Airflow Data
(CFM & Temperature Rise vs. External Static Pressure)
Model Motor
Speed
Tons
AC¹
External Static Pressure, (Inches Water Column)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM CFM CFM
DM80HS
0403A*A
High 31,521 --- 1,466 --- 1,414 --- 1,373 --- 1,298 --- 1,243 1,164 1,075
Med 2.5 1,160 26 1,160 26 1,132 26 1,121 26 1,082 27 1,042 997 925
Med-Lo 2961 31 955 31 948 31 932 32 913 33 882 821 803
Low 1.5 781 38 785 38 781 38 773 38 761 32 745 716 668
DM80HS
0603A*A
High 31,422 31 1,352 33 1,307 34 1,197 37 1,157 38 1,092 1,075 983
Med 2.5 1,098 40 1,081 41 1,051 42 1,039 43 1,021 44 983 924 868
Med-Lo 2919 48 913 49 892 50 847 ---- 829 ---- 818 792 728
Low 1.5 758 ---- 741 ---- 741 ---- 733 ---- 699 ---- 677 649 626
DM80HS
0604B*A
High 42,134 21 2,100 21 2,042 22 1,975 23 1,883 24 1,786 1,700 1,601
Med 3.5 1,668 27 1,663 27 1,656 27 1,645 27 1,616 28 1,549 1,492 1,391
Med-Lo 31,419 31 1,426 31 1,426 31 1,432 31 1,419 31 1,378 1,328 1,261
Low 2.5 1,134 39 1,145 39 1,166 38 1,171 38 1,160 38 1,144 1,111 1,071
DM80HS
0803B*A
High 31,607 37 1,572 38 1,547 39 1,498 40 1,448 41 1,390 1,302 1,222
Med 2.5 1,159 51 1,156 51 1,145 52 1,127 53 1,108 53 1,075 1,033 957
Med-Lo 2938 63 916 65 916 65 900 ---- 889 ---- 865 829 785
Low 1.5 785 ---- 766 ---- 743 ---- 730 ---- 709 ---- 683 666 604
DM80HS
0804B*A
High 42,051 ---- 1,983 ---- 1,895 --- 1,812 --- 1,725 --- 1,627 1,530 1,439
Med 3.5 1,736 --- 1,708 35 1,652 36 1,611 37 1,540 38 1,475 1,394 1,307
Med-Lo 31,493 35 1,668 36 1,459 41 1,429 41 1,389 43 1,339 1,274 1,204
Low 2.5 1,200 49 1,185 50 1,180 50 1,173 51 1,158 51 1,125 1,125 1,080
DM80HS
0805C*A
High 52,290 ---- 2,229 ---- 2,155 ---- 2,047 ---- 1,960 ---- 1,837 1,712 1,584
Med 41,852 --- 1,820 --- 1,777 --- 1,719 --- 1,641 36 1,567 1,469 1,382
Med-Lo 3.5 1,615 37 1,592 37 1,556 38 1,516 39 1,470 40 1,405 1,346 1,235
Low 31,290 46 1,285 46 1,265 47 1,235 48 1,214 49 1,174 1,044 904
DM80HS
1005C*A
High 52,323 --- 2,225 --- 2,120 35 2,040 36 1,974 38 1,801 1,688 1,577
Med 41,858 40 1,847 40 1,799 41 1,744 42 1,674 44 1,577 1,493 1,399
Med-Lo 3.5 1,596 46 1,587 47 1,571 47 1,552 48 1,493 50 1,397 1,326 1,217
Low 31,291 57 1,272 58 1,261 59 1,257 59 1,205 61 1,168 1,118 1,060
DM80HS
1205D*A
High 52,469 --- 2,389 --- 2,300 --- 2,223 40 2,131 42 2,027 1,902 1,786
Med 41,575 56 1,558 57 1,545 58 1,513 59 1,500 59 1,419 1,354 1,271
Med-Lo 3.5 1,402 63 1,380 64 1,343 66 1,319 67 1,296 69 1,245 1,183 1,106
Low 31,200 ---- 1,186 ---- 1,161 ---- 1,127 ---- 1,082 ---- 1,042 995 926
DM80HS
1405D*A
High 52,469 --- 2,389 --- 2,300 --- 2,223 40 2,131 42 2,027 1,902 1,786
Med 41,575 56 1,558 57 1,545 58 1,513 59 1,500 59 1,419 1,354 1,271
Med-Lo 3.5 1,402 63 1,380 64 1,343 66 1,319 67 1,296 69 1,245 1,183 1,106
Low 31,200 ---- 1,186 ---- 1,161 ---- 1,127 ---- 1,082 ---- 1,042 995 926
Notes
• CFM in chart is without lter(s). Filters do not ship with this furnace, but must be provided by the installer. If the furnace requires two return lters, this chart assumes both lters
are installed.
• All furnaces ship as high-speed cooling and medium-speed heang. Installer must adjust blower cooling and heang speed as needed.
• For most jobs, 400 CFM per ton for cooling is desirable.
• INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE.
• This chart is for informaon only. For sasfactory operaon, external stac pressure should not exceed value shown on the rang plate.
• The dashed (----) areas indicate a temperature rise not recommended for this model.
• At higher altudes, a properly derated unit will have approximately the same temperature rise at a parcular CFM, while ESP at the CFM will be lower.
4www.daikincomfort.com SS-DM80HS SS-DM80HS www.daikincomfort.com 5