14.3 Zones
The zones control can be used when DTC 628 is connected in C-Ring with the controllers of the
zones and accordingly is able to know the maximum temperature requested by these circuits (see
Example of Sites 12.3.4). The controller is able to run automatically according to the requirements
of the zones, without the need for its own timed program.
The value of the flow temp. Tm calculated in relation to the demand from the zones can be increased
to ensure that these circuits always have sufficient heat at their disposal.
14.4 Minimum and maximum limits of flow temperature
The desired flow temp. (Tf) calculated by the Compensated control can be limited by a minimum or
maximum value.
Under Compensated, the minimum limit is valid only for the Normal 1…5 room temp. modes.
– Min : xx c : when the temp. falls below the minimum value the controller switches on the boiler
and, using modulating control, keeps the temp. at the value set and switches it off
when the temp. exceeds by 3°C the minimum value.
On "Compensated" it applies only to the Normal Room 1...5 temperatures.
On "zones" it applies only if the desired plants temp. > 0.
– Max : xx c : when the temp. rises above the maximum value the controller uses modulating
control to keep the temp. at the value set and switches off the boiler when the
increase exceeds the 3°C.
Warning: this control system does not replace security measures required
by law.
14.5 Programme and operating mode
It is possible to programme the boiler control according to consumer requirements:
• Program = program in use :
– 7 DAY 1…2 = with one of the two 7day programmes (M2.9…15) ;
– 24 HOUR1…7 = with one of the seven 24hour programmes(M2.2…7) ;
– NORMAL 1…5 xx.x c = with one of the 5 Compensated Normal room temp. (M1.1…5) ;
– SETBACK 1-2 xx.x c = with one of 2 Compensated Setback room temp. (M1.6-7) ;
– FROSTPROT xx.x c = with Compensated Frostprot room temp. (M1.8) ;
– FIXED POINT 1-2 XX.C = with one of the 2 temp. boiler Fixed Point (M1.9-10) ;
– OFF = always Off.
When in place of programme there appears:
– ZONES = M6.1 is ZONES
– ECO OFF = Eco Off is active
– SUMMER = summer period in use (dates in (date in M2.19).
– HOLIDAY = one of holiday periods in use (M2.17).
– SPECIAL = Special period in use.
– REMOTE NORMAL 1 = remote control A is on "NORMAL 1".
– REMOTE SETBACK 1 = remote control A is on "SETBACK 1".
– REMOTE FLOW 1 = remote control A is on"FLOW 1".
– REMOTE FROSTPROT = remote control A is on "FROSTPROT".
– REMOTEOFF = remote control A is on "OFF".
The operating mode depends on programme set in M0.2 o or by the external controls:
• Mode = operating mode in use :
– Zones = M6.1 is ZONES
– Normal = with one of the 5 Compensated Normal room temp.
– Setback = with one of the 2 Compensated Setback room temp.
– Frostprot = with Compensated Frosprot room temp.
– Fixed point = with one of 2 temp. boiler Fixed Point ;
– Off = boiler switched off by programme.
• Tv xx.x c = value of desired temp.
• Var ± x.x c = variation in desired temp. (room max ±3.0°C, flow max ± 50.0 °C).
14.6 Eco Off function
This function permits switching off the boiler when outside temperature above value set and switching
it on again when it is 2°C below value set.
• Burner Off : – NO : function not enabled ; – YES: function enabled
• Outside T : x,x c : value of outside temp. for switching off boiler.
M6.1
T y p e o f c o n t r o l
Z O N E S
M1.12
I n c r e a s e T B o i l e r
f o r z o n e s : x x . x c
M4.5
F l o w T l i m i t s
M i n : x x c M a x : x x c
M0.2
P r o g r a m :
2 4 H O U R 1
M0.3
M o d e : N O R M AL
T d 2 0 . 0 c V a r ± 0 . 0 c
M1.13
B u r n e r O f f : N O
O u t s i d e T : 3 . 0 c