 functions.
1) To detect that the door has been opened and then closed to let somebody into or out
of the room.
2) To detect if the door has been left open.
3) To use as an occupancy or Auto-Off timer in training rooms or similar.
The SMT door switch input can be set for a Normally Open (switch open when door is closed) or
normally closed logic (switch closed when door is closed) or OFF (input not used). The Installer
menu 30 “Door Input Logic” and option 31“Door Input Delay” (page 16)sets the door detection
logic in the SMT-131.
Entering or exiting the room.
Once the door is opened and then closed the SMT-131 will begin its occupancy detection process
using the PIR input described below. Based on the outcome of this process the SMT-131 will remain
on and permit guest interaction with the SMT-131 (adjust mode and set point for example), or
switch to “un-occupied” mode where the SMT-131 will substitute the guest set point and mode for
the installer pre-set values.

Page 11
Door Left Open
When the door is left open for longer than the pre-set time (0 to 300 seconds) the SMT-131 will
automatically turn OFF. The text “OFF” will flash in the display to indicate that the remote door (or
window switch) is holding the SMT-131 in off mode. This is done to prevent energy waste by trying
to heat or cool an open room.
The SMT-131 will automatically restart once the door is closed.
PIR input
A PIR (passive infra-red) movement detector can be directly wired to the SMT-131 “PIR” input. As
movement is detected by the PIR it will send multiple On/Off pulses to the SMT-131 every time it
detects movement. The SMT-131 using this data (with or without a door switch) will determine the
occupancy status of the room and behave accordingly. Note, the PIR must be separately powered,
typically from a 12VDC supply. Consult the PIR manual for this information. Smart Temp do not
provide a PIR sensor, and suitable alarm PIR sensor is suitable.
Latched Occupancy Detection Logic
(Typically used in Hotel applications)
Latched occupancy detection requires a door
switch and PIR input to be wired and working.
When the door is first opened the SMT-131
instantly enters “Occupied Mode” where the
SMT-131 will permit the room occupant to set
their desired temperature and mode of
operation. Once the door is closed the SMT-131
will “look” for movement as detected by the PIR
sensor wired to the PIR input. If no movement is
seen within the installer pre-set seek time
(installer adjustable 1 to 15 minutes) the SMT-
131 will return to “Un-occupied mode” where the users temperature and mode will be replaced
with installer pre-set values. Should movement be detected within the installer pre-set seek time
the SMT-131 will Latch into “Occupied Mode” and no longer rely on continued movement within
the room to remain in “Occupied Mode”. This ensures that the room remains a conditioned space
even if the occupant stops moving or sleeps for example. Next time the door is opened and then
closed again the SMT-131 will again begin its occupancy detection process.
Note - even when the SMT-131 is in “un-occupied mode” it will continue to use the PIR input to
determine room occupancy. For example –in a hotel a couple may be staying in the room and one
leaves the room leaving the other asleep in bed. As the door closes the SMT-131 will seek
movement and when none is found it will enter “un-occupied mode". As the sleeper wakes and
then moves the SMT-131 will automatically re-enter “Occupied Mode” even though it may have
been some time since the door was closed.
Installer option “PIR Input Delay” (page 17 ) sets the PIR mode (On or Off) and the seek time value
(1 to 15 minutes).

Page 12
Using a PIR Only for occupancy Detection
(Typically used in meeting or class room applications)
When you require the SMT-131 to turn the Heating and
Cooling on when people enter a room and off when
people exit the room such as maybe the case in a
conference or class room.
Wire the PIR directly to the DS (door switch input) of the
SMT-131. When movement is detected by the PIR sensor
the SMT-131 will turn the Air conditioning on maintain the
set point. After the last person has left the room the SMT-
131 will wait an installer defined time and then switch to
"Un-Occupied Mode"
Steps to use the SMT-131 in automatic occupancy detection mode.
1. Wire the PIR movement detector into the DS (Door Switch) input.
2. Set the PIR input delay period (See page 17 for information on setting the PIR
input delay) to the number of minutes that you wish the Airconditioning to
run after the last movement has detected in the space.
3. Place a link permanently shorting the PIR input.
Manual Occupancy Input
The DI (Digital Input) & Com 0-10 terminals within the SMT-131 can be used to instantly force the
SMT-131 into “Un-occupied Mode”. This input can be wired to a simple card reader or other 3rd
party system that may be pre-installed for room occupancy detection.
When the SMT-131 is in “Un-occupied Mode” the display will go completely blank except for the
words “Unoccupied” in the top left corner. If the optional HOT-243 hall way panel is installed its
display backlight will go out to let housekeeping know the room is empty. Modbus register 40004
also indicates occupancy status.
Doorbell
A built in doorbell feature is included with the SMT-
131 thermostat. This is normally activated by the
optional outside door station as described above or
via Modbus data link. In circumstances where this
is not convenient the Digital Input (DI) terminals
can be reassigned as a doorbell activation switch
with the digital input options detailed in the
installer menu. (see page 16). Simply place a momentary volt free switch across “DI” and Com “0-
V” terminals to activate the doorbell. Once pressed, the doorbell will chime for about 10 seconds.
Outside Door Station
When coupled with the optional Smart Temp
door station the guest can set the room as
“Do Not Disturb”, call for housekeeping or be
alerted to visiting guests with a pleasant
doorbell chime. Hotel staff are informed
about the room status or guest’s needs by
text information displayed on the door
station LCD or the door station backlight
colours.

Page 13
Connection between the SMT-131 and the hotel door station is cable fitted with RJ12 plugs. Cables
can be provided at additional cost at up to 15 metres maximum. Alternatively, custom cables can
be produced. They are direct wired (not cross over).
When fitting the door station, the SMT-131 DIP Sw8 must be ON. The outside door station will flash
all LCD segments if DIP Sw8 is in the wrong position.
Automatic Day Set Temperature
The SMT-131 can optionally reset the user set point and replace with an installer defined set point
after the SMT-131 has been off for more than 6 hours. This will typically happen after one guest
has checked and before the next guest checks in but will not generally effect a guest who may turn
the thermostat off for a few hours or so or who may go out for the afternoon.
Option 40 in the installer menu defines this Function. Off or a value between 15 and 30c or 59-86F
Modbus Wiring
Modbus communications unlock many additional functions within the SMT-131 thermostat. It also
permits all modes, functions and controls to be remotely supervised and adjusted from a central
location if needed. Modbus object data can be found on page 14 of this manual.
The SMT-131 uses a high-powered Maxim chipset that will “theoretically” permit the connection
of up to 255 devices on a single Modbus node. RF noises and other interferences will reduce the
real world permitted connections to a maximum of 150 ~ 200 in most cases.
Modbus and other communication protocol rely on the quality of cable and good installation
practises to ensure reliable communications. Modbus requires the use of screen cable with the
drain grounded in a single location.
When using a common power supply or when using a modbus master that also powers the SMT-
131, ensure the R (24v active), C (24v common) Data A & B wires are not crossed.
Hint! When the SMT-131 is connected to a working Modbus Network and receiving valid data, the
decimal point in the temperature display will blink. If there is no
communication or the SMT-131 is receiving corrupted data, this
decimal point will remain on steady.
The Modbus data is provided in Addendum 1 at the back of this
manual. (page Error! Bookmark not defined.).
Modbus relies on a series connection and will normally not
tolerate “Star” wiring or “T” branches.

Page 14
Remote Temperature sensors
Occasionally the room thermostat cannot be installed in
the ideal location to measure the room temperature
accurately. In these circumstances the SMT-131 can use
optional remote temperature sensors. These are a two-
wire resistive device,(10K Type II NTC) not polarity
dependent and simply wired into the SMT-131 sensor
inputs terminals (“SI” and “Com 0-V”). Depending on
installer menu sensor settings, (shown on page 16),
remote sensor(s) will either override the SMT-131
onboard sensor or average with the onboard sensor.
Multiple sensors can be used for averaging over larger
areas if necessary.
Wireless (RF) remote sensors are also available if fixed
wiring cannot be installed economically. (P/N RS-W).
Installer Options Menu
The SMT-131 has an impressive list of options that can be installer selected. These options tune the
thermostat’s performance as well as set energy conservation settings. This menu is deliberately
hidden and difficult to enter to discourage unauthorised tampering.
The information card provided in the SMT-131 box provides details on how to enter the SMT-131
menu. If this is lost please contact Smart Temp or an authorised distributor for support.
Navigating Through the Installer Mode Settings
The bottom right button steps forward through the menu options, the bottom left button steps
you backwards.
Adjust your options with the up/down buttons.
Exit the menu saving changes by pressing and holding the
bottom right or wait 3 minutes and the SMT-131 will
automatically exit the installer menu.
The current menu option is shown between the left and right buttons. The example to the right
shows option 3, select deg C (option 0) or F display (option 1).
Note. Option 3 in the installer menu described below sets the SMT-131 native temperature display
format as deg C or Deg F modes. Temperature options in the installer options use the native
temperature format.

Page 15
Option List Table
Option
Setting
0
Buttons Shown
0: Both mode and fan buttons show (default)
1: Show mode but fan button hidden
2: Show fan but mode button hidden
3: Both mode and fan buttons Hidden
Note: If the mode button is hidden, the service and
maintenance staff can turn the SMT-131 on or off by pressing
and holding the lower left of the LCD for 15 seconds. 2 chirps
indicate the SMT-131 has turned ON. 1 chirp indicates the
SMT-131 has turned off (ver 3.03+)
1
Permitted Modes
0: Off / Auto
1: Off / Auto / Heat / Cool
2: Off / Heat /Cool
3: Off / Heat
4 Off / Cool
5: Off / Auto (Display current heating or cooling mode)
2
Room / Set display
0: Show room and set temp (default)
1: Show set temp only
3
Native display format
0: C (default)
1: F
4
C/F button shown on LCD
0: Off(default)
1: On
5
High temp set limit
5C-30C or 41F-86F
6
Low temp set limit
5C-30C or 41F-86F
7
Dead band
0C-5.0C or 0F-10.0F in 0.1C/0.1F steps.
Depending on Option 3 above.
Data format: Dead band * 10
8
Fan Purge Period
0: OFF
1: Fan purge - 1 min
2: Fan purge - 3 min
3: Fan purge - 5 min
4: Fan purge - 10 min
5: Heat only fan purge - 1 min
6: Heat only fan purge - 3 min
7: Heat only fan purge - 5 min
8: Heat only fan purge - 10 min
9: Cool only fan purge - 1 min
10: Cool only fan purge - 3 min
11: Cool only fan purge - 5 min
12: Cool only fan purge - 10 min
9
Fan span
0.5C-3.0C/1.0F-6.0F 0.1C/0.1F steps
Data format: Fan span * 10
10
0-10V Fan Interval (PI)
10-300 seconds 10 seconds' steps (60 seconds default)
11
0-10V Fan direction
0: 0 - 10V –slow to fast (Forward Acting)
1: 10 to 0V –slow to fast (Reverse Acting)
12
0-10V Fan minimum value
(Starting fan voltage when
running)
0 -10V
Data format: 0-10V Fan minimum value * 10

Page 16
13
0-10V Fan Maximum value
(Maximum fan voltage
when running)
0 -10V
Data format: 0-10V Fan minimum value * 10
14
Heat span
0.5C-3.0C/1.0F-6.0F 0.1C/0.1F steps
Data format: Fan span * 10
15
0-10V Heat interval (PI)
10-300 seconds 10 seconds' steps (60 seconds default)
16
0-10V Heat direction
0: 10V is 100% open (forward acting)
1: 0V is 100% open (reverse acting)
17
0-10V Heat minimum
Voltage
0 -10V
Data format: 0-10V Heat minimum value * 10
18
Cool span
0.5C-3.0C/1.0F-6.0F 0.1C/0.1F steps
Data format: Fan span * 10
19
0-10V Cool interval (PI)
10-300 seconds 10 seconds' steps (60 seconds default)
20
0-10V Cool direction
0: 10V is 100% open (forward acting)
1: 0V is 100% open (reverse acting)
21
0-10V Cool minimum
Voltage
0 -10V
Data format: 0-10V Cool minimum value * 10
22
Auto Off Timer
0: No auto off timer
1-10hours 0.5 hour increments.
Data format: hour * 10
23
Un-occupied heat
Set point
0: OFF
5C-30C/41F-86F 0.5C/1F steps
24
Un-occupied cool
Set point
0: OFF
5C-30C/41F-86F 0.5C/1F steps
25
Un –Occupied fan mode
Fan 3 Speed mode
1: Low (Auto) (default)
2: Med (Auto)
3: High (Auto)
4: Low (ON)
5: Med (ON)
6: High (ON)
26
Backlight
0: On with button press Only (Default > ver 3.1)
1: Always On high
2: Low when standby / high when active (Default < ver 3.1)
27
TT sensor (SI & Com)
0: Remote –Use this sensor in place of the fitted sensor.
1: Average –Use both remote and fitted sensor and control to
the average temperature of both sensors.
2: Data –Sensor value used for Modbus only.
3: Duct –Used for 2 pipe mode.
28
Temperature Calibration
+/- 10 deg (C or F)
Adjust to show correct room temp.
29
Digital Input
0: Force Room to Unoccupied Mode
1: Chime Door Bell
30
Digital Input Logic
0: Normally Open
1: Normally Closed
31
Window Input Logic
0: Normally Open
1: Normally closed
2: OFF (Input function disabled)
3: Ver 3.3+ Show FLt (Fault) on LCD (Toggles between
temperature display and “FLt”)

Page 17
32
Window Input Delay
0 - 300 seconds 30 seconds steps (30 seconds default)
33
Door Input Logic
0: Off (default)
1: Normally open
2: Normally close
34
Door Input Delay
0 - 300 seconds 30 seconds steps (180 seconds default)
35
PIR Input Delay
0: Off (default)
1 –15 minutes 1 minute steps (ver 3.3 changed 0-60min)
36
Reset Fan
0: Off
1: On
(resets indoor fan to auto every time mode is set to off)
37
Belimo Mode
0: Off 1: On
38
Modbus Address
1-255
39
Baud rate
1: 4800bps
2: 9600bps (default)
3:19200bps
40
Default Start Temp
Version Ver 3.3+
0=OFF (default) 15~35C or 59~86F
41
Beeper
Version Ver 3.9+
0: Off
1: On (default)
42
Fan Relay Lock
(Version 40.1+)
0:Off (default)
1: On
(This function locks the Fan relay logic to 0-10V outputs –if
enabled depending on other settings it may cause fan to start
and run before heat or cool calls from the W & Y relays.
43
Thermostat response to
changes in room
Temperature Ver 4.04+
0: Very Fast
1: Fast
2: Normal
3: Slow (Default)
4: Very Slow
t
Temperature calibration
Offset Ver 4.04+
-9.9c to +10c 0.0 (Default)
This permits you to apply a correction offset factor to the
room (or remote) temperature sensor used by the SMT-131.
r
Factory Reset
0: NO
1:Yes (Exit to initiate)

Page 18
Specifications
Input Voltage 24VAC 50/60 Htz +/- 15%
Operating Temperature 0°C to 50°C (32°F to 122°F)
Operating RH 0-95% (Non Condensing)
Storage Temperature 0°Cto 65°C (32°F to 150°F)
Size 113 x 103 x 25mm.
Display Size 69.5 x 46.3mm.
Backlight White LED (Other Colours Available Upon Request)
Display Type STN Touch Panel
Relay Rating 30V @ 1Amp Max
0-10V Output Load 10mA Max
Control Range 5°C to 30°C (41°F to 86°F)
Memory Type Non Volatile - Settings Do Not Require Battery Backup
Communications Modbus RTU 4 .8K / 9.6K / 19.2 K
1 Stop Bit, 8 Data Bits, 1 Start Bit. No Parity.
Plastic ABS / Poly Blend –UV Stabilised and Fire Rated
Warranty 3 Year RTB
Table of contents