VR.32 Regulator with CL.2 or CL.2A Control
Auxiliary Current Transformer No. 9061: Installation,
Connections, Calculations and Ordering Information
Supplement 5
Figure 1.
Auxiliary current transformer (part code 9061).
CAUTION ALERTS
Caution alerts in this manual describe haz-
ardous situations that may cause personal
injury and/or property damage if the instruc-
tions in the Caution alerts are not followed.
Caution alerts are highlighted like this:
FIELD INSTALLATION
The auxiliary current transformer assembly
has its own set of lift-off hinges. Installation
consists of mating the hinge halves of the
auxiliary current transformer and the control
box, then mounting the auxiliary current
transformer above the main control.
The auxiliary current transfor~er has an
accuracy of::t 1% with a 25-VA burden at a
70% power factor. The secondary of the
transformer must be short-circuited, using
the short-circuiting block provided, when a
metering device is not connected to the
secondary.
~
& CAUTION
OpentheV1 switchandclosetheC knife
switch to deenergizethecontrolbefore
installing the auxiliary current trans-
former.
INTRODUCTION
These instructions apply to the installation
of the auxiliary current transformer acces-
sory for single-phase, mineral oil-!illed, vol-
tage regulators manufactured by Cooper
Power Systems.
Supplement 5 to Service Information
S225-10-1 (CL-2) or S225-10-5 (CL-2A) VR-
32 Regulator: Operating, Maintenance and
Parts Replacement Instructions, covers field
installation, connections, current calcula-
tions, and parts ordering information for a
McGraw-Edison auxiliary current transformer
No. 9061 (Figure 1) in a CL-2 or CL-2Acontrol
mounted on a VR-32 voltage regulator.
NOTE: A copy of S225-10-1 or S225-10-()
accompanies each VR-32 regulator shipped
by Cooper.
The auxiliary current transformer steps
up the 0.2-amp control current supply to a
usable 2.5-amp or 5.0-amp source for spe-
cial metering purposes.
Only trained and experienced personnel
should install or operate this equipment.
These instructions are written to assist
such personnel, and are not intended to
replace proper training and experience.
These instructions do not claim to cover all
details or variations in this equipment, pro-
cedure, or process described, nor to pro-
vide directions for meeting every possible
contingency during installation and replac-
ing a part in an auxiliary current transformer.
If the personnel installing or replacing a
part in an auxiliary current transformer
needs information about a condition not
covered in these instructions, please con-
tact your Cooper Power Systems represen-
tative.
WARNING/DANGER ALERTS
Warning/Danger alerts in this manual des-
cribe hazardous situations that may cause
death and/or personal injury if the instruc-
tions in the Warning/Danger alerts are not
followed. Warning/Danger alerts are high-
lighted like this:
,&WARNING/DANGER
A Warning/Danger alert describes a
hazardous situation that may cause
death and/or personal injury and gives
instructions on how to avoid death and/
or personal injury.
INITIAL INSPECTION
Each McGraw-Edison auxiliary current
transformer is shippedinacarton designed
to protect the unit from in-transit damage.
Immediately upon receipt of the auxiliary
current transformer:
. Thoroughly inspect the housing and the
wiring to make sure the auxiliary C.T.is
in good condition.
If initial inspection revealsdamage or evi-
dence of rough handling in transit, im-
mediately file a claim with the carrier and
notify your Cooper Power Systems repre-
sentative.
IDENTIFICATION RECORDS
For permanent auxiliary current trans-
former identification, record complete, ac-
curate information, for example:
. VR-32 regulator serial number.
. CL-2 or CL-2Acontrol serial number.
. Aux. C.T.serial number.
. Date auxiliary current transformer was
installed.
CONNECTIONS
Figure 2 is a schematic diagram of the
auxiliary current transformer, showing its
connections and its relationship to the main
control.
The two jumpers on the terminal strip on
the rear of the accessory panel determines
the current available from the auxiliary cur-
rent transformer.
To make appropriate connections:
1. Remove the jumper between C4 and
C3 on the rear panel terminal board
(T81).
2. Connect the primary lead 83 (green) of
current transformer to C4.
3. Connect the F3 (orange) primary lead
toC3.
For selection of desired amp supply, refer
Table 1 for the proper jumper connections.
These instructions do not claim to cover all details or variations in the equipment, procedure, or process described, nor to provide
directions for meeting every possible contingency during installation, operation, or maintenance. When additional information is desired
to satisfy a problem not covered sufficiently for the users purpose, please contact your Cooper Power Systems sales engineer:
October 1991 .Supersedes 10/88 .1:)1991Cooper Power Systems, Inc.
Table 1
Amp Supply and Jumper Connections
- -
Primary to Secondary
Secondary Current
Ratio lamps)
--
1:125 25 Jumpers
F1 to S?
TO UNE-DROP-
COMPENSATIONCIRCUIT
Figure 2.
Schematic diagram.
REMOVEJUMPER-,
:; ;~f GRN-OR"" "
V4V GR L2RL4 ~3! ..
TBI ~
REAR PANEL OF
MAIN CONTROL
---
~
1"-
'-
.
~:- JUMPERS SHORTING
DEVICE
SD2
\ /' ""\
'-.,'METERING r
\ DEVICE /
Figure 3. '-~'
Auxiliary current transformer.
Figure 3 illustrates the physical wiring of the
auxiliary current transformer and the con-
nections that are made from it to the rear
panel signal circuit. The metering device is
connected to S1 and F2 for either amp
supply applications.
CURRENT CALCULATION
The primary current might not be 0.2 amp at
the rated regulator load. This current depends
upon the ratio of the toroidal current trans-
former that is inthe regulator tank and the rated
load amps ofthe regulator. Both of these values
are stamped on the nameplate or found inTable
3 of 8225-10-1 or Table 2-2 of 8225-10-5. '
To determine the actual load current on
the regulator from the reading on the meter-
ing device connected to the auxiliary current
transformer.
1. Identify the current transformer ratio by
checking the regulator rating plate.
2. Examine the jumper positions to deter-
mine the auxiliary current transformer
ratio.
3. Calculate the load amps on the regulator
using the following formula:
Load amps = CT ratio X aux CT ratio X
aux meter reading.
Example
Regulator
rating = 328 amps,7620/13200Y.
CT ratio = 400:0.2.
Aux. CT ratio =1:25. (or 1:12.5)
Auxiliary
meter reading = 3 amps.
400 1
Load amps =Q2X25X 3=240amps.
REPLACEMENT PARTS
Foreaseand accuracy in ordering provide
thedescriptionandthepartcode numberas
listedinTable2.Figure4 showsthe location
ofthese basic parts.
Table 2
Parts Description
~-1
~
CooperPowerSystems
McGraw-Edison'" is a registered trademark of Cooper Industries, Inc. P.O.Box 2850, Pittsburgh, PA 15230
-2n'I"litv frnm ~nnn"r Intil.~trio~

Other Cooper Power Systems Controllers manuals

Cooper Power Systems Kyle Type ME Series Technical specifications

Cooper Power Systems

Cooper Power Systems Kyle Type ME Series Technical specifications

Cooper Power Systems Form 6 Series User manual

Cooper Power Systems

Cooper Power Systems Form 6 Series User manual

Cooper Power Systems mcGraw Edison 9000 Guide

Cooper Power Systems

Cooper Power Systems mcGraw Edison 9000 Guide

Popular Controllers manuals by other brands

Montalvo Z4-UL Technical manual

Montalvo

Montalvo Z4-UL Technical manual

NetApp FAS2050 Installation and setup

NetApp

NetApp FAS2050 Installation and setup

I MUST SCREAM 110 Assembly guide

I MUST SCREAM

I MUST SCREAM 110 Assembly guide

Kobelt 7195 Owner's Operation, Installation & Maintenance Manual

Kobelt

Kobelt 7195 Owner's Operation, Installation & Maintenance Manual

Openpath 2ESH quick start guide

Openpath

Openpath 2ESH quick start guide

Omron E5CC-B instruction manual

Omron

Omron E5CC-B instruction manual

Onbon OVP-M4X user manual

Onbon

Onbon OVP-M4X user manual

Adaptive 1109502601SP quick start guide

Adaptive

Adaptive 1109502601SP quick start guide

Vacon NXP Hardware manual

Vacon

Vacon NXP Hardware manual

Sentiotec Pro C2 Instructions for installation and use

Sentiotec

Sentiotec Pro C2 Instructions for installation and use

zeeltronic PCDI-RGT user manual

zeeltronic

zeeltronic PCDI-RGT user manual

Siemens LOGO! manual

Siemens

Siemens LOGO! manual

CYBELEC CybTouch 6 W user manual

CYBELEC

CYBELEC CybTouch 6 W user manual

Emerson dixell XC650CX Installation and operating instructions

Emerson

Emerson dixell XC650CX Installation and operating instructions

Cumberland Evolution Back-Up owner's manual

Cumberland

Cumberland Evolution Back-Up owner's manual

GE b30 instruction manual

GE

GE b30 instruction manual

Nicolaudie STICK-CU4 manual

Nicolaudie

Nicolaudie STICK-CU4 manual

Vector 40-10 0259 manual

Vector

Vector 40-10 0259 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.