Cumberland SP-MODULE User manual

SP-MODULE
Static Pressure Module
USER'S MANUAL
M 890-00102 rev. 04
REV. 00

2SP-MODULE rev.04
TABLE OF CONTENTS
PRECAUTIONS ....................................................................... 3
INSTALLATION ...................................................................... 4
Description of the SP-MODULE ............................................... 4
Installing the Module on the Wall ............................................. 4
Connecting the Sensor .......................................................... 7
Connecting the Output Wire ................................................... 8
USING THE SENSOR ................................................................ 9
Description of the SP-MODULE ............................................... 9
TECHNICAL SPECIFICATIONS ................................................ 10
WIRING DIAGRAMS ............................................................. 11

3
SP-MODULE rev.04
PRECAUTIONS
The room temperature where the module is located MUST ALWAYS
REMAIN BETWEEN 32°F AND 104°F (0°C TO 40°C).
To avoid exposing the module to harmful gases or excessive humid-
ity, it is preferable to install it in a corridor.
DO NOT SPRAY WATER ON THE MODULE
FOR CUSTOMER USE
Enter the serial number located on
the side of the module below for
future reference.
Model number:
Serial number:
SP-MODULE

4SP-MODULE rev.04
DESCRIPTION OF THE SP-MODULE
The SP-MODULE is capable of measuring low pressures with a ±1%
accuracy - ideally suited for proper building pressurization and air
flow control. Transmitters can withstand up to 10 psig overpressure
with no damage to the unit. Variable capacitance sensor design
provides excellent sensitivity and long-term stability.
INSTALLING THE MODULE ON THE WALL
One module should be mounted on a wall indoors at each point
where the low voltage cable enters and exits a building, preferably in
a location where humidity and dirt levels are not too high. Isolate the
module from vibrations because the axis prependicular to the mount-
ing base is sensitive to vibrations. In most cases, preferred installa-
tion is with the baseplate mounted vertically and located on a
relatively flat surface in a junction box or attached to a nearby
beam.
The axis most sensitive to vibration is the one perpendicu-
lar tothe mounting base. Avoid mounting with maximum
vibration along this axis.
Pressure Fitting: Both the positive (high) pressure port and the
reference (low) pressure port are located on the top face of the unit,
labeled High and Low respectively. For best results (shortest re-
sponse times), 3/16" I.D. tubing is suggested for tubing lengths up to
100 feet long, 1/4" I.D. for tubing lengths up to 300 feet, and 3/8"
I.D. for tubing lengths up to 900 feet.
Open the module cover by removing the top cover screws (see Fig.1,
Item A). There are 2 mounting holes (Fig. 1, Item B). These holes
accept M4 or M5 screws. Figure 2 gives the mounting hole pattern.
INSTALLATION
!
WARNING

5
SP-MODULE rev.04
SP-MODULE
Do NOT install or use a damaged module. Contact your
distributor to obtain another unit.
Take a few moments to write the complete serial number
found on the side of the module on page 1 of this manual. This
will be useful for future reference.
A
A
A
A
B
B
Fig. 1 Exploded view of the SP-MODULE
!
WARNING
3.75 in
(95 mm)
3 in
(76 mm)
4.8 in
(122 mm)
12 SP-MODULE rev.04
WIRING DIAGRAMS
-
+
+
COM OUT
LOW
HIGH
EXC
-
+
RECIVER LOAD
MAIN
CONTROLLER
RECEIVER LOAD

6
SP-MODULE
SP-MODULE rev.04
ATTIC
AIR INLET:
“REFERENCE” AIR OUTLET:
“ROOM”
LOOP TO TRAP HUMIDITY LOOP TO TRAP
HUMIDITY
1/4” (0.6cm)
DIAMETER TUBE
1/4” (0.6cm)
DIAMETER TUBE
40"
(100cm)
PLASTIC
INSECT FILTER
PLASTIC
INSECT FILTER
Pressure Fitting
3/16"I.D for tubing lengths up to 100 feet long
1/4" I.D. for tubing lengths up to 300 feet
3/8" I.D. for tubing lengths up to 900 feet
*
**
Fig. 3 Installation of the SP-MODULE
Always make loops in the inlet and outlet tubes. If this is not
done, humidity may permanently damage the sensor.
!
WARNING
Fig. 2 Mounting hole pattern
Figure 3 shows how to install the SP-MODULE. The end of the outlet
tube must be placed in the ventilated room with the plastic filter pro-
vided. This filter prevents insects from entering the tube.
The end of the inlet tube must be installed with the plastic filter away
from drafts.The attic can generally be used as a reference. To deter-
mine if the attic is an adequate reference, read the pressure difference
between the attic and outside. It should be close to zero.
Make a loop in both tubes (room and reference) to trap humidity (Fig. 3).
11
SP-MODULE rev.04
TECHNICAL SPECIFICATIONS
Type SP-MODULE
Accuracy: ±1% of full scale (RSS) (includes non-
linearity, hysteresis, and non-repeatability
Nominal operating voltage: 14-28 VDC, 13-24 VAC 50/60 Hz
Operating current: 20 to 50 mA
Output 4 TO 20mA, 2-wire
Maximum pressure: 10 psig (0.7kg/cm2)
Loop Resistance: 0-800 ohms
Supply Voltage: 12-30 VDC
Zero and Span Adjust: ±1mA, non-interactive
Compensated Temperature
Range: 0 to 150°F (-18 to 65°C)
Thermal Effects: 0.033% FS/°F (0.018% FS/°C)
Housing: IP54, plastic casing
Weight: 0.35 kg (unpacked)
Dimensions (LxWxH): 114 x 114 x 85 mm
Operating temperature: 0 to 150°F (-18 TO 65°C)
Storage temperature: -40to 185°F (-40 to 85°C)
Pressure Connection: 3/16" O.D. fitting for 1/4"I.D tubing
Minimum Supply Voltage: 12+0.02x(resistance of receiver plus line)
Maximum Supply Voltage: 30+0.004x(resistance of receiver plus line)
The unit is calibrated at the factory using a 250 ohm load at 28VDC

7
SP-MODULE rev.04
SP-MODULE
Connecting the Sensor
To connect the sensor, refer to the wiring diagram. Make sure the
power supply is suitable for the sensor (see technical specifications at
the end of this manual).
WARNING. All wiring must be done by an authorized elec-
trician according to all applicable codes, laws and regula-
tions. Make sure that the power is off before doing any
wiring or opening the sensor to avoid electrical shocks and
equipment damage.
Pass all wiring through the bottom of the enclosure. Do
not drill holes on the side or the top of the enclosure as this
may allow water to enter the enclosure.
To punch holes through the bottom, use a hammer and punch to carefully
punch the holes you need.
Never mount the sensor near water or rain pipes, as failure
of these pipes may cause strong water jets to reach the
sensor.
Do not under any circumstances change the setting of the
calibration potentiomenter inside the enclosure. This will
decalibrate the pressure gauge.
Do not install ends of inlet (reference) and outlet (room)
tubes in walls, in insulation, in a humid environment or near
walls affected by drafts.
!
WARNING
!
WARNING
10
SP-MODULE
SP-MODULE rev.04
Span Adjustment (Complete the zero adjustment before setting span):
Span on full scale output adjustments should only be performed by using
an accurate pressure standard (electronic manometer, digital pressure
gage, etc.) with at least comparable accuracy to the SP-Module (668
Series) (<±1% full scale). With full scale pressure applied to the high
pressure port (reference port open to atmosphere) adjust span to achieve
20 mA output.
Example 1 : Unidirectional pressure range of 0 to 1"W.C. Apply
1.00"W.C., adjust span to 20 mA.
Notes: The input is reverse-voltage protected. The output is internally
protected against damage if shorted to ground. Recheck all
connections before applying power.

8
SP-MODULE
SP-MODULE rev.04
Connecting the Output Wire
The sensor must be connected to the main controller according to the
wiring diagram. The cable may be a 3-core low voltage shielded cable
and may be extended up to 1000ft (300 meters) (if the wire diameter is
at least 18 AWG ( .64 mm)). The recommended wire diameter for
extending sensor cables is 1.0mm.
- When extending an output wire, solder all connections.
- Never run low voltage cables parallel to high voltage wires
to prevent interference.
- Output cables must cross power cables at a 90° angle.
ALWAYS switch power to the sensor OFF before opening
the sensor.
9
SP-MODULE rev.04
USING THE SENSOR
Description of the SP-MODULE
The SP-MODULE has one output:
- 4-20mA signal
Output
current
Pressure
Difference
20mA
4"
0
4mA
Fig. 4 Output current vs pressure difference
Calibration: The SP-Module (668 Series) is factory calibrated and should
require no field adjustment. However, both zero and span adjustments
are provided. Whenever possible, any zero and/or span offsets should be
corrected by software adjustment in the user's control system. Use the
zero and span adjustments on the SP-Module (668 Series) only if abso-
lutely necessary. The SP-Module (668 Series) is calibrated in the vertical,
position the unit and follow the zero adjustement procedure listed below.
Pressure ranges are fixed and cannot be changed in the field.
Zero Adjustment: While monitoring the current output with both pressure
ports open to atmosphere, the zero may be adjusted. For unidirectional
pressure ranges, turn the zero adjustment screw until a reading of
4mA (±0.15 mA) is achieved.

8
SP-MODULE
SP-MODULE rev.04
Connecting the Output Wire
The sensor must be connected to the main controller according to the
wiring diagram. The cable may be a 3-core low voltage shielded cable
and may be extended up to 1000ft (300 meters) (if the wire diameter is
at least 18 AWG ( .64 mm)). The recommended wire diameter for
extending sensor cables is 1.0mm.
- When extending an output wire, solder all connections.
- Never run low voltage cables parallel to high voltage wires
to prevent interference.
- Output cables must cross power cables at a 90° angle.
ALWAYS switch power to the sensor OFF before opening
the sensor.
9
SP-MODULE rev.04
USING THE SENSOR
Description of the SP-MODULE
The SP-MODULE has one output:
- 4-20mA signal
Output
current
Pressure
Difference
20mA
4"
0
4mA
Fig. 4 Output current vs pressure difference
Calibration: The SP-Module (668 Series) is factory calibrated and should
require no field adjustment. However, both zero and span adjustments
are provided. Whenever possible, any zero and/or span offsets should be
corrected by software adjustment in the user's control system. Use the
zero and span adjustments on the SP-Module (668 Series) only if abso-
lutely necessary. The SP-Module (668 Series) is calibrated in the vertical,
position the unit and follow the zero adjustement procedure listed below.
Pressure ranges are fixed and cannot be changed in the field.
Zero Adjustment: While monitoring the current output with both pressure
ports open to atmosphere, the zero may be adjusted. For unidirectional
pressure ranges, turn the zero adjustment screw until a reading of
4mA (±0.15 mA) is achieved.

7
SP-MODULE rev.04
SP-MODULE
Connecting the Sensor
To connect the sensor, refer to the wiring diagram. Make sure the
power supply is suitable for the sensor (see technical specifications at
the end of this manual).
WARNING. All wiring must be done by an authorized elec-
trician according to all applicable codes, laws and regula-
tions. Make sure that the power is off before doing any
wiring or opening the sensor to avoid electrical shocks and
equipment damage.
Pass all wiring through the bottom of the enclosure. Do
not drill holes on the side or the top of the enclosure as this
may allow water to enter the enclosure.
To punch holes through the bottom, use a hammer and punch to carefully
punch the holes you need.
Never mount the sensor near water or rain pipes, as failure
of these pipes may cause strong water jets to reach the
sensor.
Do not under any circumstances change the setting of the
calibration potentiomenter inside the enclosure. This will
decalibrate the pressure gauge.
Do not install ends of inlet (reference) and outlet (room)
tubes in walls, in insulation, in a humid environment or near
walls affected by drafts.
!
WARNING
!
WARNING
10
SP-MODULE
SP-MODULE rev.04
Span Adjustment (Complete the zero adjustment before setting span):
Span on full scale output adjustments should only be performed by using
an accurate pressure standard (electronic manometer, digital pressure
gage, etc.) with at least comparable accuracy to the SP-Module (668
Series) (<±1% full scale). With full scale pressure applied to the high
pressure port (reference port open to atmosphere) adjust span to achieve
20 mA output.
Example 1 : Unidirectional pressure range of 0 to 1"W.C. Apply
1.00"W.C., adjust span to 20 mA.
Notes: The input is reverse-voltage protected. The output is internally
protected against damage if shorted to ground. Recheck all
connections before applying power.

6
SP-MODULE
SP-MODULE rev.04
ATTIC
AIR INLET:
“REFERENCE” AIR OUTLET:
“ROOM”
LOOP TO TRAP HUMIDITY LOOP TO TRAP
HUMIDITY
1/4” (0.6cm)
DIAMETER TUBE
1/4” (0.6cm)
DIAMETER TUBE
40"
(100cm)
PLASTIC
INSECT FILTER
PLASTIC
INSECT FILTER
Pressure Fitting
3/16"I.D for tubing lengths up to 100 feet long
1/4" I.D. for tubing lengths up to 300 feet
3/8" I.D. for tubing lengths up to 900 feet
*
**
Fig. 3 Installation of the SP-MODULE
Always make loops in the inlet and outlet tubes. If this is not
done, humidity may permanently damage the sensor.
!
WARNING
Fig. 2 Mounting hole pattern
Figure 3 shows how to install the SP-MODULE. The end of the outlet
tube must be placed in the ventilated room with the plastic filter pro-
vided. This filter prevents insects from entering the tube.
The end of the inlet tube must be installed with the plastic filter away
from drafts.The attic can generally be used as a reference. To deter-
mine if the attic is an adequate reference, read the pressure difference
between the attic and outside. It should be close to zero.
Make a loop in both tubes (room and reference) to trap humidity (Fig. 3).
11
SP-MODULE rev.04
TECHNICAL SPECIFICATIONS
Type SP-MODULE
Accuracy: ±1% of full scale (RSS) (includes non-
linearity, hysteresis, and non-repeatability
Nominal operating voltage: 14-28 VDC, 13-24 VAC 50/60 Hz
Operating current: 20 to 50 mA
Output 4 TO 20mA, 2-wire
Maximum pressure: 10 psig (0.7kg/cm2)
Loop Resistance: 0-800 ohms
Supply Voltage: 12-30 VDC
Zero and Span Adjust: ±1mA, non-interactive
Compensated Temperature
Range: 0 to 150°F (-18 to 65°C)
Thermal Effects: 0.033% FS/°F (0.018% FS/°C)
Housing: IP54, plastic casing
Weight: 0.35 kg (unpacked)
Dimensions (LxWxH): 114 x 114 x 85 mm
Operating temperature: 0 to 150°F (-18 TO 65°C)
Storage temperature: -40to 185°F (-40 to 85°C)
Pressure Connection: 3/16" O.D. fitting for 1/4"I.D tubing
Minimum Supply Voltage: 12+0.02x(resistance of receiver plus line)
Maximum Supply Voltage: 30+0.004x(resistance of receiver plus line)
The unit is calibrated at the factory using a 250 ohm load at 28VDC

5
SP-MODULE rev.04
SP-MODULE
Do NOT install or use a damaged module. Contact your
distributor to obtain another unit.
Take a few moments to write the complete serial number
found on the side of the module on page 1 of this manual. This
will be useful for future reference.
A
A
A
A
B
B
Fig. 1 Exploded view of the SP-MODULE
!
WARNING
3.75 in
(95 mm)
3 in
(76 mm)
4.8 in
(122 mm)
12 SP-MODULE rev.04
WIRING DIAGRAMS
-
+
+
COM OUT
LOW
HIGH
EXC
-
+
RECIVER LOAD
MAIN
CONTROLLER
RECEIVER LOAD

SP-MODULE
Static Pressure Module
USER'S MANUAL
M 890-00102 rev. 04
REV. 00
Table of contents
Other Cumberland Control Unit manuals
Popular Control Unit manuals by other brands

Bosch
Bosch rexroth M1-16 Series instruction manual

CALEFFI
CALEFFI 5213TM series Installation, commissioning and servicing instructions

Supermicro
Supermicro SuperBlade SBI-6419P-C3N user manual

Franke
Franke F5EV1013 Installation and operating instructions

GE
GE 10000 instruction manual

Emerson
Emerson Fisher 8580 instruction manual

Allen-Bradley
Allen-Bradley 1757-FFLD user manual

CIRCUIT DESIGN
CIRCUIT DESIGN CDP-RX-07M Operation guide

Siemens
Siemens Cerberus Pyrotronics NIM-1M installation instructions

Powerware
Powerware 9125 PowerPass user guide

metso automation
metso automation Eliminator 9FB-3600XT Installation maintenance and operating instructions

GRAUPNER
GRAUPNER 3975 manual