Daewoo DAEPC-7 User manual

Manufactured under license of Daewoo International Corporation, Korea
www.daewoopowerproducts.com
USER'S MANUAL
DAEPC-7
Automatic pressure switch
1. INSTRUCTIONS FOR CORRECT UNIT INSTALLATION
The control can be installed directly onthe pump or installed between
pump and the first tap. A pressure reducing valve must be installed on
the inlet of the control if pump's pressure exceeds 10 bar.
No taps can be installed between the pump and the control.
It is imperative to install the control with the arrows in the
upward position. (Fig 1/A)
It is advisable to connect the control outlet to the system by means
of a flexible pipe. (Fig 1/B)
Check suction and ensure that the pump is primed before starting the
control.
Normally pressure produced by the pump must be 1bar (0.1 MPa)
higher than the control's pre-set pressure, that is, checking on the
effective pressure of pump and system water column height
must be carried out according to the pre-set pressure.
The control's is set at its standard starting pressure
as 1.5bar (0.15 MPa) and starting pressure at 1.2 bar
or 2.2 bar are also available upon requests.
The pump can be blocked or continues to operate without stop if its
pressure is lower than stated minimum pressure. On the other hand,
the pump will not work if the height of water column exceeds above
standards. It is advisable to install the unit on a higher level to restore
a good installation condition as mentioned in the above or to change
for a unit with larger starting pressure.
2. STARTING AND WORKING
CAUTION: Never take the electronic board out of the control box. The wiring diagram inside the
terminal block will show you a correct connection. Wrong or loose connection will destroy the whole
electronic circuit.
Cable used for connection must be H05 or H07 type with 3×1.5 mm section .It shall have the outer
diameter at 8.9mm min. and 9.2 mm max. One of the leading end of the cable must be lower than
the position of the fixing screws while the cable being connected to the power as shown in the fig.
The six screws on the panel board and the two nuts for fixing cable must be well fastened to avoid
water entering into the control box and damaging the electronic circuit.
FUNCTION
The control is programmed to start and stop the pump operations automatically.
Its feature of water-shortage protection can protect the pump from being damaged during dry
running.
Except all ordinary function, It with timer can reset the pump automatically without water. When the
pump stop without water failed in the water supply system, the indicator light will be twinkled regu-
larly. In definite time, the controller reset pump every 15mins 1 time to test whether the water source
get right. If water source get right, the controller will exite this state. If in those time, no water suc-
tion, the control will keep without-water state, and after start the pump 4times every 15mins, the
control will reset pump in every 1h.Rectification of the failures that have caused the blockage allows
the system to be restarted by pressing the “restart” button for more than 2seconds. Keep button
“restart” pressed can stop the pump duringits operation and resume its work after stopping.
STARTING
When the control is connected to the electrical network, the green led “power on” lights up and the
yellow led “on”(pump in operation) lights 2-4 seconds later indicating that the pump has been
started. The pump continues to operate for 8 seconds enabling the system to fill in the pipes and to
reach the required pressure. If this lapse is insufficient, the red led “failure” lights up. In this event,
keep the “restart” button pressed and wait with a tap opened until the red led is off. Once the
button is released and the tap is closed, the control stops the pump at its max. Pressure.
3. WIRING DIAGRAMS FOR CONNECTING THE UNIT TO DIFFERENT KINDS OF PUMP’S
MOTORS
4. DEFECT DETECTING
5. AFTER SALES SERVICE
This control is guaranteed for a period of twelve months from the date of purchase and shall not be
subject to any claims caused by subjective misusing and disassemblies or any installations not in
accordance with the instruction.
6. TECHNICAL DATA
Power: 2.2 kW
Current: 30 A
Maximum working pressure: 10 bar
Max working temperature: 55ºC
Connection: 1"male - 1 1/4"male
Protection rating: IP65

INDEX
1. INSTRUCTIONS FOR CORRECT UNIT INSTALLATION
..................................................................... 2
2. STARTING AND WORKING
................................................................................................................... 2
3. WIRING DIAGRAMS FOR CONNECTING THE UNIT TO DIFFERENT KINDS
OF PUMP’S MOTORS
................................................................................................................................ 3
4
. DEFECT DETECTING ............................................................................................................................. 5
5
. AFTER SALES SERVICE ......................................................................................................................... 5
6. TECHNICAL DATA
.................................................................................................................................. 5
WARRANTY ................................................................................................................................................. 6
1. INSTRUCTIONS FOR CORRECT UNIT INSTALLATION
The control can be installed directly onthe pump or installed between
pump and the first tap. A pressure reducing valve must be installed on
the inlet of the control if pump's pressure exceeds 10 bar.
No taps can be installed between the pump and the control.
It is imperative to install the control with the arrows in the
upward position. (Fig 1/A)
It is advisable to connect the control outlet to the system by means
of a flexible pipe. (Fig 1/B)
Check suction and ensure that the pump is primed before starting the
control.
Normally pressure produced by the pump must be 1bar (0.1 MPa)
higher than the control's pre-set pressure, that is, checking on the
effective pressure of pump and system water column height
must be carried out according to the pre-set pressure.
The control's is set at its standard starting pressure
as 1.5bar (0.15 MPa) and starting pressure at 1.2 bar
or 2.2 bar are also available upon requests.
The pump can be blocked or continues to operate without stop if its
pressure is lower than stated minimum pressure. On the other hand,
the pump will not work if the height of water column exceeds above
standards. It is advisable to install the unit on a higher level to restore
a good installation condition as mentioned in the above or to change
for a unit with larger starting pressure.
2. STARTING AND WORKING
CAUTION: Never take the electronic board out of the control box. The wiring diagram inside the
terminal block will show you a correct connection. Wrong or loose connection will destroy the whole
electronic circuit.
Cable used for connection must be H05 or H07 type with 3×1.5 mm section .It shall have the outer
diameter at 8.9mm min. and 9.2 mm max. One of the leading end of the cable must be lower than
the position of the fixing screws while the cable being connected to the power as shown in the fig.
The six screws on the panel board and the two nuts for fixing cable must be well fastened to avoid
water entering into the control box and damaging the electronic circuit.
FUNCTION
The control is programmed to start and stop the pump operations automatically.
Its feature of water-shortage protection can protect the pump from being damaged during dry
running.
Except all ordinary function, It with timer can reset the pump automatically without water. When the
pump stop without water failed in the water supply system, the indicator light will be twinkled regu-
larly. In definite time, the controller reset pump every 15mins 1 time to test whether the water source
get right. If water source get right, the controller will exite this state. If in those time, no water suc-
tion, the control will keep without-water state, and after start the pump 4times every 15mins, the
control will reset pump in every 1h.Rectification of the failures that have caused the blockage allows
the system to be restarted by pressing the “restart” button for more than 2seconds. Keep button
“restart” pressed can stop the pump duringits operation and resume its work after stopping.
STARTING
When the control is connected to the electrical network, the green led “power on” lights up and the
yellow led “on”(pump in operation) lights 2-4 seconds later indicating that the pump has been
started. The pump continues to operate for 8 seconds enabling the system to fill in the pipes and to
reach the required pressure. If this lapse is insufficient, the red led “failure” lights up. In this event,
keep the “restart” button pressed and wait with a tap opened until the red led is off. Once the
button is released and the tap is closed, the control stops the pump at its max. Pressure.
3. WIRING DIAGRAMS FOR CONNECTING THE UNIT TO DIFFERENT KINDS OF PUMP’S
MOTORS
4. DEFECT DETECTING
5. AFTER SALES SERVICE
This control is guaranteed for a period of twelve months from the date of purchase and shall not be
subject to any claims caused by subjective misusing and disassemblies or any installations not in
accordance with the instruction.
6. TECHNICAL DATA
Power: 2.2 kW
Current: 30 A
Maximum working pressure: 10 bar
Max working temperature: 55ºC
Connection: 1"male - 1 1/4"male
Protection rating: IP65
1

EN
1. INSTRUCTIONS FOR CORRECT UNIT INSTALLATION
The control can be installed directly onthe pump or installed between
pump and the first tap. A pressure reducing valve must be installed on
the inlet of the control if pump's pressure exceeds 10 bar.
No taps can be installed between the pump and the control.
It is imperative to install the control with the arrows in the
upward position. (Fig 1/A)
It is advisable to connect the control outlet to the system by means
of a flexible pipe. (Fig 1/B)
Check suction and ensure that the pump is primed before starting the
control.
Normally pressure produced by the pump must be 1bar (0.1 MPa)
higher than the control's pre-set pressure, that is, checking on the
effective pressure of pump and system water column height
must be carried out according to the pre-set pressure.
The control's is set at its standard starting pressure
as 1.5bar (0.15 MPa) and starting pressure at 1.2 bar
or 2.2 bar are also available upon requests.
The pump can be blocked or continues to operate without stop if its
pressure is lower than stated minimum pressure. On the other hand,
the pump will not work if the height of water column exceeds above
standards. It is advisable to install the unit on a higher level to restore
a good installation condition as mentioned in the above or to change
for a unit with larger starting pressure.
2. STARTING AND WORKING
CAUTION: Never take the electronic board out of the control box. The wiring diagram inside the
terminal block will show you a correct connection. Wrong or loose connection will destroy the whole
electronic circuit.
Cable used for connection must be H05 or H07 type with 3×1.5 mm section .It shall have the outer
diameter at 8.9mm min. and 9.2 mm max. One of the leading end of the cable must be lower than
the position of the fixing screws while the cable being connected to the power as shown in the fig.
The six screws on the panel board and the two nuts for fixing cable must be well fastened to avoid
water entering into the control box and damaging the electronic circuit.
A
B
Fig1
r
)
e
H
1.5bar
(0.15MPa
Pump’s pressure≥3.0bar(0.30MPa)
Starting pressu
≤15m
FUNCTION
The control is programmed to start and stop the pump operations automatically.
Its feature of water-shortage protection can protect the pump from being damaged during dry
running.
Except all ordinary function, It with timer can reset the pump automatically without water. When the
pump stop without water failed in the water supply system, the indicator light will be twinkled regu-
larly. In definite time, the controller reset pump every 15mins 1 time to test whether the water source
get right. If water source get right, the controller will exite this state. If in those time, no water suc-
tion, the control will keep without-water state, and after start the pump 4times every 15mins, the
control will reset pump in every 1h.Rectification of the failures that have caused the blockage allows
the system to be restarted by pressing the “restart” button for more than 2seconds. Keep button
“restart” pressed can stop the pump duringits operation and resume its work after stopping.
STARTING
When the control is connected to the electrical network, the green led “power on” lights up and the
yellow led “on”(pump in operation) lights 2-4 seconds later indicating that the pump has been
started. The pump continues to operate for 8 seconds enabling the system to fill in the pipes and to
reach the required pressure. If this lapse is insufficient, the red led “failure” lights up. In this event,
keep the “restart” button pressed and wait with a tap opened until the red led is off. Once the
button is released and the tap is closed, the control stops the pump at its max. Pressure.
3. WIRING DIAGRAMS FOR CONNECTING THE UNIT TO DIFFERENT KINDS OF PUMP’S
MOTORS
4. DEFECT DETECTING
5. AFTER SALES SERVICE
This control is guaranteed for a period of twelve months from the date of purchase and shall not be
subject to any claims caused by subjective misusing and disassemblies or any installations not in
accordance with the instruction.
6. TECHNICAL DATA
Power: 2.2 kW
Current: 30 A
Maximum working pressure: 10 bar
Max working temperature: 55ºC
Connection: 1"male - 1 1/4"male
Protection rating: IP65
Starting pressure
1.2 bar ( 0.12 MPa)
1.5 bar ( 0.15 MPa)
2.2 bar ( 0.22 MPa) ≥3.5 bar (0.35 MPa) ≤ 22m
≤ 15 m
≤ 10 m
≥3.0 bar (0.30 MPa)
≥2.5 bar (0.25 MPa)
Pump’s pressure The height of water
column(H)
2

1. INSTRUCTIONS FOR CORRECT UNIT INSTALLATION
The control can be installed directly onthe pump or installed between
pump and the first tap. A pressure reducing valve must be installed on
the inlet of the control if pump's pressure exceeds 10 bar.
No taps can be installed between the pump and the control.
It is imperative to install the control with the arrows in the
upward position. (Fig 1/A)
It is advisable to connect the control outlet to the system by means
of a flexible pipe. (Fig 1/B)
Check suction and ensure that the pump is primed before starting the
control.
Normally pressure produced by the pump must be 1bar (0.1 MPa)
higher than the control's pre-set pressure, that is, checking on the
effective pressure of pump and system water column height
must be carried out according to the pre-set pressure.
The control's is set at its standard starting pressure
as 1.5bar (0.15 MPa) and starting pressure at 1.2 bar
or 2.2 bar are also available upon requests.
The pump can be blocked or continues to operate without stop if its
pressure is lower than stated minimum pressure. On the other hand,
the pump will not work if the height of water column exceeds above
standards. It is advisable to install the unit on a higher level to restore
a good installation condition as mentioned in the above or to change
for a unit with larger starting pressure.
2. STARTING AND WORKING
CAUTION: Never take the electronic board out of the control box. The wiring diagram inside the
terminal block will show you a correct connection. Wrong or loose connection will destroy the whole
electronic circuit.
Cable used for connection must be H05 or H07 type with 3×1.5 mm section .It shall have the outer
diameter at 8.9mm min. and 9.2 mm max. One of the leading end of the cable must be lower than
the position of the fixing screws while the cable being connected to the power as shown in the fig.
The six screws on the panel board and the two nuts for fixing cable must be well fastened to avoid
water entering into the control box and damaging the electronic circuit.
FUNCTION
The control is programmed to start and stop the pump operations automatically.
Its feature of water-shortage protection can protect the pump from being damaged during dry
running.
Except all ordinary function, It with timer can reset the pump automatically without water. When the
pump stop without water failed in the water supply system, the indicator light will be twinkled regu-
larly. In definite time, the controller reset pump every 15mins 1 time to test whether the water source
get right. If water source get right, the controller will exite this state. If in those time, no water suc-
tion, the control will keep without-water state, and after start the pump 4times every 15mins, the
control will reset pump in every 1h.Rectification of the failures that have caused the blockage allows
the system to be restarted by pressing the “restart” button for more than 2seconds. Keep button
“restart” pressed can stop the pump duringits operation and resume its work after stopping.
STARTING
When the control is connected to the electrical network, the green led “power on” lights up and the
yellow led “on”(pump in operation) lights 2-4 seconds later indicating that the pump has been
started. The pump continues to operate for 8 seconds enabling the system to fill in the pipes and to
reach the required pressure. If this lapse is insufficient, the red led “failure” lights up. In this event,
keep the “restart” button pressed and wait with a tap opened until the red led is off. Once the
button is released and the tap is closed, the control stops the pump at its max. Pressure.
3. WIRING DIAGRAMS FOR CONNECTING THE UNIT TO DIFFERENT KINDS OF PUMP’S
MOTORS
The six screws
must be fastened
The two nuts for fixing
cables must be fastened
Power
This part must be lower
than the fixing nuts
Pump
Inlet
4. DEFECT DETECTING
5. AFTER SALES SERVICE
This control is guaranteed for a period of twelve months from the date of purchase and shall not be
subject to any claims caused by subjective misusing and disassemblies or any installations not in
accordance with the instruction.
6. TECHNICAL DATA
Power: 2.2 kW
Current: 30 A
Maximum working pressure: 10 bar
Max working temperature: 55ºC
Connection: 1"male - 1 1/4"male
Protection rating: IP65
contactor contactor
~~
Wiring diagram for
connection of single
-phase 110V/230V pumps
up to 1.1 kW/2.2 kW (3 hp)
Wiring diagram for connection
of single-phase 110V/230V pumps
over1.1 kW/2.2 kW(3 hp) through
remote control switch.
SPECIFICATIONS FOR
REMOTE CONTROL SWITCH
Minimum contacts capacity of
4 kW or 5.5 hp approx
SPECIFICATIONS FOR
REMOTE CONTROL SWITCH
Minimum contacts capacity of
4 kW or 5.5 hp approx
Wiring diagram for connection
of three phase 380V motor
pumps through remote control
switch.
3

EN
1. INSTRUCTIONS FOR CORRECT UNIT INSTALLATION
The control can be installed directly onthe pump or installed between
pump and the first tap. A pressure reducing valve must be installed on
the inlet of the control if pump's pressure exceeds 10 bar.
No taps can be installed between the pump and the control.
It is imperative to install the control with the arrows in the
upward position. (Fig 1/A)
It is advisable to connect the control outlet to the system by means
of a flexible pipe. (Fig 1/B)
Check suction and ensure that the pump is primed before starting the
control.
Normally pressure produced by the pump must be 1bar (0.1 MPa)
higher than the control's pre-set pressure, that is, checking on the
effective pressure of pump and system water column height
must be carried out according to the pre-set pressure.
The control's is set at its standard starting pressure
as 1.5bar (0.15 MPa) and starting pressure at 1.2 bar
or 2.2 bar are also available upon requests.
The pump can be blocked or continues to operate without stop if its
pressure is lower than stated minimum pressure. On the other hand,
the pump will not work if the height of water column exceeds above
standards. It is advisable to install the unit on a higher level to restore
a good installation condition as mentioned in the above or to change
for a unit with larger starting pressure.
2. STARTING AND WORKING
CAUTION: Never take the electronic board out of the control box. The wiring diagram inside the
terminal block will show you a correct connection. Wrong or loose connection will destroy the whole
electronic circuit.
Cable used for connection must be H05 or H07 type with 3×1.5 mm section .It shall have the outer
diameter at 8.9mm min. and 9.2 mm max. One of the leading end of the cable must be lower than
the position of the fixing screws while the cable being connected to the power as shown in the fig.
The six screws on the panel board and the two nuts for fixing cable must be well fastened to avoid
water entering into the control box and damaging the electronic circuit.
FUNCTION
The control is programmed to start and stop the pump operations automatically.
Its feature of water-shortage protection can protect the pump from being damaged during dry
running.
Except all ordinary function, It with timer can reset the pump automatically without water. When the
pump stop without water failed in the water supply system, the indicator light will be twinkled regu-
larly. In definite time, the controller reset pump every 15mins 1 time to test whether the water source
get right. If water source get right, the controller will exite this state. If in those time, no water suc-
tion, the control will keep without-water state, and after start the pump 4times every 15mins, the
control will reset pump in every 1h.Rectification of the failures that have caused the blockage allows
the system to be restarted by pressing the “restart” button for more than 2seconds. Keep button
“restart” pressed can stop the pump duringits operation and resume its work after stopping.
STARTING
When the control is connected to the electrical network, the green led “power on” lights up and the
yellow led “on”(pump in operation) lights 2-4 seconds later indicating that the pump has been
started. The pump continues to operate for 8 seconds enabling the system to fill in the pipes and to
reach the required pressure. If this lapse is insufficient, the red led “failure” lights up. In this event,
keep the “restart” button pressed and wait with a tap opened until the red led is off. Once the
button is released and the tap is closed, the control stops the pump at its max. Pressure.
3. WIRING DIAGRAMS FOR CONNECTING THE UNIT TO DIFFERENT KINDS OF PUMP’S
MOTORS
4. DEFECT DETECTING
5. AFTER SALES SERVICE
This control is guaranteed for a period of twelve months from the date of purchase and shall not be
subject to any claims caused by subjective misusing and disassemblies or any installations not in
accordance with the instruction.
6. TECHNICAL DATA
Power: 2.2 kW
Current: 30 A
Maximum working pressure: 10 bar
Max working temperature: 55ºC
Connection: 1"male - 1 1/4"male
Protection rating: IP65
TYPE OF DEFECT
- The pump does
not start
- The pump does
not stop
- Intermittent
pump working
- The pump is
jammed
- The electronic card is broken
- The electronic card is broken
- The flow detector is blocked in
the upper position
- The reset button is broken
- The pump does not provide
sufficient pressure
- The electronic card is broken
- The pump does not provide
sufficient pressure
- The electronic card is broken
- The pump provides a pressure
which is lower than the
restarting pressure
- Voltage failure
- Pump is jammed
- Electric cables inverted
(line/motor)
-Presence of leaks which are
higher than the minimum
flow 1 L/min
- Presence of leaks which are
lower than the minimum
flow 1 L/min
- Water failure
- Suction problems
CAUSES DEPENDING
ON THE UNIT
CAUSES NOT DEPENDING
ON THE UNIT
4

GUARANTEE
WARRANTY DOES NOT COVER
Product model
Serial number
Username
Date of sale
Company
Client's signature
The warranty period starts from the date of sale of the products and covers 1 year for all power products.
During the warranty period, free failures caused due to the use of poor-quality materials in the production and
manufacturer workmanship admitted fault are removed. The guarantee comes into force only when warranty card
and cutting coupons are properly filled. The product is accepted for repair in its pure form and full completeness.
• Mechanical damage (cracks, chips, etc.) and damage
caused by exposure to aggressive media, foreign objects
inside the unit and air vents, as well as for damage occurred
as a result of improper storage (corrosion of metal parts);
• Failures caused by overloading or product misuse, use of
the product for other purposes. A sure sign of overload
products is melting or discoloration of parts due to the high
temperature, simultaneous failure of two or more nodes,
teaser on the surfaces of the cylinder and the piston or
destruction of piston rings. Also, the warranty does not
cover failure of the automatic voltage regulator due to
incorrect operation;
• Failure caused by clogging of the fuel and cooling systems;
• Wearing parts (carbon brushes, belts, rubber seals, oil
seals, shock absorbers, springs, clutches, spark plugs,
mufflers, nozzles, pulleys, guide rollers, cables, recoil starter,
chucks, collets, removable batteries, filters and safety
elements, grease, removable devices, equipment, knives,
drills, etc.);
• Electrical cables with mechanical and thermal damage;
• Product opened or repaired by a non-authorized service center.
• Prevention, care products (cleaning, washing, lubrication,
etc.), installation and configuration of the product;
• Natural wear products (production share);
• Failures caused by using the product for the needs related
to business activities;
• If the warranty card is empty or missing seal (stamp) of the Seller;
• The absence of the holder's signature on the warranty card.
WARRANTY CARD
The product is in good conditions and fully complete. Read and agree the terms of the warranty.
Product
Model
Company
Date
of sale
Product
Model
Company
Date
of sale

www.daewoopowerproducts.com
Manufactured under license of Daewoo International Corporation, Korea
Table of contents
Other Daewoo Switch manuals
Popular Switch manuals by other brands

TekTone
TekTone NC554/8 installation instructions

prophecy
prophecy Gofanco PRO-KVMDP-2P user guide

ITT
ITT Neo-Dyn 801P5 Installation and operation manual

Rose electronics
Rose electronics UltraView Installation and operation manual

IDEC
IDEC HS5E Series manual

Converters.TV
Converters.TV 15376 Operation manual

SMC Networks
SMC Networks D-F8B Series Installation & maintenance manual

Brocade Communications Systems
Brocade Communications Systems VDX 8770-4 Hardware installation guide

Terra
Terra SRM940 manual

Larson Electronics
Larson Electronics MPD-DS-WML-NFDS Series instruction manual

Eaton
Eaton CurrentWatch ECS7 Series Instruction leaflet

Ruijie
Ruijie RG-ES200 Series Web-based configuration guide