cor thermostat 5 Setup guide

1
TSTPHA01, Côr5
TSTWHA01, Côr5C
TSTPRH01, Côr7
TSTWRH01 Côr7C
Residential Thermostats
Advanced Installation and Configuration
Instructions
Côrr7 N o n -- W i -- F i ,
Côrr7C Wi--Fi Series
(Humidity Control)
Côrr5 N o n -- W i -- F i ,
Côrr5C Wi--Fi
(No Humidity Control)
TABLE OF CONTENTS
PAGE
SAFETY CONSIDERATIONS 2...........................................................................
INTRODUCTION 2.....................................................................................
HOW TO USE THIS DOCUMENT 2.......................................................................
WIRING DIAGRAMS 3..................................................................................
INSTALLATIONS WITHOUT A COMMON (C) WIRE 10......................................................
Repurposing the G wire for the C wire --Single Stage Equipment 10..............................................
EQUIPMENT CONFIGURATION 12.......................................................................
Accessing the Dealer Options Menu 12....................................................................
Configuration Options 12..............................................................................
SYSTEM START--UP AND TEST EQUIPMENT 19...........................................................
Aux Heat 19........................................................................................
Heat 19............................................................................................
Cool 19............................................................................................
To Test Fan 19.......................................................................................
Accessing the Standard Menus 19........................................................................
OPERATIONAL INFORMATION 21.......................................................................
Dehumidification Options 22...........................................................................
Dehumidification Options with Variable Speed Carrier/Bryant equipment 22.......................................
Perfect®Humidity / Ideal®Humidity System technology (Standard Dehumidification + Super Dehumidification) 23.......
Perfect®Humidity / Ideal®Humidity System Technology with FK/FV Fan Coils 24................................
Standard Dehumidification with FV/FK Fan Coils 26.........................................................

2
Standard Dehumidification with FX4 Multi--tap ECM Fan Coils 28..............................................
Ideal Humidity®/ Perfect Humidity®System Technology with Infinity®/ Evolution®Furnaces 29....................
Furnace Dehumidification with Performance / Preferred Furnaces 30.............................................
Furnace Dehumidification with Tapped ECM Motors 30......................................................
Furnace Dehumidification with Carrier 58DLA/DLX, 58CTA/58CTX Models and Bryant 312A(J), 311A(J) Models 31.....
Standrad Dehumidification with Geothermal 31.............................................................
Dehumidification with an Accessory Dehumidifier 32........................................................
TROUBLESHOOTING 33...............................................................................
No Display 33.......................................................................................
Error Codes 33......................................................................................
Frequently Asked Questions 35..........................................................................
SAFETY CONSIDERATIONS
Read and follow manufacturer instructions carefully. Follow all local electrical codes during installation. All wiring must conform to local and
national electrical codes. Improper wiring or installation may damage Thermostat.
Recognize safety information. This is the safety--alert symbol . When you see this symbol on the equipment and in the instruction manual,
be alert to the potential for personal injury.
Understand the signal words DANGER,WARNING,andCAUTION. These words are used with the safety--alert symbol. DANGER
identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in
personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property
damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
INTRODUCTION
The Côr 5 series and Côr 7 series thermostat models are 7--day, 5/2--day, 1--day programmable wall--mounted, low--voltage controls. The Côr
7 and Côr 7C combines temperature and humidity control in the units. The Côr Thermostats have no need for batteries to store
user--configured settings in memory. During power loss its internal memory saves settings for unlimited time, and the clock continues to run
for at least 12 hours.
A Two--Wire Relay Module option for the Côr 7 series thermostats allows them to connect to a system using only two thermostat wires at the
wall. The Two--Wire Relay Module is located near the indoor equipment and two wires are used between the thermostat and the Two--Wire
Relay Module.
HOW TO USE THIS DOCUMENT
The advanced installation and configuration instructions are intended to supplement the standard installation instructions shipped with the
thermostat or available for download on www.HVACpartners.com. The advanced settings and configuration options detailed in this document
are intended for professional installers only. Incorrect configuration may lead to improper operation and equipment damage.
Each section of this document is outlined in the following structure:
Section Title
Location of this section within the thermostat menus.
Image showing available features in this section on the thermostat.
Feature Title
Feature Description
SDefault Configuration
SConfiguration Options
Image showing screen on the thermostat
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF position.
There may be more than 1 disconnect switch. Lock out and
tag switch with a suitable warning label.
!WARNING

3
ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Improper wiring or installation may damage the thermostat.
Check to make sure wiring is correct before proceeding
with installation or turning on unit.
!CAUTION
WIRING DIAGRAMS
The following pages provide wiring diagrams for multiple heating and cooling equipment configurations.
Y/Y2
G
W1
R
C
Y/Y2
C
Fan Coil Heat Pump
R
O/W2/B
G
Y1/W2
Y/Y2
Rc/V+
Rh
C/Vg
W/W1
HUM*
O O
W1
Fan
24VAC Hot Cooling
24VAC Hot Heating
24VAC Common
Aux Heat (Stage 3)
Humidify
Reversing Valve
W2
Heat/Cool (Stage 2)
Heat/Cool (Stage 1) Y1 Y1
Côr 5, Côr 5C, Côr 7, or Côr 7C Thermostat
Humidifier Solenoid
Valve*
* Indicates connection may not be required /available
Fig. 1 -- FV/FK Fan Coil with 2--Stage Heat Pump
G
W2
R
C
Y
C
Fan CoilCôr 5, Côr 5C, Côr 7, or Côr 7C Thermostat Heat Pump
R
O/W2/B
G
Y1/W2
Y/Y2
Rc/V+
Rh
C/Vg
W/W1
HUM*
O
W2
Fan
N/A
Cool Stage 1
24VAC Hot Cooling
24VAC Common
Heat Stage 1
Humidify
24VAC Hot Heating
E
Humidifier Solenoid
Valve*
* Indicates connection may not be required/available
Reversing Valve
Fig. 2 -- Typical Fan Coil with Heat Pump

4
Y/Y2
G
W/W1
R
C
Y2
C
Fan Coil Air Conditioner
R
O/W2/B
G
Y1/W2
Y/Y2
Rc/V+
Rh
C/Vg
W/W1
HUM*
W2
Fan
Cool Stage 1
Cool Stage 2
24VAC Hot Cooling
24VAC Hot Heating
24VAC Common
Heat Stage 1
Humidify
Heat Stage 2
Y1 Y1
Humidifier Solenoid
Valve*
Côr 5, Côr 5C, Côr 7, or Côr 7C Thermostat
* Indicates connection may not be required /available
Fig. 3 -- FV/FK Fan Coil with 2--Stage Air Conditioner
Y
G
W2
R
C
Y
C
Typical
Fan Coil Single-Stage
Air Conditioner
R*
O/W2/B
G
Y1/W2
Y/Y2
Rc/V+
Rh
C/Vg
W/W1
HUM*
W3
* Indicates connection may not be required /available
Fan
N/A
Cool Stage 1
24VAC Hot Cooling
24VAC Hot Heating
24VAC Common
Heat Stage 1
Humidify
Heat Stage 2
Humidifier Solenoid
Valve*
E
Côr 5, Côr 5C, Côr 7, or Côr 7C Thermostat
Fig. 4 -- Typical Fan Coil with Air Conditioner

5
Y
G
W1
R
C
Y
C
Fan Coil Heat Pump
R
O/W2/B
G
Y1/W2
Y/Y2
Rc/V+
Rh
C/Vg
W/W1
HUM*
O ORVS Cooling
Fan
Heat Stage 3
Heat/Cool Stage 1
24VAC Hot Cooling
24VAC Hot Heating
24VAC Common
Heat Stage 2
Humidify E
W2W2
Remove J2
Jumper for
heat staging
Côr 5, Côr 5C, Côr 7, or Côr 7C Thermostat
* Indicates connection may not be required /available
Humidifier Solenoid
Valve*
Fig. 5 -- FV/FK Fan Coil with 1--Stage Heat Pump
*Indicates connection may not be required/available
Fig. 6 -- Typical Fan Coil Heating Only

6
Y/Y2
G
W1
R
C
Y
C
Fan Coil Air Conditioner
R
O/W2/B
G
Y1/W2
Y/Y2
Rc/V+
Rh
C/Vg
W/W1
HUM*
W2Heat Stage 2
Fan
N/A
Cool Stage 1
24VAC Hot Cooling
24VAC Hot Heating
24VAC Common
Heat Stage 1
Humidify
Y1
Remove J2
Jumper for
heat staging
Côr 5, Côr 5C, Côr 7, or Côr 7C Thermostat
Humidifier Solenoid
Valve*
* Indicates connection may not be required /available
Fig. 7 -- FV/FK Fan Coil with 1--Stage Air Conditioner
G
R
C
Y
C
Typical
Fan Coil
Single-Stage
Air Conditioner
R*
O/W2/B
G
Y1/W2
Y/Y2
Rc/V+
Rh
C/Vg
W/W1
HUM*
* Indicates connection may not be required /available
Fan
NA
Compressor High
24VAC Hot Cooling
24VAC Hot Heating
24VAC Common
Heat Stage 1
Humidify
NA
Humidifier Solenoid
Valve*
Côr 5, Côr 5C, Côr 7, or Côr 7C Thermostat
Fig. 8 -- Typical Fan Coil Cooling Only

7
Y/Y2
G
W/W1
R
C
Y/Y2
C
Furnace Heat Pump
R
O/W2/B
G
Y1/W2
Y/Y2
Rc/V+
Rh
C/Vg
W/W1
HUM*
O
** Some heat pumps may designate W 1
W2**
Fan
Heat/Cool (Stage 1)
Heat/Cool (Stage 2)
24VAC Hot Cooling
24VAC Hot Heating
24VAC Common
Aux Heat (Stage 3)
Humidify
Reversing Valve
Y1 Y1
Côr 5, Côr 5C, Côr 7, or Côr 7C Thermostat
Humidifier Solenoid
Valve*
* Indicates connection may not be required /available
Fig. 9 -- Variable Speed, Multi--Stage, Stage Modulating and
Single--Stage Furnace with 2--Stage Heat Pump
Y/Y2
G
W
R
C
Y
C
Furnace
Single Stage
Heat Pump
R
O/W2/B
G
Y1/W2
Y/Y2
Rc/V+
Rh
C/Vg
W/W1
HUM*
O
** Some heat pumps may designate W 1
W2**
Fan
N/A
Heat/Cool (Stage 1)
24VAC Hot Cooling
24VAC Hot Heating
24VAC Common
Heat Stage 2 (furnace)
Humidify
Reversing Valve
Y1
Côr 5, Côr 5C, Côr 7, or Côr 7C Thermostat
* Indicates connection may not be required /available
Humidifier Solenoid
Valve*
Fig. 10 -- Single--Stage Furnace with Heat Pump (Hybrid Heat)

8
Y/Y2
G
W/W1
R
C
Y/Y2
C
Furnace Air Conditioner
R
O/W2/B
G
Y1/W2
Y/Y2
Rc/V+
Rh
C/Vg
W/W1
HUM*
Fan
Cool(Stage 1)
Cool(Stage 2)
24VAC Hot Cooling
24VAC Hot Heating
24VAC Common
Heat Stage1
Humidify
Heat Stage2
Y1 Y1
W2
Côr 5, Côr 5C, Côr 7, or Côr 7C Thermostat
Humidifier Solenoid
Valve*
* Indicates connection may not be required/available
Fig. 11 -- Variable Speed, Step Modulating, Multi--Stage and
Single--Stage Furnace with Two--Stage Air Conditioner
Y
G
W
C
Y
C
Furnace Single-Stage
Air Conditioner
* Indicates connection may not be required/available
O/W2/B
G
Y1/W2
Y/Y2
Rc/V+
Rh
C/Vg
W/W1
HUM*
N/A
Fan
N/A
Cool Stage1
24VAC Hot Cooling
24VAC Hot Heating
24VAC Common
Heat Stage1
Humidify
RR*
Côr 5, Côr 5C, Côr 7, or Côr 7C Thermostat
Humidifier Solenoid
Valve*
Fig. 12 -- Single--Stage Furnace with Single--Speed Air Conditioner

9
Y/Y2
G
W/W1
R
C
Y
C
Furnace Heat Pump
R
O/W2/B
G
Y1/W2
Y/Y2
Rc/V+
Rh
C/Vg
W/W1
HUM*
O
** Some heat pumps may designate W 1
W2**
Fan
Heat Stage 3 (furnace)
Heat/Cool (Stage 1)
24VAC Hot Cooling
24VAC Hot Heating
24VAC Common
Heat Stage 2 (furnace)
Humidify
Reversing Valve
W2
Côr 5, Côr 5C, Côr 7, or Côr 7C Thermostat
* Indicates connection may not be required /available
Humidifier Solenoid
Valve*
Fig. 13 -- Variable Speed, Multi--Stage and Modulating Furnace with Single--Stage Heat Pump
G
W
C
Furnace
* Indicates connection may not be required / available
O/W 2/B
G
Y1/W2
Y/Y2
Rc /V+
Rh
C/Vg
W/W1
HUM *
N/A
Fan
N/A
N/A
24 VAC Hot Cooling
24 VAC Hot Heating
24VAC Common
Heat Stage 1
Humidify
R
Côr 5, Côr 5C, Côr 7, or Côr 7C Thermostat
Humidifier Solenoid
Valve *
Fig. 14 -- Single--Stage Furnace Heating Only

10
Y/Y2
G
W/W1
R
C C
Furnace Air Conditioner
R*
O/W2/B
G
Y1/W2
Y/Y2
Rc/V+
Rh
C/Vg
W/W1
HUM*
* Indicates Connection may not be required /available.
Fan
N/A
Cool Stage 1
24VAC Hot Cooling
24VAC Hot Heating
24VAC Common
Heat Stage 1
Humidify
Heat Stage 2
Y1
Y
W2
Côr 5, Côr 5C, Côr 7, or Côr 7C Thermostat
Humidifier Solenoid
Valve*
Fig. 15 -- Variable Speed, Multi--Stage, Step Modulating and Single--Stage
Furnace with Single--Stage Air Conditioner
Y
G
W
C
Y
C
Furnace Air Conditioner
* Indicates connection ma
y
not be re
q
uired/available
O/W2/B
G
Y1/W2
Y/Y2
Rc/V+
Rh
C/Vg
W/W1
HUM*
N/A
Fan
N/A
Cool Stage1
24VAC Hot Cooling
24VAC Hot Heating
24VAC Common
Heat Stage1
Humidify
R
Côr 5, Côr 5C, Côr 7, or Côr 7C Thermostat
Humidifier Solenoid
Valve*
R
Note: Twist off PCB breakout jumper to
separate Rc and Rh.
Fig. 16 -- Single--Stage Furnace with Air Conditioner and Split Power
INSTALLATIONS WITHOUT A COMMON (C) WIRE
If your current thermostat does not have a wire connected to the C, the following options are available:
1. Repurpose the G wire as a C wire per the instructions below.
2. Use the Add--A--Wire for the Côr 5/5C or Use the Two Wire Relay Module for the Côr 7/7C thermostats.
3. Run an additional wire from the equipment to the thermostat.
Repurposing the G wire for the C wire – Single Stage Equipment
NOTE: Repurposing G wire for the C wire will result in the loss of continuous fan operation and air circulation feature of the thermostat.

11
IMPORTANT: This is only recommended on single stage Gas, Oil or Propane Furnace equipment applications with 4 wires running the
thermostat (R, W, Y, G) and Carrier/Bryant Fan Coils.
1. Use the G wire for the C wire at the equipment.
2. Add a jumper wire from Y (or Y1) to G on the furnace board or Fancoil wiring to allow the blower to turn on during cooling opera-
tion.
3. Connect repurposed wire to the Thermostat.
4. Follow standard installation instructions to complete installation.
NOTE: There will no longer be a wire connected to the G terminal at the thermostat.
Fig. 17 -- Wiring Diagram – Furnace and AC

12
Fig. 18 -- Wiring Diagram – Fan Coil
OPERATION AND SYSTEM HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Advanced settings and configuration options are located in
the dealer options menu. These setting are intended for
professional installers only. Incorrect configuration of the
system may lead to improper operation and system damage.
!CAUTION
EQUIPMENT CONFIGURATION
Accessing the Dealer Options Menu
On the thermostat
1. On the Côr 7/7C thermostats press START if the MENU button is not visible.
2. On the main screen touch and hold the MENU button (about 5 seconds) until the Options Menu is showing SW01 blinking.
Configuration Options -- Description Summary
Only those marked with an asterisk (*) are available to the homeowner through the standard menu’s.

13
CONFIGURATION
OPTIONS DESCRIPTION SUMMARY
Only those marked with an asterisk (*) are available to the homeowner.
SW01 – Equipment Type
SW02 – Clean Filter Timer Adjustment
SW03* – Fahrenheit/Centigrade Selection
SW04 – Fan (G) on with W/W1 Selection
SW05 – Room Air Temperature Sensing (Côr 7/7C only)
SW06 – Cooling Lockout Below 55_F/13_C Selection (only available if outdoor air sensor is present)
SW07 – Zoning
SW08 – Auxiliary Heat Lockout Temperature Setting (only available when heat pump is used and when outdoor air tem-
perature sensor is present)
SW09 – Heat Pump Lockout Temperature Balance Point (only available when outdoor air temperature sensor is present)
SW10 – Reversing Valve
SW11 – Adjustable Setpoint Deadband (not available on heat only and cool only systems)
SW12 – Smart Recovery
SW13 – Room Temperature Offset Adjustment
SW14 – Humidity Offset Adjustment (Only on Côr 7)
SW15 – Enable Auto Mode
SW16 – Cycles Per Hour
SW17 – Time Between Stages
SW18* – Backlight Configuration (Only on Côr 7)
SW19 – Dry Contact (Only on Côr 7)
SW20 – Outdoor Air Temperature Offset Adjustment
SW21* – Keypad Lockout
SW22 – High Cool Latch Temperature
SW23 – High Heat Latch Temperature
SW24* – Programmable/Non—Programmable
SW25* – Number of Programmable Periods per Day
SW26 – Minimum Cooling Setpoint
SW27 – Maximum Heating Setpoint
SW28 – UV Light Reminder
SW29 – Humidifier Pad Reminder
SW30* – Programmable Fan
SW31* – Daylight Savings Time Configuration
SW32 – Furnace Heat Staging
SW33 – Single or Two--Piece Installation
SW34 – Hybrid Heat Furnace Latch
SW35 – Advanced Smart Setback
SW40 – Fan Humidify
SW41 – Variable Speed Blower
SW42 – Variable Speed Super Dehumidification
SW43 – Intelligent Heat Staging
SW44 – Super Comfort Heat
SW99 – Reset to Factory Defaults

14
Configuration Options–Selection
SW01–Equipment Type
Range: H2, A2, HP1, AC1, HH1, HH2, HT, CL
HP2 – operates a two--speed heat pump with a fan coil
HP1 – operates a single--speed heat pump with a fan coil
AC2 – operates a two--speed AC with a fan coil or furnace
AC1 – operates a single--speed AC with a fan coil or furnace
HH1 – operates a single--speed heat pump with a furnace
HH2 – operates a two--speed heat pump with a furnace
HT – operates a heat--only system. Furnace or fan coil only; no outdoor unit.
CL – operates a cool only--system. Outdoor AC unit with an indoor fan coil with no strip heaters.
Default is HP2.
SW02 -- Clean Filter Timer
Select number of months before CHECK FILTER is displayed in the text box on the screen. With OFF selected, the reminder will never come
on, disabling this feature. Time selection can range from 1 to 9 months by selecting numbers 1 through 9. For filter time recommendations,
please consult filter’s Installation Instruction for details.
SW03 -- Fahrenheit/Centigrade
Select between Fahrenheit (F) and Centigrade (C) operation.
Factory default is Fahrenheit (F).
SW04 -- Fan (G) on with W/WI
This selection determines whether fan (G) output is to be On or OFF when any W/W1 (furnace or strip heat) output is On. Most furnaces and
fan coils manage their own blowers and do not require separate G signal. For these applications, select OFF. Some auxiliary heaters require
separate G signal to turn on blower. In this case, select On. Select On for geothermal applications.
Default is OFF.
SW05 -- Room Air Temperature Sensing (with Two--Wire Relay Module installed)
The remote room sensor may be installed as a single sensor or multiple sensors may be installed for further averaging functionality. See Fig.
19.
Fig. 19 -- Remote Room Sensor -- Parallel Wiring
This selection determines which sensor the Thermostat will use for measuring room air temperature. Room air temperature can be sensed in
one of three ways; the local sensor (L) located on the Display Module, the remote room air sensor (r), or the average of local and remote
sensors (Lr). Settings are L, r, Lr.
Default is L.
SW06 —Cooling Lockout Below 55_F/13_C
This selection disables cooling when outdoor temperature is below 55_F/13_C. It requires an outdoor temperature sensor or Wi--Fi
connection with internet weather (internet through Wi--Fi is required and the unit must be registered with location information entered to
obtain internet weather). Setting is not available if valid outdoor sensor is not connected or the thermostat not receiving internet weather
information. Set to OFF to allow cooling below 55_F/13_C. Set to On to prevent cooling below 55_F/13_C.
Factory default is OFF.

15
SW07 —Zoning
This selection should be set to On when the Thermostat is to be used as part of a zoning system. It is assumed that the zoning equipment will
take care of time guard and cycle timers. The minimum On time is still controlled by the Thermostat.
Default is OFF.
SW08 —Auxiliary Heat Lockout Temperature
This selection is available on heat pump systems with a valid outdoor temperature sensor connected or Wi--Fi connection with internet
weather setup. Available settings are: Off, 5, 10, 15, 20, 25, 30, 35, 40, 45, 50, 55.
OFF -- function is disabled. Auxiliary heat is allowed to operate whenever sufficient demand for heat is available.
5to55_F (--15 to 13_C) -- Outdoor temperature above which the auxiliary heat is not allowed to operate (unless MODE is set to Emergency
Heat). If room temperature falls below 45_F(7_C), the auxiliary heat will be allowed to turn on and will continue to run until demand is
satisfied.
Default is OFF.
SW09 —Heat Pump Lockout Temperature Balance Point
Only available when heat pump is used and when outdoor air temperature sensor is present or Wi--Fi connection with internet weather
(internet through Wi--Fi is required and the unit must be registered with location information entered to obtain internet weather).
This selection is only available on Hybrid Heat systems. A Hybrid Heat system is selected via the SW1 Equipment Type configuration.
Configurations settings are: OFF, 5, 10, 15, 20, 25, 30, 35, 40, 45, 50, 55.
OFF — the heating cycle will always start with heat pump heating.
5to55_F (--15 to 13_C) — the outdoor temperature below which heat pump operation is not allowed.
This selection determines which sensor the Thermostat will use for measuring room air temperature. Room air temperature can be sensed in
one of three ways; the local sensor (L) located on the Display Module, the remote room air sensor (r), or the average of local and remote
sensors (Lr). Settings are L, r, Lr.
Default is L.
SW10 —Reversing Valve
This selection is only available on heat pump systems. “O” terminal can be configured to be energized in either heating mode or in cooling
mode, depending on heat pump operation. “O” is used to describe a heat pump system that energizes its reversing valve in cooling. “B” is
used to describe a heat pump system that energized its reversing valve in heating.
H — Reversing valve output (O/W2/B) is energized when HEAT mode is selected.
C — Reversing valve output (O/W2/B) is energized when COOL mode is selected.
Default is C.
SW11 —Deadband Setting Between Heat & Cool
This option is NOT available on Heat Only and Cool Only systems. The selection allows the installer to choose how much differential exists
between the heating and cooling setpoints. Allowable selections are 1 thru 6.
Default is 2.
SW12 —Smart Recovery
Smart Recovery OFF means setpoints change precisely at setback recovery time. 30, 60, or 90 selects the number of minutes recovery starts
before programmed recovery time. Recovery takes place smoothly during the selected recovery time, ending at the recovery time and
temperature which is programmed. Not available when thermostat is configured as non--programmable.
Default is 60.
SW13 —Room Air Temperature Offset Adjust
The number of degrees to be added to the displayed temperature to calibrate or deliberately miscalibrate the measured room temperature (--5
to +5_F).
Default is 0.
SW14 —Humidity Display Offset Adjust
The percentage to be added to the displayed humidity to calibrate or deliberately miscalibrate the measured room humidity (--9% to +9% RH).
Default is 0.
SW15 —Enable Auto Mode
This selection is not available if the Thermostat is configured as Heat Only or Cool Only in SW1. This allows the homeowner to select auto
changeover mode in addition to heat and cool. This allows the Thermostat to automatically change between heating mode and cooling mode
when sufficient demand for heating or cooling exists.
ON — Auto mode is available.
OFF — Auto mode is not available.
Default is ON

16
SW16 —Maximum Cycles Per Hour
This selection limits the number of cycles per hour that the Thermostat allows the system to operate. Selections are 2, 4, 6.
2 — The heating and cooling outputs will be energized no more than 2 times per hour. When an output is energized, it will not be energized
again for 30 minutes.
4 — The heating and cooling outputs will be energized no more than 4 times per hour. When an output is energized, it will not be energized
again for 15 minutes.
6 — The heating and cooling outputs will be energized no more than 6 times per hour. When an output is energized, it will not be energized
again for 10 minutes.
Default is 4.
SW17 —Minimum Time Between Equipment Stages
This selection is only available for heat pump systems. This determines the minimum number of minutes of equipment operation on the
highest compressor stage before allowing the transition to auxiliary heat. Available selections are 10, 15, 20, and 25. The minimum time
between stages of any individual piece of equipment, such as low speed and high speed compressor or fan coil stages, will be fixed at 10
minutes.
Default is 15.
SW18 – not used
SW19 —Dry Contact Configuration (With optional Two--Wire Relay Module)
There are 3 available selections, OFF, 1 and 2.
OFF — The dry contact is always de--energized.
VENT — The dry contact will be energized for the specified number of minutes per hour. This selection is programmable by period. When
this selection is changed from OFF to VENT, Ventilation will be available in the homeowners menu under schedule (from the home screen
tap menu, select when schedule is blinking then the up/dn arrow to ventilation). Wake will be shown above the min/hr. the up/dn arrow will
adjust min/hr between 0 and 60. Press Next to move through the four periods and set the times per period. See Operational Information and
Wiring Diagrams for further explanation of dry contact configuration and use in the Two--Wire Relay Module installation instructions.
DEHUM — The dry contact will operate as a DH relay. This relay is reverse logic. When the humidity level is above the dehumidify setpoint,
the dry contact D1--D2 will be opened. When the humidity level is below the dehumidify setpoint, D1--D2 will be closed. There is a +/-- 2%
hysteresis around the dehumidify setpoint to prevent rapid on/off cycling of the DH output. When configured for dehumidification, the Rc
terminal must be connected to one of the dry contact terminals. This provides power to energize the dehumidify terminal on the cooling
equipment when the dry contact is closed. See Wiring Diagrams for more information.
Default is OFF.
SW20 —Outdoor Air Temperature Offset Adjustment
This selection allows the calibration, or deliberate miscalibration of the outdoor air temperature sensor reading. The selection ranges from --5
to +5_F.
Default is 0.
SW22 —High Cool Latch Temperature
Only available if outdoor sensor is present or Wi--Fi weather is setup for the high cool latch feature.
This selection is only available when SW1 is set to H2, A2, or h2 and when SW7 (zoning) is set to OFF. Configuration settings are OFF, 80,
85, 90, 95, 100, 105, 110, On.
OFF — Cooling always starts in low stage (Y1) and stages up to high stage (Y1 and Y/Y2) when demand is sufficient and staging timer
constraints have been satisfied.
80 to 110_F (27 to 43_C) — Outdoor temperature above which both first and second stages of the compressor are energized to satisfy all
cooling demands. When a cycle starts under a high cool latch, it will finish the cooling cycle on high stage. If the cooling equipment is
energized to satisfy a dehumidify demand only (no cooling demand), the latch will not be applied.
ON — The Y1 and Y/Y2 outputs are simultaneously energized to satisfy all cooling demands.
Default is OFF.
SW23 —High Heat Latch Temperature (only available if outdoor sensor is present)
This selection is only available when SW1 is set to H2, or h2 and SW7 (zoning) is set to OFF. Configuration settings are OFF, 20, 25, 30, 35,
40, 45, 50, On.
OFF —Heating always starts in low stage (Y1) and stages up to high stage (Y1 and Y/Y2) when demand is sufficient and staging timer
constraints have been satisfied.
20 to 50_F(--7to10_C) – Outdoor temperature below which both first and second stages of the compressor are energized to satisfy all
heating demands. When a cycle starts under a high heat latch, it will finish the heating cycle on high stage.
On — The Y1 and Y/Y2 outputs are simultaneously energized to satisfy all heating demands.
Default is OFF.
SW24 —Programmable/Non--Programmable
This selection allows the installer to configure the Thermostat as either programmable or non--programmable. Selections are P, nP.
Default is P.

17
SW25 —Number of Programmable Periods
This selection allows the installer to configure the Thermostat for two or four periods per day. Two periods is a common commercial
application and four periods is more common for residential. This selection is not available if SW24 has been set to nP to configure the
Thermostat for non—programmable operation.
2 PER — Periods WAKE and SLEEP are available
4 PER — Periods WAKE, AWAY, HOME, and SLEEP are available.
Default is 4.
SW26 —Minimum Cooling Setpoint
This selection allows the installer to configure the minimum cooling setpoint that the user is allowed to set. The range is based on the value of
the adjustable deadband SW11, such that the minimum of the range is 50_F/10_C plus the adjustable deadband and the maximum is
90_F/32_C.
Default is 52_F/11_C (based on the adjustable deadband default = 2).
SW27 —Maximum Heating Setpoint
This selection allows the installer to configure the maximum heating setpoint. The range is based on the adjustable deadband value SW11,
such that the minimum of the range is 50_F/10_C and the maximum is 90_F/32_C minus the deadband.
Default is 88_F/31_C (based on the adjustable deadband default = 2).
SW28 —UV Light Reminder
This selection allows the installer to select the number of months after which the UV Light reminder will be displayed to indicate to the
homeowner that it is time to call the dealer to have the UV Lights replaced. Selections available are OFF, 6, 12, 18, 24, 30, 36, 42, 48.
OFF — The UV Light reminder is turned off and will never be displayed.
6 -- 48 — The number of months after which the UV Light reminder will be displayed.
Default is OFF.
SW29 —Humidifier Pad Reminder
This selects the number of months after which the Humidifier Pad Reminder will be displayed. This is not based on run time.
OFF — The Humidifier Pad Reminder is disabled and will never be displayed.
1--24 — The number of months after which the Humidifier Pad Reminder icon will be displayed.
Default is OFF.
SW30 —Programmable Fan
This selection allows the homeowner to program the fan selection to “Auto” or “On” fan operation for each of the program schedule periods.
Also they can program air circulation by period.
OFF — Programmable fan is disabled and the homeowner must manually select “Auto” or “On” for fan operation and there is no option for
air circulation.
On — Programmable fan is enabled. The homeowner can program “Auto” or “On” fan operation along with the heat and cool setpoints for
each programmed period. When the program schedule is running, the programmed heat setpoint, cool setpoint, and fan selection for that
period will be used. If the homeowner “overrides” the programmed fan setting by pressing the fan button, the override selection will remain
in effect until the next programmed period time.
Default is ON.
SW32 —Furnace Heat Staging Control (available only when the Thermostat is configured to operate AC
or A2 equipment).
FURN – The Thermostat controls W1 output only and furnace controls the turn on and turn off of higher stages of heat.
TSTAT – The Thermostat will control the W1 and O/W2/B outputs.
Default is FURN.
SW34 — Hybrid Heat Furnace Latch
This selection allows a Hybrid Heat system to finish a heating cycle using the furnace.
On – Once the furnace is on, it will finish the heating cycle with the furnace. If a heat pump defrost occurs, the heating cycle will finish with
the furnace.
OFF – The system will stage from furnace back to heat pump if heating demand dictates, or 2 minutes after a defrost has ended.
Default is On.
SW35 – Advanced Smart Setback
This selection enables the Advanced Smart Setback algorithm.
On – When transitioning from the Away profile to the Home profile, the system will calculate the amount of time needed to efficiently reach
the desired home setpoint on--time.
OFF – When transitioning from the Away profile to the Home profile, the system will ramp according to the Smart recovery algorithm (30,
60, or 90 minute recovery).
Default is On.

18
SW40 —Humidify Fan
This selection controls whether humidification can only be done when a heating demand is present. If the homeowner turns humidification
OFF, this configuration operates as if the selection was set to OFF.
OFF – The humidity output will only energize when there is a humidity demand and the heating equipment is energized.
On – The humidity output and the fan will energize anytime humidification is needed during heating mode regardless of the state of the
heating equipment.
Factory default is OFF.
SW41 —Variable Speed Blower
This selection allows the installer to select between a single speed or variable motor. In a system with a two speed compressor (A2, h2, H2),
if a dehumidification demand exists and the compressor is energized for cool to dehumidify, cooling, or both, and the system has a PSC
blower (SW41 = OFF), then both Y/Y2 and Y1/W2 are energized.
OFF–Thesystemhasasinglespeed(PSC)blower.
On – The system has a variable speed blower.
Select OFF for geothermal applications.
Factory default is OFF.
SW42 —Variable Speed Super Dehumidification
This option will only be available if the Variable Speed Blower setup (SW41) has been set to ON.
OFF – The fan output (G) is energized when the compressor is on for cool to dehumidify functionality.
On – The fan output (G) is de--energized when the compressor is running for cool to dehumidify functionality. In this setup the fan will run at
very low speed because a Y/Y2 or Y1/W2 is present but the G signal is not. The fan output (G) will be energized any time the compressor is
energized in response to a cooling demand.
Factory default is OFF.
SW43 —Intelligent Heat Staging
This function is only available if the equipment configuration is a single speed heat pump (SW01 = HP).
OFF – Electric heat will not be staged.
On – Three stages of electric heat will be staged.
This switch should be set to On if the HVAC equipment has two banks of strip heaters. When electric heat is required, the thermostat will
energize the smallest bank first (W1 only), then the larger bank (turning the smaller bank off -- Y1/W2 only), and then both banks together
(both W1 and Y1/W2). When power is cycled to the thermostat, this unit configuration will be displayed as HS.
Factory defaults is OFF.
SW44 —Super Comfort Heat
This option is only available on heat pump units HP (HP, H2, hh1, and h2) when SW41 (Variable Speed Blower) is set to On and the system
has a valid outdoor air temperature sensor or Wi--Fi connection with weather setup
OFF – Comfort Heat is off.
On – Comfort Heat feature is on.
If the outdoor air temperature is between 12 to 40_F(--11to4_C) and the compressor is running in heating, then the fan output is turned off.
This will signal the variable speed blower to reduce the air speed. The fan output is turned off even if the user has the fan selection set to
continuous fan. The fan output will be turned back on in this temperature range if the maximum capacity of auxiliary heat is on due to system
demand (auxiliary heat on in response to a defrost signal shouldn’t cause the fan to turn back on).
If the outdoor air temperature is below 12_F/--11_C and there is sufficient demand for the equipment to be on, then the fan output is turned
back on and the W/W1 output is energized. In a two speed unit the Y/Y2 output should be energized in addition to the W/W1 output. This
logic does not apply to a Hybrid Heat system. In the unlikely event that the installer has selected a heat pump lockout temperature (SW09) of
5_F/--15_C in a Hybrid Heat system and the comfort heat feature is on, then the comfort heat feature will turn the W/W1 on and the
compressors off when the outdoor air temperature drops below 12_F/--11_C instead of at the lower temperature of 5_F/--15_C.
NOTE: All temperature boundaries have a +/-- 2_hysteresis.
Factory default is OFF.
SW99 —Reset to Factory Defaults
Use this capability to reset the Thermostat to “out of the box” conditions. BEWARE! All configuration settings, program settings, clock, and
calendar which have been manually entered will be lost! When this option is selected, the configuration number (SW99), will appear on the
left and 10 will appear on the right. To perform the reset, first use the NEXT key to move the box from the SW99 to the 10. Then press and
hold the DOWN key. The 10 will start counting down toward zero. If the DOWN key is kept pressed until the count reaches zero, the reset
will be performed. When the value reaches zero, the room air temperature shall display Fd and “RESETTING..” in the text box. When the
factory defaults have been restored, the Thermostat will act as if power was cycled and return to normal operation. If the DOWN key is
released early, the number will return to 10 and the reset will not occur.
NOTE: If you reset to factory defaults you will need to reconfigure the thermostat for the connected equipment. To reset homeowner
preferences exit the dealer setup menu and select menu from the home screen then select settings and go to item 14 “RST DEFAULT” to reset
user preferences.

19
SYSTEM START--UP AND TEST EQUIPMENT
The Thermostat is designed with a built--in installer test capability. It allows easy operation of equipment without delays or setpoint
adjustments to force heating or cooling. To enable installer Output Test mode, press and hold the fan button for 10 seconds. Pressing the
Heat/Cool button will change the system operating mode to test the heating and cooling equipment based on the equipment setup. Auto Mode
is not available during Installer Test Mode. If no buttons are pressed for 15 minutes, the installer test mode will be terminated. Pressing
Heat/Cool mode button will stop the test but remain in Output Test mode. Pressing DONE or START at any time will exit installer test mode.
Aux Heat – The first stage of Aux Heat will be energize for three minutes, then the first and second stages (if a second stage exists) will turn
on for an additional three minutes. The Aux Heat icon at the top of the screen will be displayed and a text message on the screen will display
STG 1 and count down from 180 seconds. After three minutes the thermostat will go back to Heat/Cool mode to Off. If no buttons are
pressed for 15 minutes, the installer test mode will be terminated.
Heat – The first stage of heating will be energized for three minutes, then the first and second stages (if a second stage exists) will turn on for
an additional three minutes. During the first stage of heating, the HEAT icon will be displayed along with the text “STG 1”. During the
second stage of heating (if one exists), the “STG 2” text will be displayed if the system has a two--stage compressor (A2, h2, or H2 unit
types). The “auxiliary heat on” icon will be displayed if the second stage is electric heat (HP unit type). While the heating test is active, the fan
output (accessory output on the Côr 7 series) can be toggled by pressing Menu then the up/dn arrows to select.
Cool – Output Test for cooling is the same as described for heating above. The COOL icon and the stage text will be displayed during
cooling in Installer Test Mode. While the cooling test is active, the fan output (and accessory output on the Côr 7 series) can be toggled by
pressing Menu then the up/dn arrows to select and toggle them on/off.
To Test Fan
Fan – The fan button switches FAN icon between AUTO and On. While On is displayed, G output will be energized, turning fan on. On
some fan coils, fan continues to operate for 90 sec after G signal is removed.
Accessing the Standard Menus
On the thermostat
1. On the Côr 7/7C thermostats press START if the MENU button is not visible.
2. On the main screen touch MENU button for standard Menus.
3. Menu options are: Schedule, Alerts, Settings, and Wi--Fir.
4. Use the up or down arrows to move through the 4 menu options.
5. Côr 5 touch Next to go into that menu and on Côr 7 touch Select.
Côrr7 N o n -- W i -- F i ,
Côrr7C Wi--Fi Series
(Humidity Control)
Côrr5 N o n -- W i -- F i ,
Côrr5C Wi--Fi
(No Humidity Control)
Fig. 20 -- Côr Thermostats

20
Table 1 – Thermostat Standard Menu Map and Options*
Options:
Schedule PROFILES Enter Heat To and Cool To temperatures by period
PROGRAM All Days, Weekdays/Weekends, Individual days
NUM PERIODS 2or4periods (Wake, Sleep) or (Wake, Away, Home, Sleep)
HOLD PREFER Timed Hold, Permanent, until next Schedule Change
PRGM ENABLE Enabled / Disabled
TOUCH--N--GO Enabled / Disabled
CIRCULATION Minutes / Hr By period
Alerts AIR FILER Off or Number of Months, Dismiss (Yes/No)
UV FILTER Off or Number of Months, Dismiss (Yes/No)
HUM FILTER Off or Number of Months, Dismiss (Yes/No)
LOW TEMP Enable (Yes/No), Limit (50--90_F), Dismiss (Yes/No)
HIGH TEMP Enable (Yes/No), Limit (50--90_F), Dismiss (Yes/No)
AUX RUNTIME Enable (Yes/No), Limit (1--8 hours), Dismiss (Yes/No)
LO HUMIDITY Enable (Yes/No), Limit (5--95%), Dismiss (Yes/No)
HI HUMIDITY Enable (Yes/No), Limit (5--95%), Dismiss (Yes/No)
BAD DEFROST Enable (Yes/No), Dismiss (Yes/No)
EQUIP ISSUE Enable (Yes/No), Dismiss (Yes/No)
EQUIP FAIL Enable (Yes/No), Dismiss (Yes/No)
Settings DATE Date
TIME Time
DST SETUP (Daylight Savings Time) Eastern, Central, etc…(US and Canada zones)
HUMIDIFY Normal (10--44%), Auto (Level 1--9 “window protect”), Off
DEHUMIDIFY Overcool (46--66%), Normal, Off
DST SETUP Daylight Savings Time -- Off, On (select dates)
TEMP UNITS Fahrenheit,Celsius
BACKLIGHT Level 1--5 per period (1=dim, 5=bright)
SCREEN LOCK Off, Level 1, Level 2 (plus password if enabled)
SCRN CLEAN (30 second countdown timer, no buttons)
SCRN COLORS White, Yellow, Pink, Red, Cyan,Green,Blue
RST DEFAULT (Reset Default preferences) Hold for 10 seconds for default settings (excludes system/equipment setup settings)
SERIAL NUM 11--digit serial number
SW VERSION Software version
Wi--FirSETUP N APP Disable, Enable (make thermostat an Access Point)
SCAN Wi--Fi Lists available Wi--Fi networks in the area
Wi--Fi NAME View, Edit, Change
Wi--Fi PASSWD View, Edit, Change
Wi--Fi SECUR WPA2,WEP,Open
REG CODE Requests the Registration code from Server
Wi--Fi STATUS Displays -- No Connect, To Router, To Server
CHK UPDATE Yes -- Forces update of firmware if available
UPDATE INFO Shows status of the firmware update if available
POSTAL CODE Enter postal code for internet weather
Wi--Fi ON/OFF Enable, Disable
MAC ADDRESS Displays the thermostats MAC Address
NOTE: The default settings are underlined if applicable.
*Instructions for most of the setting above are located in the Owner’s Manuals online or the installation instructions.
Other manuals for 5
1
This manual suits for next models
7
Table of contents
Other cor thermostat Thermostat manuals