Daintree GE current 365DisInFx LPU Series User manual

When using electrical equipment, basic safety precautions should always be followed including the following:
This equipment is designed for use with germicidal UV radiation sources and must be installed in compliance with
competent technical directions to prevent risk of personal injury from UV radiation.
UV radiation can pose a risk of personal injury. Overexposure can result in damage to eyes and bare skin. To reduce
the risk of overexposure this equipment must be installed in accordance with the manufacturer’s site planning
recommendations. This may include instructions on the relative location of each germicidal system component, the
minimum distances between UV-generating devices and other objects or surfaces, and protection from line-of-sight
exposure to UV radiation in occupied spaces located above the equipment mounting area (e.g. upper oor balconies,
open staircases, etc.)
UV and optical radiation can be reected by surrounding surfaces such as ceilings and walls. Since the reective
properties of surfaces can vary widely, it should be considered as part of site planning. Follow the manufacturer’s
recommendations for selecting appropriate ceiling and wall nishes.
IT IS THE RESPONSIBILITY OF THE INSTALLER TO ENSURE THAT PERSONS WILL NOT BE EXPOSED TO EXCESSIVE
UV OR OPTICAL RADIATION DURING EQUIPMENT OPERATION. THIS WILL REQUIRE THE INSTALLER TO
CONDUCT AN ASSESSMENT OF IRRADIANCE OR ILLUMINANCE LEVELS IN THE SURROUNDING OCCUPIED
SPACES PRIOR TO OCCUPANCY.
Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by
unauthorized personnel.
Maintenance and servicing of this UV generating equipment shall be performed by authorized personnel. Service
personnel must wear appropriate Personal Protective Equipment (PPE) if the equipment will be in operation during
the maintenance or servicing work. Contact the equipment manufacturer for PPE recommendations and guidance.
The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
Do not use this equipment for other than intended use.
Device using Current’s 365DisInFx™ technology are not intended to be used as medical
devices and are not registered as such under any applicable laws.
IMPORTANT SAFEGUARDS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
Installation Guide
DSX105 |A-1034174
365DisInFx™LPU- Series

365DisInFx™
LPU Series-UVC (120-277V)
BEFORE YOU BEGIN
Read these instructions and the Application Design
Guide (IND701)) for LPU Series layout completely
and carefully.
Installation Guide
DSX105 |A-1034174
RISK OF FIRE
• Follow all NEC and local codes.
• Use only UL approved wire for input/output connections.
Minimum size 18 AWG (0.75mm2).
RISQUES D’INCENDIE
• Respectez tous les codes NEC et codes locaux.
• N’utilisez que des ls approuvés par UL pour les entrées/sorties de
connexion. Taille minimum 18 AWG (0.75mm2).
RISK OF ELECTRICAL SHOCK
• Turn power off before inspection, installation or removal.
• Properly ground electrical enclosure.
RISQUE D’ÉLECTROCUTION
• Coupez l’alimentation avant l’inspection, l’installation ou l’enlèvement
du produit.
• Assurez-vous de correctement mettre à la terre le boîtier
d’alimentation électrique.
WARNING/AVERTISSEMENT
WARNING/AVERTISSEMENT
• Turn power off prior to installation; risk of UV exposure.
• Coupez l’alimentation avant d’installer; risque d’exposition à un
rayonnement UV.
• Wear appropriate Personal Protective Equipment (PPE).
• Portez les équipements de protection individuelle (EPI) appropriés.
• This product contains components that may be susceptible to
Electrostatic Discharge (ESD) under certain conditions. As a precaution
avoid touching the LEDs that are exposed through the plastic cover.
CAUTION/ATTENTION
365DisInFx™LPU- Series
Tools and Components Required:
• LPU Series xture
• Slot or Phillips head screwdriver
• UL Listed conduit connections per NEC/CEC for nominal conduit
trade sizes 1/2” or 3/4”
• UL Listed wire connectors
• Wire cutters
• Appropriate Personal Protective Equipment (PPE)
CAUTION/ATTENTION
RISK OF UV RADIATION OVEREXPOSURE
• For 8.5-9ft. :HIGHEST IRRADIANCE AT 500 MM: 0.022 µW/cm2
• Pour 8.5-9pi. :IRRADIANCE LA PLUS ÉLEVÉE À 500 MM: 0.022 µW/ cm
2
• For 9-10ft. HIGHEST IRRADIANCE AT 500 MM: 0.038 µW/cm2
• Pour 9-10pi. IRRADIANCE LA PLUS ÉLEVÉE À 500 MM: 0.038 µW/cm2
• For 10-11ft. : HIGHEST IRRADIANCE AT 500 MM: 0.074 µW/cm2
• Pour 10-11pi. : IRRADIANCE LA PLUS ÉLEVÉE À 500 MM: 0.074 µW/cm
2
• For 11ft. And more : HIGHEST IRRADIANCE AT 500 MM: 0.12 µW/cm2
• Pour 11pi. et plus : IRRADIANCE LA PLUS ÉLEVÉE À 500 MM: 0.12 µW/cm2
Components Supplied:
• (1) LPU Device UVC LED module
• (1) BZ50 Power Pack
• (1) Mounting Plate
• (1) 6ft Plenum Rated Cables
• (2) #8-32 x 3/4in Screws
For Technical Support, Please Contact:
• By phone: 1-888-694-3533
• By Email: [email protected]
Save These Instruction
Use only in the manner intended by the manufacturer.
If you have any questions, contact the manufacturer.
Installation and servicing should be performed by qualied personnel.
Prepare Electrical Wiring
Electrical Requirements
• The LPU device must be connected to the mains
supply according to its ratings on the product label.
Grounding Instructions
• The grounding and bonding of the overall system shall
be done in accordance to with National Electric Code
(NEC) and local codes.

Installation Guide365DisInFx™LPU- Series
3
IMPORTANT NOTES — PLEASE READ Before Installing
Mounting Height:
• This installation guide is to be used in conjunction with the
Application Design Guide (IND701) for LPU Series layout.
• LPU10ADQQSTxxWHTE, where xx denes the mounting height
per the table below.
• This product can only be installed as part of an indoor ceiling.
RISK OF PERSONAL INJURIES FROM UV RADIATION & RISK OF
REDUCED PATHOGEN INACTIVATION
• Risk of UV radiation overexposure if installed lower than minimum height
and risk of reduced effectiveness if installed above intended height range.
• Mount Product within the assigned mounting height range.
• Install according to approved layout by Current and conrm any
changes by Current.
CAUTION/ATTENTION
• Product must be inspected once a month to verify normal operation and
conrm the device is properly secured to the ceiling per these install instructions.
• Ensure power to LPU device is shut off prior to performing any
maintenance near or around the ceiling where the LPU device is installed.
• For cleaning maintenance, please use dry paper towel or Air spray (no
oil or chemical base) or a fabric duster to wipe down any dust that might
be gathered on the LPU device. Please do not touch the center LED. For
further guidelines please consult guidelines from NEMA GD 4-2020
NOTICE
GENERAL VISUAL AND AUDIBLE INDICATOR OPERATION
LED Indicator Green Yellow Red
Status On = Power On On = UV On Flashing and audible alarm = Fault
Action Normal Operation Normal Operation Perform a Power Cycle, if Fault continues
replace unit
Cat-Logic ‘xx’ Mounting Height/Ceiling Height
08 8’6” up to 9’
09 9’ up to 10’
10 10’ up to 11’
11 11’ and higher
Yellow LED
UVC LED
Green LED
Red LED (Flashes)
[
Mounting height, from
oor to lowest point of the
product. Please refer to Table
1, for exact distance needed
per cat logic.
Ceiling
Floor
LPU Product
Wall
Diagram:
Table 1:

Installation Guide365DisInFx™LPU- Series
WHITE
BZ-50
Power Pack
LPU
Device
NEUTRAL
BLACK
BLACK
RED
COMMON
+24VDC
LINE 120VAC
277VAC
1
2
1
2
1
2
1
2
BZ-50 Power Pack
WattStopper
For safety, turn off main power prior to installation.
Notes: The LED Module must be used with BZ50, as Provided.
A
A
Carefully unpack unit from its packaging. Properly inspect for
defects before installing. Wear work gloves to prevent dirt and
oil from being transferred to the unit.
Install the BZ50 to a junction box and make the appropriate AC
connection. (Junction box and connectors not provided. Please ensure
UL listed connectors are being used.)
High
Voltage
Low Voltage
Class 2
B
B
4
Installation
1
Electrical Connections
2
RISK OF ELECTRICAL SHOCK
Disconnect power before servicing or installing product. RISQUE DE CHOC ÉLECTRIQUE.
Couper l’alimentation avant le dépannage ou avant l’installation du produit.
WARNING/AVERTISSEMENT
1
2
1
2
1
2
1
2
BZ-50 Power Pack
WattStopper
Install the mounting plate. If installing to a junction box, ensure that
no AC / Class 1 circuitry is present. (Junction box not provided for T-Grid
installation, please refer to section 3c.)
C
Connect the Plenum Rated Cable provided to the Power pack’s
low voltage wires and the LPU LED module.
Cable from
BZ-50
D

Installation Guide365DisInFx™LPU- Series
Insert the LED module into the mounting plate, twist LED module
clockwise until a ‘click’ sound is made, locking the LED module in
place. Not applicable to T-Grid installation.
E
Upon completing the installation of LPU module in ceiling.
Please peel of the label to UVC transmission.
Turn on the breaker and ensure the Green and Yellow LED are
on. Turn on unit when all personnel are located in the occupied
space. Occupied space is dened as the area in a room within
7ft of the oor.
F
G
Mounting Options
3
Direct install on Drywall.
A
Direct install on Junction box. Note: junction box not provided)
B
Electrical Connections
2

Installation Guide365DisInFx™LPU- Series
www.gecurrent.com
© 2020 Current Lighting Solutions, LLC. All rights reserved. GE and the GE monogram are trademarks of the
General Electric Company and are used under license. Information provided is subject to change without notice.
All values are design or typical values when measured under laboratory conditions.
DSX105 (A-1034174 Rev. 12/21/2020)
T-Grid Install
3c
These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation, operation or maintenance.
Should further information be desired or should particular problems arise which are not covered sufciently for the purchaser’s purposes, the matter should be referred to GE current.
Ces instructions ne prétendent pas couvrir tous les détails ou variantes de l’équipement ni couvrir toutes les conditions possibles à satisfaire en rapport avec l’installation, l’opération ou l’entretien. Si des informations
supplémentaires sont souhaitées sur des aspects qui ne sont pas sufsamment couverts pour satisfaire les besoins du client, ou sides problèmes particuliers se présentent, veuillez addresser ces questions à GE current.
All product and company names are trademarks™ or registered® trademarks of their respective holders. Use of them does not imply any afliation with or endorsement by them.
All specications are subject to change without notice.
Questions:
Web: products.gecurrent.com | Phone: 1-866-855-8629
FCC Statements:
Luminaires using Current’s 365DisInFx™ technology are not intended to be used as medical devices and are not registered as such under any applicable laws.
This device complies with part 15 of the FCC rules for the United States and Industry Canada (IC) license exempt RSS standard(s). Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Any changes or modications not
expressly approved by the manufacturer could void the user’s authority to operate this equipment. This product is intended for commercial use only.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation. CAN ICES-005 (A) / NMB-005 (A)
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance
with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be
required to correct the interference at his own expense.clase [A] cumple con la norma canadiense CAN ICES-005 (A) / NMB-005 (A). Ce DEFR de la classe [A] est conforme à la NMB-005 du Canada.
Break T-grid mounting clip into two pieces.
Insert ¼-20 carriage bolt into lower half.
Insert lower half onto T-grid. Insert tab of
upper half into slot of lower half and click
release tab into place.
Screw on the UVC LED module. The mounting
plate used for Drywall or Junction Box
installation is not required and provided.
Complete install by following step D, F & G under
Electrical connections. (Step E not required.)
Make An Informed Decision
5
1. UV radiation can pose a risk of personal injury. Overexposure can result in damage to eyes and bare skin. To reduce risk of overexposure,
equipment must be installed in accordance with manufacturer’s site planning and application recommendations, including minimum ceiling
height restrictions.
2. UV solutions are intended for common high trafc spaces and not recommended for dwellings or home use.
3. Installation of the devices should be performed by qualied professionals as detailed in Current’s installation guid
4. To allow for occupancy during use, Current products comply with IEC 62471 – Photobiological Safety of Lamps and Lamp Systems standards
and American Conference of Governmental Industrial Hygienists (ACGIH®) TLVs® guidelines when installed as directed.
5. Current’s UV products are meant to be used in conjunction with other protective measures like manual cleaning and the use of proper PPE.
They are not a substitute for other measures.
6. Current products are not intended for use as a medical device.
7. If combining two or more UV solutions, whether from GE Current, a Daintree company and/or other manufacturers, please consult a trained
product application representative to ensure the total irradiance (UV dose) does not exceed recommended human exposure limits. To the
extent UV solutions are combined, it may impact inactivation rates.
BA C
Table of contents