Installation and servicing of the
compressor by qualified personnel
only. Follow these instructions and
sound refrigeration engineering practice
relating to installation, commissioning,
maintenance and service.
A: Model number
B: Serial Number
C: Manufacturing year
D: Internal protection
E: Supply voltage range
F: Locked rotor current
Maximum operating current
G: Lubricant type and nominal charge
H: Approved Refrigerant
push
push
push
Operating limits
Electrical connections Name plate
C
T₁
Ring connect screw terminals
C terminal box type
S
T₂
R
T₃
Ring connect screw terminals
C terminal box type
MADE IN CHINA
Model no : LLZ034T4LQ9B
Serial no : HM2500000001
380-415 V 3~50Hz
460 V 3~60Hz
LR: 150A MAX OPER. 22.8 A
Lubricant: P.O.E. / 2.51 L
Refrigerant: Group 1
P.E.D.
Marking
PS 25.44 bar 30.7 bar
TS max 55 °C 150 °C
TS min -40 °C -40 °C
Volume 4.70l 5.30l
2020
Thermally protected
876543210
PROTECTED BY DOMESTIC AND FOREIGN PATENTS
089
IS 10617 2018
CM/L-4100085780
LP side HP side
A
B
C
D
E
G
H
F
Condensing temperature (°C)
Evaporating temperature (°C)
Evaporating temperature (°F)
Condensing temperature (°F)
5
10
15
20
25
30
35
40
45
50
55
60
65
70
-40 -35 -30 -25 -20 -15 -10 -5 0 5 10 15
-40 -31 -22 -13 -4 5 14 23 32 41 50 59
41
50
59
68
77
86
95
104
113
122
131
140
149
158
S.H. = 10K
RGT = 20°C
0 32
-45
-49
-50
-58
-55
-67
Condensing temperature (°C)
Evaporating temperature (°C)
Evaporating temperature (°F)
Condensing temperature (°F)
5
10
15
20
25
30
35
40
45
50
55
60
65
70
-40 -35 -30 -25 -20 -15 -10 -5 0 5 10 15
-40 -31 -22 -13 -4 5 14 23 32 41 50 59
41
50
59
68
77
86
95
104
113
122
131
140
149
158
S.H. = 10K
RGT = 20°C
0 32
-45
-49
-50
-58
-55
-67
Condensing temperature (°C)
Evaporating temperature (°C)
Evaporating temperature (°F)
Condensing temperature (°F)
5
10
15
20
25
30
35
40
45
50
55
60
65
70
-40 -35 -30 -25 -20 -15 -10 -5 0 5 10 15
-40 -31 -22 -13 -4 5 14 23 32 41 50 59
41
50
59
68
77
86
95
104
113
122
131
140
149
158
S.H. = 10K
RGT = 20°C
0 32
-45
-49
-50
-58
-55
-67
Condensing temperature (°C)
Evaporating temperature (°C)
Evaporating temperature (°F)
Condensing temperature (°F)
5
10
15
20
25
30
35
40
45
50
55
60
65
70
-40 -35 -30 -25 -20 -15 -10 -5 0 5 10 15
-40 -31 -22 -13 -4 5 14 23 32 41 50 59
41
50
59
68
77
86
95
104
113
122
131
140
149
158
S.H. = 10K
RGT = 20°C
0 32
-45
-49
-50
-58
-55
-67
R454C LI
R455A LI
R454C Non LI
R455A Non LI

Instructions
Danfoss scroll compressors
LLZ - B
© Danfoss | Climate Solutions | 2021.08 8510306P01AB - AN382129347378en-000101 | 1
Instructions
2 | AN382129347378en-000101 - 8510306P01AB © Danfoss | Climate Solutions | 2021.08
1 – Introduction
These instructions pertain to the LLZ scroll
compressors used for refrigeration systems. They
provide necessary information regarding safety
and proper usage of this product.
2 – Handling and storage
•Handle the compressor with care. Use the
dedicated handles in the packaging. Use the
compressor lifting lug and use appropriate and
safe lifting equipment.
•Store and transport the compressor in an upright
position.
•Store the compressor between -35°C and 70°C /
-31°F and 158°F.
•Don’t expose the compressor and the packaging
to rain or corrosive atmosphere.
3 – Safety measures before assembly
Never use the compressor in a flammable
atmosphere.
•Mount the compressor on a horizontal flat surface
with less than 7° slope.
•Verify that the power supply corresponds to the
compressor motor characteristics (see nameplate).
•When installing a compressor for R452A, R404A/
R507, R448A/R449A, use equipment specifically
reserved for HFC refrigerants which was never
used for CFC or HCFC refrigerants.
•Use clean and dehydrated refrigeration-grade
copper tubes and silver alloy brazing material.
•Use clean and dehydrated system components.
•The piping connected to the compressor must be
flexible in 3 dimensions to dampen vibrations.
•The compressor must always be mounted with the
rubber grommets supplied with the compressor.
4 – Assembly
•Slowly release the nitrogen holding charge
through discharge and suction ports.
•Connect the compressor to the system as soon as
possible to avoid oil contamination from ambient
moisture.
•Avoid material entering into the system while
cutting tubes. Never drill holes where burrs
cannot be removed.
•Do not exceed the maximum tightening torque
for rotolock connections
Rotolock connections Tightening torque
1” Rotolock 80 Nm±10Nm
1” 1/4 Rotolock 90 Nm±10Nm
1” 3/4 Rotolock 110 Nm±10Nm
• Connect the required safety and control devices.
When the schrader port, if any, is used for this,
remove the internal valve.
5 – Leak detection
Never pressurize the circuit with oxygen or dry
air. This could cause fire or explosion.
•Do not use leak detection dye.
•Perform a leak detection test on the complete
system.
•The low side test pressure must not exceed 31 bar
/450 psi.
•When a leak is discovered, repair the leak and
repeat the leak detection.
6 – Vacuum dehydration
•Never use the compressor to evacuate the system.
•Connect a vacuum pump to both the LP & HP
sides.
•Pull down the system under a vacuum of
500 µm Hg (0.67 mbar) / 0.02 inch Hg absolute.
•Do not use a megohmmeter nor apply power to
the compressor while it is under vacuum as this
may cause internal damage.
7 – Electrical connections
•Switch off and isolate the main power supply.
•All electrical components must be selected as per
local standards and compressor requirements.
•Refer to page 1 for electrical connections details.
For three phase applications, the terminals are
labeled T1, T2, and T3.
•Danfoss scroll compressors will only compress gas
while rotating counter-clockwise (when viewed
from the compressor top). Three-phase motors,
however, will start and run in either direction,
depending on the phase angles of the supplied
power. Care must be taken during installation
to ensure that the compressor operates in the
correct direction.
•Use ø 4.8 mm / #10 - 32 screws and ¼” ring
terminals for the power connection with ring
connect screw terminal (C type). Fasten with 3 Nm
torque.
•Use a self tapping screw to connect the
compressor to earth.
8 – Filling the system
•Keep the compressor switched off.
•Keep the refrigerant charge below the indicated
charge limits if possible. Above this limit; protect
the compressor against liquid flood-back with a
pump-down cycle or suction line accumulator.
•Never leave the filling cylinder connected to the
circuit.
Compressor models Refrigerant charge limit
LLZ013-015-018 4.5 kg / 10 lb
LLZ024-034 7.2 kg / 16 lb
M
DGT
HPs
180 s
TH
LP
CONTROL CIRCUIT
F1F1
KM
KM
KM
KA KA
A1
A2
A3
KA
KA
KS
KS
KS
L1 L3 L2
Q1
T1
T3
T2
LLSV KS
PM
Three phase (Wiring diagram with pump-down cycle)
Instructions
8510306P01AB - AN382129347378en-000101 | 3
© Danfoss | Climate Solutions | 2021.08
9 – Verification before commissioning
Use safety devices such as safety pressure switch
and mechanical relief valve in compliance with both
generally and locally applicable regulations and
safety standards. Ensure that they are operational
and properly set.
Check that the settings of high-pressure switches
don’t exceed the maximum service pressure of any
system component.
•A low-pressure switch is recommended to avoid
low pressure operation.
Minimum setting for R454C/R455A
1.0bar (absolute) / 14.5psia
•Verify that all electrical connections are properly
fastened and in compliance with local regulations.
•When a crankcase heater is required, it must be
energized at least 24 hours before initial start-up
and start-up after prolonged shutdown.
10 – Start-up
•Never start the compressor when no refrigerant is
charged.
•Do not provide any power to the compresor
unless suction and discharge service valves are
open, if installed.
•Energize the compressor. It must start promptly.
If the compressor does not start, check wiring
conformity and voltage on terminals.
•Eventual reverse rotation can be detected by
following phenomena; the excessive noise,
no pressure differential between suction
and discharge, and line warming rather than
immediate cooling. A service technician should
be present at initial start-up to verify that
supply power is properly phased and that the
compressor is rotating in the correct direction. For
LLZ compressors, phase monitors are required for
all applications.
•If the internal overload protector trips out, it must
cool down to 60°C / 140°F to reset. Depending on
ambient temperature, this may take up to several
hours.
11 – Check with running compressor
Check current draw and voltage. Measurement
of amps and volts during running conditions must
be taken at other points in the power supply, not in
the compressor electrical box.
•Check suction superheat to reduce risk of
slugging.
•Observe the oil level in the sight glass (if provided)
for about 60 minutes to ensure proper oil return to
the compressor.
•Respect the operating limits.
•Check all tubes for abnormal vibration.
Movements in excess of 1.5 mm / 0.06 in require
corrective measures such as tube brackets.
•When needed, additional refrigerant in liquid
phase may be added in the low-pressure side as far
as possible from the compressor. The compressor
must be operating during this process.
•Do not overcharge the system.
•Never release refrigerant to atmosphere.
•Before leaving the installation site, carry out
a general installation inspection regarding
cleanliness, noise and leak detection.
•Record type and amount of refrigerant charge
as well as operating conditions as a reference for
future inspections.
12 – Maintenance
Internal pressure and surface temperature
are dangerous and may cause permanent injury.
Maintenance operators and installers require
appropriate skills and tools. Tubing temperature
may exceed 100°C / 212°F and can cause severe
burns.
Ensure that periodic service inspections to
ensure system reliability and as required by local
regulations are performed.
To prevent system related compressor problems,
following periodic maintenance is recommended:
•Verify that safety devices are operational and
properly set.
•Ensure that the system is leak tight.
•Check the compressor current draw.
•Confirm that the system is operating in a way
consistent with previous maintenance records
and ambient conditions.
•Check that all electrical connections are still
adequately fastened.
•Keep the compressor clean and verify the absence
of rust and oxidation on the compressor shell,
tubes and electrical connections.
•Acid / moisture content in system and oil should
be checked regularly.
13 - Warranty
Always transmit the model number and serial
number with any claim filed regarding this product.
The product warranty may be void in following
cases:
•Absence of nameplate.
•External modifications; in particular, drilling,
welding, broken feet and shock marks.
•Compressor opened or returned unsealed.
•Rust, water or leak detection dye inside the
compressor.
•Use of a refrigerant or lubricant not approved by
Danfoss.
•Any deviation from recommended instructions
pertaining to installation, application or
maintenance.
•Use in mobile applications.
•Use in explosive atmospheric environment.
•No model number or serial number transmitted
with the warranty claim.
14 – Disposal
Danfoss recommends that compressors
and compressor oil should be recycled
by a suitable company at its site.
4 | AN382129347378en-000101 - 8510306P01AB © Danfoss | Climate Solutions | 2021.08


This manual suits for next models

2

Other Danfoss Air Compressor manuals

Danfoss MLM Series Instruction Manual

Danfoss

Danfoss MLM Series Instruction Manual

Danfoss MT User manual

Danfoss

Danfoss MT User manual

Danfoss CH290 Instruction Manual

Danfoss

Danfoss CH290 Instruction Manual

Danfoss DSG Series User manual

Danfoss

Danfoss DSG Series User manual

Danfoss LLZ User manual

Danfoss

Danfoss LLZ User manual

Danfoss PSH051-4 Instruction Manual

Danfoss

Danfoss PSH051-4 Instruction Manual

Danfoss VRJ Instruction Manual

Danfoss

Danfoss VRJ Instruction Manual

Danfoss AKC 25H1 User manual

Danfoss

Danfoss AKC 25H1 User manual

Danfoss CXH User manual

Danfoss

Danfoss CXH User manual

Danfoss VTZ Series User manual

Danfoss

Danfoss VTZ Series User manual

Danfoss BOCK FK20 User manual

Danfoss

Danfoss BOCK FK20 User manual

Danfoss PSH Series User manual

Danfoss

Danfoss PSH Series User manual

Danfoss DSF485A4ABA User manual

Danfoss

Danfoss DSF485A4ABA User manual

Danfoss GD30FDC User manual

Danfoss

Danfoss GD30FDC User manual

Danfoss BOCK UL-HGX24 CO2 T Series User manual

Danfoss

Danfoss BOCK UL-HGX24 CO2 T Series User manual

Danfoss Turbocor Twin-Turbine TTS Series User guide

Danfoss

Danfoss Turbocor Twin-Turbine TTS Series User guide

Danfoss BOCK UL-HGX12 CO2 T User manual

Danfoss

Danfoss BOCK UL-HGX12 CO2 T User manual

Danfoss Turbocor TT Series User manual

Danfoss

Danfoss Turbocor TT Series User manual

Danfoss PCH065A8VBA User manual

Danfoss

Danfoss PCH065A8VBA User manual

Danfoss Performer SM Series Instruction Manual

Danfoss

Danfoss Performer SM Series Instruction Manual

Danfoss MLZ Series User manual

Danfoss

Danfoss MLZ Series User manual

Danfoss Turbocor VTT Series User manual

Danfoss

Danfoss Turbocor VTT Series User manual

Danfoss Performer SH090 Instruction Manual

Danfoss

Danfoss Performer SH090 Instruction Manual

Danfoss Maneurop NTZ Series Instruction Manual

Danfoss

Danfoss Maneurop NTZ Series Instruction Manual

Popular Air Compressor manuals by other brands

Becker KDT 3.100 operating instructions

Becker

Becker KDT 3.100 operating instructions

DeWalt D55141-CA instruction manual

DeWalt

DeWalt D55141-CA instruction manual

General Air Products LT Series Installation, operation and maintenance manual

General Air Products

General Air Products LT Series Installation, operation and maintenance manual

Ingersoll-Rand CENTAC instruction manual

Ingersoll-Rand

Ingersoll-Rand CENTAC instruction manual

Bitzer F400 operating instructions

Bitzer

Bitzer F400 operating instructions

Metabo Mega 450 W + D Brochure & specs

Metabo

Metabo Mega 450 W + D Brochure & specs

Sullair LS-25S Operator's manual and parts list

Sullair

Sullair LS-25S Operator's manual and parts list

VEVOR FB3500-10A300 user manual

VEVOR

VEVOR FB3500-10A300 user manual

HARDELL CZCQ-101 Operator's manual

HARDELL

HARDELL CZCQ-101 Operator's manual

Hydrovane V04 PUAS Series Service manual

Hydrovane

Hydrovane V04 PUAS Series Service manual

Jula Meec tools 016372 operating instructions

Jula

Jula Meec tools 016372 operating instructions

Philips RESPIRONICS InnoSpire Essence user manual

Philips

Philips RESPIRONICS InnoSpire Essence user manual

Dorin innovation H Series manual

Dorin innovation

Dorin innovation H Series manual

EINHELL Euro 8/24 operating instructions

EINHELL

EINHELL Euro 8/24 operating instructions

Porter-Cable D24938-044-2 instruction manual

Porter-Cable

Porter-Cable D24938-044-2 instruction manual

GÜDE 300/10/50 DG 12 TLG manual

GÜDE

GÜDE 300/10/50 DG 12 TLG manual

Focusrite Sonible Fast manual

Focusrite

Focusrite Sonible Fast manual

Craftsman 919.156640 owner's manual

Craftsman

Craftsman 919.156640 owner's manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.