
Start-Up Responsibility
The start-up organization is responsible for determining that
the furnace, as installed and as applied, will operate within the
limits specied on the furnace rating plate.
1. The furnace must not exceed the specied Maximum
MBh Input. See Verify Input Rate on page 18.
2. The furnace must not operate at an airow below the
specied Minimum Airow CFM. On variable air volume
systems it must be determined that the furnace will not
be operated if or when system cfm is reduced below the
specied minimum airow cfm.
3. It must be established that the gas supply is within the
proper pressure range. See Gas Pressure Requirements
on page 6.
Start-Up Procedure
WARNING
Overheating or failure of the gas supply to shut off can cause equipment
damage, severe personal injury or death. Turn off the manual gas valve to
the appliance before shutting off the electrical supply..
Start-up and service of this equipment must be done by
trained, experienced technicians. It is highly recommended
that the initial start-up and future service be performed by
Daikin trained technicians who are familiar with working on
live equipment. A representative of the owner or the operator
of the equipment should be present during start-up to receive
instructions in the operation, care and adjustment of the unit.
Before Start-Up
1. Notify inspectors or representatives who may be required
to be present during start-up of gas fuel equipment.
These could include the gas utility company, city gas
inspectors, heating inspectors, etc.
2. Review the equipment and service literature and become
familiar with the location and purpose of the burner
controls. Determine where the gas and power can be
turned o at the unit, and before the unit.
3. Determine that power is connected to the unit and
available.
4. Determine that the gas piping, meter, and service
regulator have been installed, tested, and meet the
equipment requirements.
5. Determine that proper instruments will be available for
the start-up. A proper start-up requires the following:
voltmeter, manometer or gauges with ranges for both
manifold pressure and inlet gas pressure, keyboard
display module or a 20K ohm/volt meter for ame
safeguard, signal strength measurement, CO2indicator,
carbon monoxide indicator, and a stopwatch for timing
the gas meter.
Start-Up Preliminary
Close main and pilot gas cocks. Install a keyboard display
module or connect a 20K ohm/volt meter to the test jack on the
ame safeguard. See Figure 7.
1. Check the burner fan wheel for binding, rubbing, or loose
setscrews. Inspect the air damper and gas valve linkages
for binding and check the linkage fasteners for tightness.
2. Check power. Position control switch on burner panel to
AUTO. The POWER LED on the ame safeguard should
come on and, after 10 seconds, the burner motor should
start. Check for Counter-clockwise rotation as viewed
through blower housing inlet. If motor does not start,
press the reset button on the ame safeguard. If motor
still does not start, consult the appropriate section of the
Troubleshooting Chart, page 26. Continue on to Item 3
when burner motor will run when the switch is positioned
to AUTO.
3. Check voltage. With the switch at AUTO, measure the
voltage across ame safeguard terminals 5 and L2. If it
is not between 108 and 132 volts, check the voltage and
tapping connections to the supplying transformer at the
unit’s main control panel.
4. Purge the gas lines. Close the main gas valves and turn
the electrical switches o. Make sure there are no arcing
or sparking switches, motors, or other equipment, pilot
lights, open ames, or other sources of ignition in the
areas sharing ventilation. Disconnect the pilot gas tube at
the pilot pressure regulator and bleed the gas line of all
air. Close the pilot cock and reconnect the pilot tubing.
5. Leak check. Using a rich soap-water mixture and a
brush, check the gas lines for leaks. Correct all leaks
before starting burner.
IM 684-6 • ROOFTOP SYSTEMS 10 www.DaikinApplied.com