CyberPower CPS1000E-FR User manual

K01-0000234-01
CPS1000E-FR
User’s Manual

2
SAFETY AND EMC INSTRUCTIONS
This manual contains important safety instructions. Please read and follow all instructions carefully
during installation and operation of the unit. Read this manual thoroughly before attempting to unpack,
install, or operate your Emergency Power System (EPS).
CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity controlled
indoor area free of conductive contaminants. (Please see specifications for acceptable temperature
and humidity range).
CAUTION! To reduce the risk of electric shock, do not remove the cover, except to service the battery.
There are no serviceable parts inside, except for the battery.
CAUTION! EPS must be connected to an AC power outlet with circuit breaker protection. Do not plug
into an outlet that is not grounded. If you need to de-energize this equipment, turn off and unplug the
unit.
CAUTION! To avoid electrical shock, turn off the unit and unplug it from the AC power source before
servicing EPS, replacing the external battery or installing equipment.
CAUTION! To reduce the risk of fire, only connect the EPS to a circuit with 10 amperes maximum
branch circuit over-current protection in accordance with the CE requirement.
CAUTION! The building wiring socket outlet (shockproof socket outlet) must be easily accessible and
close to the EPS.
CAUTION! Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your
equipment) to connect the EPS to the building wiring socket outlet (shockproof socket outlet).
CAUTION! Please use only VDE-tested, CE-marked power cables to connect the loads to the EPS.
CAUTION! When installing the equipment, ensure that the sum of the leakage current of the EPS and
the connected equipment does not exceed 3.5mA.
CAUTION! Do not disconnect the mains cable on the EPS or the building wiring socket outlet
(shockproof socket outlet) during operations since this would remove the protective ground of the EPS
and of all connected loads.
DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT!
DO NOT use in any circumstance that would affect operation and safety of any life support equipment,
any medical applications or patient care.
DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire or electric shock, do not use
with or near an aquarium. Condensation from the aquarium can cause the unit to short out.
DO NOT INSTALL THE EPS WHERE IT WOULD BE EXPOSED TO DIRECT SUNLIGHT OR NEAR
HEAT!
DO NOT BLOCK OFF VENTILATION OPENINGS IN THE EPS’S HOUSING!
SAFETY:
EN62040-1-1
EMI:
Conducted Emission: IEC/EN 62040-2…Category C2
Radiated Emission: IEC/EN 62040-2……Category C2
Harmonic Current: IEC/EN61000-3-2
Voltage Fluctuations and Flicker: IEC/EN61000-3-3

3
EMS:
IEC/EN61000-4-2(ESD)
IEC/EN61000-4-3(RS)
IEC/EN61000-4-4(EFT)
IEC/EN61000-4-5(lightning surge)
IEC/EN61000-2-2 (Immunity to low frequency signals)
INSTALLING YOUR EPS
UNPACKING
Inspect the EPS upon receipt. The box should contain the following:
(1) EPS Unit x 1; (2) User Manual x 1; (3) Input Power Cord x 1
AUTOMATIC VOLTAGE REGULATOR
Utility power is inconsistent. The EPS increases low voltage to computer safe 230 volts. The EPS
automatically provides battery backup (External battery connection required) if the voltage drops below
140 volts or exceeds 300 volts.
HARDWARE INSTALLATION GUIDE
1. Your new EPS may be used immediately upon receipt. However, recharging the external battery
for at least 8 hours is recommended to ensure that the battery’s maximum charge capacity is
achieved (Charging time varies with capacity and a 100Ah or great battery is recommended). To
recharge the external battery, simply leave the unit plugged into an AC outlet. Your EPS is
equipped with an auto-charge feature. When the EPS is plugged into an AC outlet, the external
battery will automatically recharge. The unit will charge when Battery Switch is ON, whenever
Power Switch is ON or OFF.
2. DO NOT use with medical or life support equipment. DO NOT use with or near aquariums
as condensation may cause the unit to short out.
3. After connecting the hard wires, plug the EPS into a 2 pole, 3 wire grounded receptacle (wall
outlet). Make sure the wall branch outlet is protected by a fuse or circuit breaker and does not
service equipment with large electrical demands (e.g. air conditioner, copier, etc…). The warranty
prohibits the use of extension cords, outlet strips, and surge strips.
4. Press the power switch to turn the unit on. The power on indicator light will illuminate and the unit
will beep once.
5. If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To
correct this, turn the EPS off and unplug at least one piece of equipment from the battery power
supplied outlets. Wait 10 seconds. Make sure the circuit breaker is depressed and then turn the
EPS on.
6. To maintain optimum battery charge performance, make the EPS plugged into an AC outlet at all
times. Enabling the switch provides the bypass for charge only.

4
BASIC OPERATION
DESCRIPTION
1. Power Switch
Used as the master on/off switch for equipment connected to the AC outlets.
2. Power On Indicator
This LED is above the power switch. It illuminates when the utility condition is normal and the AC
outlet is providing power, free of surges and spikes.
3. Multifunction LCD Readout
High resolution and intelligent LCD display shows all the EPS information with icons and messages.
For more information please check the DEFINITIONS FOR ILLUMINATED LCD INDICATORS
section.
4. LCD Display Toggle / Selected Switch
Users can monitor EPS status and set up functions using the toggle. The buzzer on/off can also be
controlled by the toggle switch. Please refer to “EPS Status Inquiry and Functions Setup”section
for more details.
5. AC Outlet
The unit has two FR type outlets for connected equipment to ensure temporary uninterrupted
operation during a power failure. Max. Output is 10A; Max. Output wattage is 700W.
Note! Maximum cord length is 10 meters and the cable O.D. must be 14AWG or greater.
6. AC Inlet
AC input terminals
Note:The O.D. of the distribution cables must be 14AWG or greater.
7. DC Inlet
Battery input terminals
Note:Maximum battery wiring cable length is 2 meters and the cable O.D. must be 4AWG or
greater.
8. Battery Switch
Turn on/off the battery switch, and the battery source will be connected/disconnected to the EPS
unit. The unit will only charge in the ON position.
9. AC Output Circuit Breaker
Located on the back of the EPS, the circuit breaker serves to provide overload and fault protection.
10. AC Input Circuit Breaker
Located on the back of the EPS, the circuit breaker serves to provide overload and fault protection.

5
11. Battery Input Wiring Fault LED
Battery input wiring fault LED will illuminate to indicate the wiring polarity is reversed.
12. Bypass Switch
Bypass switch provides the bypass for charge only. In charger only mode, AVR and battery backup
will not work.
INSTALLATION GUIDE
Note: The installation must be done by professionals.
STEP1
- Remove the cover from the back of the machine.
- Make sure both the POWER SW. and the BATTERY SW. are turned off and the Bypass SW. is
disabled.
STEP2
- Connect the AC OUTPUT connections.
STEP3
- Connect the batteries to the BATTERY INPUT.
- Connect red (positive (+)) battery cable to the red (positive (+)) connectors on the EPS and
external batteries.
- Connect black (negative (-)) battery cable to the black (negative (-)) connectors on the EPS and
external batteries.

6
- WIRING FAULT LED will illuminate to indicate the wiring polarity is reversed.
STEP4
- Connect the AC power source to AC INPUT (Make sure AC power is off first).
STEP5
- Turn on the BATTERY SW. on the back of the machine.
STEP6
- Turn on the Power Switch on the front panel. The Power On Indicator and the LCD Display will
blink 4 times. Press the Display toggle (Selected Switch) once. The output voltage showing on the

7
LCD Display should be 230V. This completes the start-up process.
- Press and hold the Display toggle switch for 4 seconds. The machine will begin a self test and
enter Battery Mode for 10 seconds before returning to Line Mode. Make sure the self test is ready,
or see the Definitions for illuminated LCD on page 9 for a list of alarm code definitions.
- After ensuring the machine works normally, reassemble the back cover. The installation is now
complete.
- When the external battery needs to be maintained or replaced remember to turn the machine off.
Once off, remove the AC power source and switch off the BATTERY SW. before maintenance or
replacing the batteries. When the work is complete, please start from Step 3 to re-install the
machine.
REPLACING THE BATTERY
CAUTION! Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery.
Battery service should only be done by qualified professionals.
CAUTION! Use only the specified type and number of external batteries. Please see the technical
specifications for replacement batteries.
CAUTION! The battery may present a risk of electrical shock. Do not dispose of battery in a fire as it
may explode. Follow all local ordinances regarding proper disposal of batteries. Lead-acid batteries
should be recycled.
CAUTION! Do not open or mutilate the batteries. Released electrolyte is harmful to skin and eyes and
may be toxic.
CAUTION! The external battery cabinet must be provided with 100Ah / 12V for models CPS1000E-
FR.
CAUTION! A battery can present a high risk of short circuit current and electrical shock.
Take the following precautions before replacing the battery:
1. Remove all watches, rings or other metal objects.
2. Only use tools with insulated handles.
3. Do not lay tools or metal parts on top of battery or any terminals.
4. Wear rubber gloves and boots.
5. Determine if the external battery is inadvertently grounded. If grounded, remove the source of
ground. CONTACT WITH GROUNDED BATTERY CAN RESULT IN ELECTRICAL SHOCK!

8
DEFINITIONS FOR ILLUMINATED LCD INDICATORS
The LCD Display indicates a variety of EPS operational
conditions. All descriptions apply when the EPS is plugged
into an AC outlet and turned on or when the EPS is on
battery.
1. INPUT VOLTAGE Meter: This meter measures the AC voltage that the EPS is receiving from the
utility wall outlet. The EPS is designed, through the use of automatic voltage regulation, to
continuously supply connected equipment with stable, 230 output voltage. In the event of a
complete power loss, severe brownout or over-voltage the EPS will rely on its external battery to
supply consistent 230 output voltage. The Input Voltage Meter can be used as a diagnostic tool to
identify poor quality input power.
2. OUTPUT VOLTAGE Meter: This meter measures, the AC voltage that the EPS is providing to the
computer. It displays normal line mode, AVR mode, and battery backup mode.
3. NORMAL MODE Icon: This icon will illuminate when the EPS is working under normal conditions.
4. ON BAT (On Battery) Icon: When a severe brownout or blackout, this icon appearing and an
alarm (two short beeps) activated indicate that the EPS is working via its batteries. Once the
batteries are running out of power, for a period of time, an alarm (two short beeps) will appear
continuously. If this occurs, it is recommended that save your files and turn off your equipment
manually as soon as possible.
5. SILENT MODE Icon: This icon appearing indicates that the buzzer does not beep in the silent
mode until the low battery capacity.
6. OVER LOAD Icon: This icon appearing and an alarm activated indicate that the overload
condition. To relieve the overload, unplug your equipment from the EPS outlets until the icon
disappears and the alarm stops being activated.
7. LOAD CAPACITY: Load CAPACITY is also shown on the bar chart; equal 25% load capacity for
each segment.
8. BATTERY VOLTAGE: BATT. VOLTAGE indicates the voltage of battery.
EPS STATUS INQUIRY AND FUNCTIONS SETUP
GENERAL MODE
a. Press the “Display” button to check the status of the EPS
Items
Unit
Input Voltage
V
Output Voltage
V
Load Capacity
%
Battery Voltage
V

9
b. Press and hold the Display toggle for 4 seconds.
If the machine is in the Battery Mode, it enters the silent mode. Press again for 4 seconds
and it will return to normal (buzzer) mode.
If the machine is in the Line Mode, it proceeds to Self Test.
c. If the Display toggle remains untouched for over 30 seconds, the LCD backlight will turn off
automatically.
SET-UP MODE
Step 1: Hold the Display toggle for 10 seconds to enter the EPS set-up Mode. LCD icon 1, 2 lights
indicate Set-Up Mode.
Step 2: By pressing the Display toggle, users can switch between setup functions. User configurable
functions are as follows:
a. Delay Time: The time delay between switching from Battery Mode to Line Mode. There are 9
different settings. The default setting is 0 minute.
Function description: The machine will switch from Battery Mode to Line Mode after theAC
power transmission reaches stability within the preset delay time.
b. Charging Current: The function adjusts the battery charging current according to the capacity of
the connected batteries. It can be configured for 0, 25, 50, 75 and 100%. The default setting is 50
%. 100% indicates that charging current is about 15Amps.
c. Nominal Output Voltage: Configures the correct electricity/voltage supplied in the area/country
where the EPS will be used. 220V, 230V and 240V may be selected. The system default setting is
230V.
Function description:AVR Dynamic Voltage Compensation works automatically based on the
system voltage settings.
d. Static Frequency Tolerance: There are 6 settings (1,2,4,6,8,10%), and the default setting is +/-6
%.
Function description: The settings may be adjusted to the quality of the electricity in use.
e. Slew Rate: Also called Dynamic Frequency Tolerance. There are 5 different settings
(0.25,0.5,1,2,4 Hz/Sec). The default value is 4Hz/sec.
Function description: “Slew Rate” indicates the tolerance of a device in accepting frequency
variances. The lower “Slew Rate” results in less tolerance but better protection for the connected
loads.
f. Low Battery Shutdown Voltage: This function adjusts the EPS shutdown point according to the
battery voltage. The default setting is 10.8V (with load).
g. Mode Select: The standard mode (setting: 2) and the robust mode (setting: 1) are provided to
select. Using the generators is suggested to select the robust mode (setting: 1), and using the
computers is suggested to select the standard mode (setting: 2). The system default setting is
standard mode (setting: 2).
The settable items are sorted by unit as in the following table:
Items
Unit
Icon Lit
Delay Time
Min
ON BAT
Charging Current
%
ON BAT
Nominal Output Voltage
V
NORMAL MODE
Static Frequency Tolerance
%
NORMAL MODE

10
Step 3: Press and hold the toggle for 4 seconds. When the icons blink, the value of each item can be
changed by slightly pressing the toggle.
Step 4: To save the value and return to general mode, press and hold the toggle for 4 seconds.
Note: If the machine is left idle for over 30 seconds during setup, it will turn off the backlight and
return to general mode automatically.
Note: If user wants to return to general mode without saving changes, there are two methods:
1. Wait for the backlight to turn off
2. Press and hold the “Display” toggle for 10 seconds
FAULT WARNING DISPLAY AND ALARM
1. Overheat Protection: The EPS output will be interrupted. After 30 seconds, the machine shuts
down and the LCD display output voltage is zero.
2. Over-Load Protection:The EPS output will be interrupted. After 30 seconds, the machine shuts
down and Over Load Icon lights on the LCD display.
3. Battery Missing:You should hear a long beep and Battery Indicator flashes。
4. Low Battery Protection: The EPS output will be interrupted. After 30 seconds, the machine shuts
down and the LCD display output voltage is zero.
5. The following table shows each corresponding warning message on the LCD display and the
alarm reacts during the machine shut down:
LCD Warning
Display
Alarm
Condition
Solution
Over Load Icon
Constant tone
Over Load Output-Off
- Load exceed the
rating of EPS.
Check total load to
confirm the rating of
EPS.
Battery Icon Flash
Beep Once
Battery Missing- In
Line Mode Battery
Missing.
Turn the EPS off,
check battery wiring
and presence of
battery
Zero Output Voltage
Constant tone
High Temperature
Output-Off
Check fans function
and air vent
clearances.
Slew Rate
%
None
Low Battery Shutdown
Voltage
V
ON BAT
Mode Select
None
None
Firmware Version
Here displays the firmware version. It
can not be configured.

11
Low Battery
Output-Off
-- Insufficient battery
capacity.
Recharge the battery.
Over Charge or AVR
Error-- In Line Mode,
battery is overcharged
or AVR is faulty.
Inform service agents.
Short Output-Off --
Output Short Circuit
Protection
Check the EPS output
to see if there is a
short circuit.
Can Not Start Up
None
Line Input/ Output
Error Output-Off --
incorrect Input/ Output
connection
Check Input/ Output
connection.
Cold Start Battery
High Voltage
Output-Off -- the
battery voltage is too
high during cold start.
Check the reason for
battery over-voltage.
TROUBLESHOOTING
Problem
Possible Cause
Solution
Outlet does not provide
power to equipment.
Circuit breaker has
tripped due to an
overload.
First, turn the EPS off and unplug at least
one piece of equipment. Wait 10 seconds,
reset the circuit breaker by pressing the
button, and then turn the EPS on.
Batteries are
discharged.
Recharge the unit for at least 4 hours.
Unit has been
damaged by a surge
or spike.
Contact CyberPower Systems about
replacement batteries.
The EPS does not perform
expected runtime.
Batteries are not fully
charged.
Recharge the battery by leaving the EPS
plugged in.
Batteries are
degraded.
Contact CyberPower Systems about
replacement batteries.
The UPS will not turn on.
The on/off switch is
designed to prevent
the damage that
rapidly turns it off and
on.
Turn the EPS off. Wait 10 seconds and
then turn the EPS on.

12
The unit is not
connected to an AC
outlet.
The unit must be connected to a
220/230/240V outlet.
The battery is worn
out.
Contact CyberPower Systems about
replacement batteries.
Mechanical problem.
Contact CyberPower Systems via phone or
visit our website at www.cpsww.eu
TECHNICAL SPECIFICATIONS
Model
CPS1000E-FR
Capacity (VA)
1000VA
Capacity (Watts)
700W
Operation Technology
AVR ( Double Boost & Single Buck )
AC Input
Input Voltage Range
140Vac –300Vac
Input Frequency Range
45~65Hz (auto sensing)
AC Output
Number of Phase
Single Phase
On Battery Typical
Output Voltage
0 ~40% LOAD Pure Sine Wave at 230Vac +/- 5%
40~100% LOAD Trapezoidal Wave at 230Vac+/- 5%
Nominal Output
Voltage Configuration
Note
Configurable for 220 / 230 / 240Vac
On Battery Output
Frequency
50 / 60 Hz +/- 1%
Overload Protection
On Utility: Circuit Breaker
On Battery: Internal Current Limiting
Transfer Time
< 10 ms ( Typical )
Output Receptacles
FR Type * 2
External Battery
Voltage x
Recommended Rating
x Quantity
12V x 100Ah x 1
External Battery Rating
12V
External Battery Type
Sealed Maintenance Free Lead Acid Battery
External Battery
Protection
Fuse & Relay
Hot Swappable
External Battery
Yes
Status Indication
Indicators
Power On, LCD Display
Audible Alarms
On Battery, Low Battery, Overload
Environment

13
Operating Temperature
32F to 104F ( 0C to 40C )
Operating Relative
Humidity
0 to 90% Non-Condensing
Physical
Dimensions
(L*W*H)( mm )
153 * 208 * 241
Weight (Kg)
8.2
Agency
Certificated
CE, SONCAP
For more information, visit www.cpsww.eu.
All rights reserved. Reproduction without permission is prohibited.

14
FR

15
CPS1000E-FR
Manuel d’utilisation
INSTRUCTIONS DE SÉCURITÉ ET DE COMPATIBILITÉ

16
ÉLECTROMAGNÉTIQUE
Ce manuel contient des instructions de sécurité importantes. Lisez attentivement et suivez ces
instructions lors de l’installation et de l’utilisation de l’unité. Lisez ce manuel dans son intégralité avant
de déballer, d’installer ou d’utiliser votre générateur électrique de secours.
ATTENTION ! Afin d’éviter tout risque d’incendie ou d’électrocution, installez l’unité à l’intérieur, dans
une zone équipée d’un système de régulation thermique et hygrométrique, et exempte de
contaminants conducteurs. (Reportez-vous aux caractéristiques techniques pour connaître les plages
de température et d’humidité acceptables).
ATTENTION ! Afin de réduire le risque d’électrocution, n’ôtez pas le capot, hormis lors de la
maintenance de la batterie. L’unité ne contient aucun composant nécessitant des opérations de
maintenance, à l’exception de la batterie.
ATTENTION ! Le générateur doit être branché sur une prise secteur protégée par un sectionneur. Ne
branchez en aucun cas l'unité sur une prise secteur non reliée à la terre. Si vous avez besoin de mettre
l'unité hors circuit, mettez-la hors tension et débranchez-la.
ATTENTION ! Afin d’éviter tout risque d’électrocution, mettez l’unité hors tension et débranchez-la de
la prise secteur avant d’entreprendre des opérations de maintenance sur le générateur, de remplacer
la batterie externe ou d’installer des équipements.
ATTENTION ! Afin de réduire le risque d’incendie, branchez uniquement le générateur sur un circuit
électrique équipé d'un dispositif de protection contre les surintensités de 16 ampères, conformément
aux exigences CE.
ATTENTION ! Pour faciliter le raccordement, la prise murale du bâtiment (prise murale antichoc) doit
être facile d’accès et située à proximité du générateur.
ATTENTION ! Utilisez uniquement des câbles secteur homologués VDE et portant le marquage CE
(par exemple, les câbles secteur de vos équipements) pour brancher le générateur sur la prise murale
du bâtiment (prise murale antichoc).
ATTENTION ! Utilisez uniquement des câbles d’alimentation homologués VDE et portant le marquage
CE pour brancher des charges sur le générateur.
ATTENTION ! Lors de l’installation de vos équipements, veillez à ce que la somme des courants de
fuite du générateur et des équipements connectés ne dépasse pas 3,5 mA.
ATTENTION ! Ne débranchez pas le câble secteur du générateur de la prise murale du bâtiment (prise
murale antichoc) en cours d’utilisation. Cela aurait pour effet de supprimer la mise à la terre du
générateur et de toutes les charges connectées.
N’UTILISEZ PAS CE GÉNÉRATEUR AVEC UN ÉQUIPEMENT MÉDICAL OU D’ASSISTANCE
MÉDICALE !
N’UTILISEZ PAS ce générateur dans des circonstances susceptibles d’affecter le fonctionnement et la
sécurité d’un équipement d’assistance médicale, les applications médicales ou les soins des patients.
N’UTILISEZ PAS CE GÉNÉRATEUR AVEC UN AQUARIUM OU À PROXIMITÉ D’UN AQUARIUM !
Afin de réduire le risque d’incendie ou d’électrocution, n’utilisez pas ce générateur avec un aquarium
ou à proximité d’un aquarium. La condensation de l’aquarium peut engendrer un court-circuit dans
l’unité.
N’INSTALLEZ PAS CE GÉNÉRATEUR À PROXIMITÉ D’UNE SOURCE DE CHALEUR OU DANS
UN LIEU DIRECTEMENT EXPOSÉ AUX RAYONS DU SOLEIL.
N’OBSTRUEZ PAS LES OUVERTURES D’AÉRATION SITUÉES SUR LE BOÎTIER DU
GÉNÉRATEUR !

17
SÉCURITÉ :
EN62040-1-1
EMI :
Émissions conduites : IEC/EN 62040-2…Catégorie C2
Émissions rayonnées : IEC/EN 62040-2……Catégorie C2
Courant harmonique : IEC/EN61000-3-2
Fluctuations de tension et papillotement : IEC/EN61000-3-3
EMS :
IEC/EN61000-4-2 (ESD)
IEC/EN61000-4-3 (RS)
IEC/EN61000-4-4 (EFT)
IEC/EN61000-4-5 (surtension)
IEC/EN61000-2-2 (immunité contre les signaux basse fréquence)
INSTALLATION DU GÉNÉRATEUR
DÉBALLAGE
Inspectez le générateur à réception. Le carton devrait contenir les éléments suivants :
1 générateur ; 1 manuel d’utilisation ; 1 cordon d’alimentation en entrée
RÉGULATEUR AUTOMATIQUE DE TENSION
Le courant électrique du secteur n’est pas homogène. Le générateur compense les sous-tensions afin
de délivrer une tension de 230 volts aux ordinateurs. Le générateur fournit automatiquement une
alimentation secourue par batterie (connexion à une batterie externe requise) lorsque la tension chute
en dessous de 140 volts ou dépasse 300 volts.
GUIDE D’INSTALLATION DU MATÉRIEL
1. Votre nouvel EPS peut être utilisé dès sa réception. Cependant, il est recommandé de le laisser
se recharger pendant au moins 8 heures afin que les batteries puissent atteindre le maximum de
leur capacité (le temps de recharge varie en fonction de la capacité des batteries et une capacité
de 100AH au moins est recommandée). Pour recharger les batteries, il suffit simplement de
laisser l’EPS connecté au réseau électrique. Votre EPS est équipé d’un système de charge
automatique. Lorsque l’EPS est raccordé au réseau électrique, les batteries externes se
rechargent automatiquement. Attention elles se rechargeront si l’interrupteur Batterie est
positionné sur ON, même l’interrupteur M/A est sur OFF.
2. N’UTILISEZ PAS le générateur avec un équipement médical ou d’assistance médicale.
N’UTILISEZ PAS le générateur avec un aquarium ou à proximité d’un aquarium, car la
condensation pourrait faire engendrer un court-circuit dans l’unité.
3. Une fois les branchements filaires effectués, branchez le générateur sur une prise murale 2 pôles
+ Terre. Assurez-vous que la prise murale est protégée par un sectionneur et qu’elle n’alimente
pas des équipements ayant d’importants besoins en électricité (ex., climatiseur, copieur, etc.). La
garantie interdit l’utilisation des cordons prolongateurs, prises multiples et parasurtenseurs.
4. Appuyez sur l’interrupteur principal pour mettre l’unité sous tension. Le voyant de mise sous
tension s’allume et l’unité émet un bip.
5. En cas de surcharge, une alarme sonore apparaît sous forme d’un long bip continu. Pour
remédier à ce problème, arrêtez l’EPS et déconnectez au moins un matériel de sur les prises

18
ondulées. Patientez 10 secondes. Vérifiez que le disjoncteur d’entrée est enclancher et redémarrez
l’EPS.
6. Pour obtenir une autonomie maximum, faîtes que l’EPS soit toujours raccordé sur le réseau
électrique. Positionnez le bouton By-Pass sur charge seulement.
FONCTIONNEMENT DE BASE
DESCRIPTION
1. Interrupteur principal
Il s’agit de l’interrupteur marche/arrêt
principal de l’équipement branché sur la prise secteur.
2. Voyant de mise sous tension
Ce voyant se trouve au-dessus de l’interrupteur principal. Lorsqu’il est allumé, cela signifie que les
conditions secteur sont normales et que la prise secteur délivre un courant exempt de surtensions et
de pointes.
3. Écran LCD multifonction
L’écran LCD haute résolution et intelligent affiche toutes les informations sur le générateur au moyen
d’icônes et de messages. Pour en savoir plus, reportez-vous à la section « Indications affichées sur
l’écran LCD ».
4. Bouton poussoir/de sélection de l’écran LCD
Les utilisateurs peuvent surveiller l’état du générateur et configurer des fonctions à l’aide du bouton
poussoir. Ce bouton permet également d’activer ou de désactiver l’avertisseur sonore. Pour en
savoir plus, reportez-vous à la section « Détermination de l’état et configuration des fonctions du
générateur ».
5. Sortie CA
L’unité est équipée d’une prise de type FR pour brancher l’équipement et garantir un fonctionnement
temporairement ininterrompu en cas de panne d’électricité. Sortie max. : 10 A ; Puissance de sortie
max. : 700 W.
Remarque ! La longueur maximale du cordon est de 10 mètres et le diamètre extérieur du
câble doit être de 1.5mm² ou plus.
6. Entrée CA
Cette entrée est branchée sur le secteur via le cordon d’alimentation en entrée.
Remarque :le diamètre extérieur des câbles de distribution doit être de 1,0 mm ou plus.
7.Bornier de raccordement des batteries

19
Raccordement des batteries.
Note:La longueur maximum du cable de raccordement ne doit pas dépasser 2M et sa
section doit être au minimum de 25mm².
8. Interrupteur Batterie
Permet de connecter ou de déconnecter les batteries de l’EPS.
Les batteries se chargent lorsque l’interrupteur est sur ON.
9.Disjoncteur de sortie AC
Situé en face arrière, ce disjoncteur protége l’EPS contre les surcharges et les courtcircuits.
10.Disjoncteur d’entrée AC
Situé en face arrière, ce disjoncteur protége l’EPS contre les surcharges et les courtcircuits.
11.Voyant d’erreur de connexion des batteries
Le voyant s’allume lorsque les polarités + et – sont inversées sur la batterie.
12.Bouton By-Pass
Le bouton By-Pass permet de recharger la batterie uniquement. En mode chargeur uniquement, le
régulateur de tension ne fonctionnera pas.
GUIDE D’INSTALLATION
Note: L’installation doit être réalisée par un professionnel.
ETAPE 1
- Démonter le capot arrière de l’EPS.
- Assurez-vous que les boutons Power Switch et Battery Switch sont bien sur OFF et que le
By-Pass est désactive.
ETAPE 2
- Raccordez les charges en sortie.
ETAPE 3

20
- Raccordez les batteries au bornier Batterie.
- Raccordez le câble rouge (positif (+)) à la borne rouge (positive (+)) du bornier Batterie de l’EPS.
- Raccordez le câble noir (négatif (+)) à la borne noire (négatif (+)) du bornier Batterie de l’EPS.
- Le voyant d’inversion de polarité s’allumera en cas d’erreur.
ETAPE 4
- Raccordez le câble d’alimentation à la prise d’entrée
réseau.
ETAPE 5
- Enclanchez le bouton Batterie (BAT SW) situé en face arrière de l’EPS.
ETAPE 6
- Positionnez le bouton principal ON/OFF situé en face avant sur ON. Le voyant de mise sous
tension et l’afficheur clignotent 4 fois. Appuyez sur le bouton poussoir de selection une fois. La
Table of contents
Languages:
Other CyberPower Power Supply manuals

CyberPower
CyberPower CPS7500PRO User manual

CyberPower
CyberPower CP685AVR-G User manual

CyberPower
CyberPower PowerPanel Business Edition User manual

CyberPower
CyberPower CA50A48V2 User manual

CyberPower
CyberPower CPS3000PIE User manual

CyberPower
CyberPower LX1000G User manual

CyberPower
CyberPower PowerPanel Business Edition User manual

CyberPower
CyberPower CPS3500PIE User manual