Cooper EG2-NA User manual

EG2-NA
Ethernet Gateway
Installation Guide

Cooper Lighting Solutions EG2-NA 9850-000762-01 2
Please Read This First
The EG2-NA is built and tested to strict safety regulations. By following the steps listed
below and elsewhere within this guide, you can ensure safe installation and operation of
these controller units.
• The EG2-NA must be installed only by a qualied electrician.
• The installation must comply with the appropriate electrical codes and regulations in
force in your area.
• The EG2-NA is designed for indoor installation and use only.
• Ensure that all wiring used conforms fully to local specications and is suciently rated
for the installation.
• All new wiring must be fully veried before applying power.
• The high voltage supply should be fed to the EG2-NA via an external isolation breaker
with sucient capacity for the planned installation.
• Ensure that the supply is fully isolated at an external breaker before removing
the chassis covers. Test that power has been removed before starting to handle
conductors.
• Ensure that high voltage and low voltage wiring remains separate.
Contents
Safety 2
Introduction 3
Dimensions 3
Specication 3
Weight 3
Product Overview 4
Mounting 4
Control Wiring 5
Supply Wiring 5
Setup Instructions 6

Cooper Lighting Solutions EG2-NA 9850-000762-01 3
Introduction
The Ethernet Gateway provides a connection
between an iCAN network and an Ethernet LAN.
This allows a user to control and congure the
iCAN system using iCANsoft on a LAN network
PC or via the internet rather than by connecting
directly into iCANnet
TM
. Where a wireless LAN is
in place (or by connecting a wireless router into
the EG2-NA) the user can access the network
with a Wi-Fi enabled PC running iCANsoft.
The Ethernet Gateway is also the host for the
iCAN series of remote applications including
iOS (iPhone®/ iPod touch®/ iPad®) and a
webserver front end where applications are
downloaded separately. Coupling the EG2-NA
to a WIFI network enables scene control, visual
feedback and modication from your hand held
device.
The Ethernet Gateway also facilitates
connection to the internet when used with
iCANsoft, a rewall, ISP and a Ethernet switch,
this then enables remote connection for
programming & obtaining diagnostics of the
lighting control system.
The built in astronomical timeclock feature
enables preprogrammed timed events for your
lighting system.
Weight
• Packed: 2.6 kg (5.7 lbs)
• Unpacked: 2.4 kg (5.3 lbs)
Dimensions
Specication
Unit requires: 120-240 VAC 50/60 Hz 0.45A 1Ø
Maximum
iCAN network connection
Ethernet connection: Fully transformer isolated
Ambient temperature range: 0°C to 40°C
(32°F to 104°F)
Humidity: 20% to 90% non-condensing
Conguration and sequence memory
Field upgradable FLASH program memory
Internal +15 VDC, 2A power supply

Cooper Lighting Solutions EG2-NA 9850-000762-01 4
Product Overview Mounting
Location and spacing
The EG2-NA should be installed in a dry
ventilated location, where ambient conditions
are maintained within the requirements of the
unit.
The unit has ventilation slots on its sides
to allow convection cooling and under no
circumstances should these be blocked.
Allow 50mm (2”) above and below the unit if
trunking with a depth greater than 50mm (2”)
is used.
Mounting Holes
The unit is provided with four 6mm (1/4in)
diameter xing holes for wall mounting.
The mounting holes can be accessed by
undoing the four screws on the front cover and
removing it.
1. Ethernet Connection
2. CAN ID Button
3. iCAN Network Connector with a green
(power) and yellow (network activity) LED
4. Main Supply Terminal Block
5. Power Supply
6. Reset Button
1
2
3
4
5
6
6.89” (175mm)
7.09” (180mm)
0.25" (6.35mm)
Mounting Holes
4-O.

Cooper Lighting Solutions EG2-NA 9850-000762-01 5
Supply Wiring
Connecting the Supply
This unit requires a 120-240 VAC single phase
supply (live and neutral) with 0.45 A capability.
A terminal block is used to connect the
incoming feed to the internal power supply.
iCAN Network Connections
A removable 5 position terminal block is
provided for the connection of iCAN network
cables. If the EG2-NA is located in the middle of
the network, incoming and outgoing cables will
terminate within the same connector.
iCAN Connectors
Cable type:
iCANnet Cable
Maximum segment distance: 500m (1640 ft)
Devices per segment: 100 (without bridge or
repeater)
Consult Cooper Lighting Solutions for information
on alternative cable types.
Wire Gauge for Supply Terminals
The live, neutral and earth ground power
connections are made to the terminal
block provided for main power connection.
Recommended cable size for live, neutral, and
earth is 26 AWG - 10 AWG.
Live (Gray)
Neutral (Blue)
Earth (Green/Yellow)
Live (Gray)
Neutral (Blue)
Earth (Green/Yellow)
Termination OFF
Termination ON
+12V
(Red)
CAN-H
(White)
SHIELD
(Gray)
CAN-L
(Blue)
0V
(Black)
iCAN
Device
iCAN
Device
EG2-NA
The EG-2-NA has in-built network termination.
If the EG-2-NA is at the end of the network,
ensure the CAN TERM jumper is tted in the
Termination ON position.
iCAN devices are ‘daisy-chained’ on the
network. Spurs from the Network are not
permitted and will result in communications
problems. Devices on an iCAN network can be
wired in any order. Termination is required at
both ends of the network.
T - Indicates where a termination is required.
Function iCANnet Cable Colours
0V Black
CAN L Blue
Shield Silver
CAN H White
+VDC Red

Cooper Lighting Solutions EG2-NA 9850-000762-01 6
Setup Instructions
Ethernet Network
Connect the provided RJ45 (568B) jack to an
Ethernet Switch or Wireless Router.
Conguration
iCAN Device Number
The EG2-NA is supplied with a iCANnet Device
number with Segment number 255 and a node
number in the range 1-255. Both Segment and
Node number can be changed using iCANsoft.
Power Up
The EG2-NA takes approximately 60 seconds
to be ready for use once power is applied. Wait
for the Green CAN LED to ash slowly. The
Green Power LED will double ash continuously
while EG2-NA is on. If Ethernet is connected
the Link and Data LEDs will indicate successful
connection.
Setting the IP Address
The factory set IP Address can be changed
using iCANsoft software either through a direct
PC Node connection through the iCANnet or
directly into the Ethernet port of the EG2-NA.
PC Node Method
Connect a computer running iCANsoft to the
iCAN network using a PC Node. Search the
network and load the EG2-NA into iCANsoft.
Open the EG2-NA device and select the
Ethernet tab. Type in the desired settings.
Select OK or Apply to downoad the changes to
the EG2-NA.
To restore settings back to default, select the
‘Restore Settings’ button. Select OK or Apply
to download the changes to the EG2-NA.
NOTE: The EG2-NA default settings are to
use a xed IP address of 192.168.0.100.
Any device used to communicate with
the EG2-NA will need to be located within
the 192.168.0.x subnet unless IP Address
settings are changed.
Factory Default IP Settings
• IP Address 192.168.0.100
• Mask 255.255.255.0
• Default Gateway 192.168.0.1
• DHCP Off
Ethernet Input

Cooper Lighting Solutions EG2-NA 9850-000762-01 7
Ethernet Port Method
The EG2-NA is supplied from the factory
without DHCP enabled and with a factory
default IP address assigned. In order to
communicate to the EG2-NA using the Ethernet
port, the PC being used must be congured
on the same subnet as the default IP address.
For details of setting the IP address of your
computer consult information online specic to
your Operating System.
If the EG2-NA you are conguring is at the
factory default settings, the following settings
are suggested when assigning a static IP
address to your computer:
Reset to Factory Defaults
Factory defaults may be reset by the following
procedure:
• Remove power from the board.
• Press the CAN ID button and reapply
power. Keep the button pressed until the
CAN LED ashes then stays on. At this
point the Ethernet settings will have been
restored to defaults.
• After setting to factory defaults, the
IP address of the device will revert to
192.168.0.100
Once you have congured your PC’s IP address,
connect the EG2-NA directly to the PC. It may
be necessary to use a crossover cable, however,
most current computers are able to connect
directly to another Ethernet device using a
standard Ethernet cable.
iCANsoft will be used for the conguration
process. Open iCANsoft, then select from the
Toolbar Tools>Options>Network. Select the
Ethernet Gateway option and change the IP
Address to 192.168.0.100. Ensure that the
‘Use Password’ check box is ticked and the
default password: Cooper123 is entered (case
sensitive).
Select OK to conrm.
Search the network and load the EG2-NA into
iCANsoft. Follow the steps outlined in the PC
Node Method section to congure the desired
IP Address for the EG2-NA.
Once the IP Address settings have been applied,
initialize the new settings in the
EG2-NA device by pressing the reset button next
to the Ethernet conneciton or by disconnecting
and reapplying power.
Once conguration is complete, if you will be
using iCANsoft through the ethernet connection,
you will need to update the IP Address in the
Toolbar Tools>Options>Network section to
match the settings you have assigned to the
unit. This screen will also allow you to re-select
the option for PC Node to allow for direct PC
Node access for this database.
Factory Default IP Settings
• IP Address 192.168.0.99
• Subnet Mask 255.255.255.0
• Gateway 192.168.0.1

Document: EG2-NA 9850-000762-01
All products manufactured by Cooper Lighting Solutions are warranted to be free from defects in
material and workmanship and shall conform to and perform in accordance with Seller’s written
specications. For detailed warranty information, contact Cooper Lighting Solutions.
This warranty will be limited to the repair or replacement, at Seller’s discretion, of any such goods
found to be defective, upon their authorized return to Seller. This limited warranty does not apply
if the goods have been damaged by accident, abuse, misuse, modication or misapplication, by
damage during shipment or by improper service.
There are no warranties, which extend beyond the hereinabove-limited warranty,
INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE
IMPLIED WARRANTY OF FITNESS.
No employee, agent, dealer, or other person is authorised to give any warranties on behalf of the
Seller or to assume for the Seller any other liability in connection with any of its goods except in
writing and signed by the Seller. The Seller makes no representation that the goods comply with
any present or future federal, state or local regulation or ordinance. Compliance is the Buyer’s
responsibility.
The use of the Seller’s goods should be in accordance with the provision of the National Electrical
Code, UL and/or other industry or military standards that are pertinent to the particular end use.
Installation or use not in accordance with these codes and standards could be hazardous.
FM 664349
Technical Support
Tel: +44 (0)844 324 9100 (available Mon-Fri 9am-5pm GMT)
Email: [email protected]
Cooper Lighting Solutions
UK
Usk House, Lakeside, Llantarnam Park,
Cwmbran, NP44 3HD, UK
t: +44 (0)1923 495495
www.
cooperlighting.co.uk
US
1121 Highway 74 South
Peachtree City, GA 30269
www.cooperlighting.com
P: 1-800-553-3879
Canada
5925 McLaughlin Road
Mississauga, Ontario L5R 1B8
P: 905-501-3000
F: 905-501-3172