We reserve the right to make changes without notice
FOR CONTROL OF VALVE OR BURNER
• Analogue controller for boiler plant:
– 1 modulating or On-Off output for control valve or burner
– 1 On-Off output for control pump or burner in relation to programmed times
– voltage-free output contacts
– adjustment of heating curve to compensate for weather variations in intermediate seasons
– possibility of adjusting value of desired ambient temperature by remote control
• Power supply 230 V~; installation on 144 x 144 control panel back plate
RTE 98. controller is designed for winter compensated control in medium and large central heating plants for
– administrative and commercial centres
– schools and public buildings
It is suitable for all climatic zones and for any type of heating media:
RTE 98. controls mixing or diverting valves operated by reversible electric actuators with three-wire control and
opening times of from 90 to 630 seconds, or the boiler burner.
The main functions of RTE 98. are:
• Winter regulation of the flow temperature in relation to the outside temperature with:
– adjustment of heating curve to compensate for weather variations in intermediate seasons
• Modulating three-wire control or On-Off
• Control plant pump from timed programme in use
• Timed programming: 24-hour (RTE 982) or 7-day (RTE 983)
• Remote control for adjusting temperature programmed on controller
• Timed control : RTE 98 is able to control an On-Off output which operates with the program times used. It can be
used for the control of the plant circulation pump : in the Normal "Sun" periods contacts 8-10 are closed, while in
the Setback "Moon" periods contacts 8-10 are open.
4. DETECTORS & ACCESSORIES
No. Description Type Sensing element Code Data sheet
No. Description Type Sensing element Code Data sheet
1 Surface plant flow temperature detector
1 Surface plant flow temperature detector
1 Outside temperature detector
1 Outside temperature detector
No. Description Type Sensing element Code Data sheet
1 Surface plant flow temperature detector
1 Outside temperature detector
No. Description Type Sensing element Code Data sheet
No. Description Type Sensing element Code Data sheet
No. Description Type Sensing element Code Data sheet
No. Description Type Sensing element Code Data sheet
Compensating controller with 24-hour time switch
Compensating controller with 7-day time switch
Compensating controller with 7-day time switch
– minimum daily interval 15 min.
– minimum weekly interval 24 h
Suitable actuators 90...630 s
Room humidity Class F (DIN 40040)
Electromagnetic compatibility CEE 93/68
– maximum switched voltage 250 V~
– maximum switched current 5 (1) A
– Normal and Setback ambient temperature 0...30 °C
– adjustment C curve ± 5 °C