Datcon DT1600 U Series User manual

DT1600 Ux xx xx
AC Voltage Transmitters
Operating Instructions

DT1600 Ux xx xx
2 20180621-V0
Contents
1. About this document.....................................................4
1.1. Function ................................................................................... 4
1.2. Target group............................................................................. 4
1.3. Symbolism used....................................................................... 4
2. For your safety...............................................................5
2.1. Authorized personnel ............................................................... 5
2.2. Appropriate use........................................................................ 5
2.3. Warning about misuse ............................................................. 5
2.4. General safety instructions....................................................... 5
2.5. CE conformity........................................................................... 5
2.6. Environmental instructions ....................................................... 5
3. Product description.......................................................6
3.1. Delivery configuration............................................................... 6
3.2. Type designation...................................................................... 6
3.3. Principle of operation ............................................................... 6
3.4. Adjustment ............................................................................... 7
3.5. Indicator ................................................................................... 7
3.6. Storage and transport .............................................................. 8
4. Mounting.........................................................................9
4.1. General instructions ................................................................. 9
4.2. Main dimensions of the instrument .......................................... 9
4.3. Mounting procedure ............................................................... 10
5. Connecting ...................................................................11
5.1. Preparing the connection ....................................................... 11
5.2. Connecting to the power network........................................... 12
5.3. Connecting the signal processing unit and the power supply 13
5.4. Put the instrument under supply voltage................................ 13

DT1600 Ux xx xx
20180621-V0 3
6. Fault rectification.........................................................14
6.1. Fault finding............................................................................ 14
6.2. Repairing................................................................................ 14
7. Dismounting.................................................................15
7.1. Dismounting procedure .......................................................... 15
7.2. Disposal ................................................................................. 15
8. Calculation for application..........................................16
8.1. Calculations............................................................................ 16
9. Appendix.......................................................................17
9.1. Technical specification ........................................................... 17
9.2. Application example ............................................................... 19

DT1600 Ux xx xx
4 20180621-V0
1. About this document
1.1. Function
This operating instructions manual has all the information
you need for quick set-up and safe operation of
DT1600 Ux xx xx.
Please read this manual before you start setup.
1.2. Target group
This operating instructions manual is directed to trained
personnel. The contents of this manual should be made
available to these personnel and put into practice by them
1.3. Symbolism used
Information, tip, note
This symbol indicates helpful additional information.
Caution, warning, danger
This symbol informs you of a dangerous situation that could
occur. Ignoring this cautionary note can impair the person
and/or the instrument.
•
List
The dot set in front indicates a list with no implied
sequence.
→Action
This arrow indicates a single action.
1
Sequence
Numbers set in front indicate successive steps in a
procedure.

DT1600 Ux xx xx
20180621-V0 5
2. For your safety
2.1. Authorized personnel
All operations described in this operating instructions
manual must be carried out only by trained and authorized
specialist personnel. For safety and warranty reasons, any
internal work on the instruments must be carried out only by
DATCON personnel.
2.2. Appropriate use
The DT1600 Ux xx xx an AC voltage transmitter.
Detailed information on the application range is available in
Chapter 3. Product description.
2.3. Warning about misuse
Inappropriate or incorrect use of the instrument can give rise
to application-specific hazards, or damage to system
components through incorrect mounting or adjustment.
2.4. General safety instructions
The DT1600 Ux xx xx is a high-tech instrument requiring the
strict observance of standard regulations and guidelines.
The user must take note of the safety instructions in this
operating instructions manual, the country-specific
installation standards as well as all prevailing safety
regulations and accident prevention rules.
2.5. CE conformity
The DT1600 Ux xx xx is in conformity with the provisions of
the following standard:
EN 61326:2004 (EMC)
EN 61010-1:2001 (safety)
2.6. Environmental instructions
Protection of the environment is one of our most important
duties.
Please take note of the instructions written in the following
chapters:
•Chapter 3.6. Storage and transport
•Chapter 7.2. Disposal

DT1600 Ux xx xx
6 20180621-V0
3. Product description
3.1. Delivery configuration
Delivered items The scope of delivery encompasses:
•DT1600 Ux xx xx
•documentation:
this operating instructions manual
certification
warranty
3.2. Type designation
3.3. Principle of operation
Area of application The DT1600 Ux xx xx AC Voltage Transmitters provide an
output signal proportionally with the average value (F) or
with the TRMS value (R) of the input AC voltage.
The version marked with R is recommended to use for
measure of non-sinusoidal signals.
The output can be current (0-20 mA, 4-20 mA), active (A) or
passive (P) or voltage (0-10 V).
In all types the input, the output and power supply are
galvanic isolated from each other.
Operating principle
The AC voltage connected to the input is transformed and
isolated by the input transformer. The secondary voltage of
the transformer is lead to the AC/DC converter. The DC
voltage controls the output current or voltage according to
the input AC current.

DT1600 Ux xx xx
20180621-V0 7
Power supply There are two power supply versions:
18-40 VDC / 14-29 VAC (DT1600 Ux xx xx) or
140-250 VAC / 180-250 VDC (DT1600 Ux xx xx PS).
The overcurrent protection in installation is 4 A (B).
3.4. Adjustment
The DT1600 Ux xx xx doesn’t need any adjustment.
After connected to the power supply it is ready to work.
3.5. Indicator
The following figure shows the indicator on the
DT1600 Ux xx xx front panel.
1. The power green indicator shows that the instrument is
in “power on” state.

DT1600 Ux xx xx
8 20180621-V0
3.6. Storage and transport
This instrument should be stored and transport in places
whose climatic conditions are in accordance with chapter
9.1 Technical specifications, as described under the title:
Environmental conditions.
The packaging of DT1600 Ux xx xx consist of environment-
friendly, recyclable cardboard is used to protect the
instrument against the impacts of normal stresses occurring
during transportation. The corrugated cardboard box is
made from environment-friendly, recyclable paper. The
inner protective material is nylon, which should be disposed
of via specialized recycling companies.

DT1600 Ux xx xx
20180621-V0 9
4. Mounting
4.1. General instructions
The instrument should be installed in a cabinet with
sufficient IP protection, where the operating conditions are
in accordance with chapter 9.1 Technical specifications,
as described under the title: Operating conditions.
Mounting position
The DT1600 Ux xx xx is built in a plastic housing, for
mounting on TS-35 rail.
The instrument should be mounted in vertical position
(horizontal rail position).
Horizontal mounting may cause overheating and damage of
the instrument.
4.2. Main dimensions of the instrument

DT1600 Ux xx xx
10 20180621-V0
4.3. Mounting procedure
The following figure shows the mounting procedures (fixing
on the rail):
Mounting on the rail
The mounting doesn’t need any tools.
1. Tilt the instrument according to the figure; put the
instrument’s mounting hole onto the upper edge of the rail
(figure step 1.).
2. Push the instrument’s bottom onto the bottom edge of the
rail (figure step 2.), you will hear the fixing assembly
closing.
3. Check the hold of the fixing by moving the instrument
firmly.

DT1600 Ux xx xx
20180621-V0 11
5. Connecting
5.1. Preparing the connection
Select connection
cable
Preparing cables
Always observe the following safety instructions:
• Connect or disconnect only in the complete absence of
line voltage
• If overvoltages are accepted, overvoltage arresters
should be installed
• You should take note the data concerning on the
overcurrent protection in installation.
• Use only a screwdriver with appropriate head
Take note the suitability of the connecting cable
(wire cross-section, insulation, etc.).
You may use either solid conductor or flexible conductor.
Prepare the cable for the connection.
Strip approx. 8 mm insulation.
In case of using flexible conductor use crimped wire end.

DT1600 Ux xx xx
12 20180621-V0
5.2. Connecting to the power network
The following figure shows the wiring plan, connecting the
transmitter:
Wiring plan, connecting
to the power network
(see also “Application
example”)
1. Loosen terminal screws.
2. Insert the wire ends into the open terminals according to
the wiring plan.
3. Screw the terminal in.
4. Check the hold of the wires in terminals by pulling on
them firmly.

DT1600 Ux xx xx
20180621-V0 13
5.3. Connecting the signal processing unit and the
power supply
The following figure shows the wiring plan, connecting the
signal processing unit and the power supply:
Wiring plan, connecting
the signal processing
unit and the power
supply
(see also “Application
example”)
Be careful the polarity of
the cables
Checking the
connections
1. Loosen terminal screws.
2. Insert the wire ends into the open terminals according to
the wiring plan.
3. Screw the terminal in.
4. Check the hold of the wires in terminals by pulling on
them firmly.
Check if the cables are connected properly (have you
connected all the cables, have you connected to the right
place, do not the cable-ends touch each other).
5.4. Put the instrument under supply voltage
Put the instrument
under supply voltage
After you have completed the connections, put the
instrument under supply voltage. If the connection is correct
the green indicator give light and you can measure output
current or voltage on the output of the instrument according
to the measured value of the transmitter.

DT1600 Ux xx xx
14 20180621-V0
6. Fault rectification
6.1. Fault finding
The fault finding must be carried out by trained and
authorized personnel only.
•The green indicator is dark →check the mains voltage.
If the mains voltage is OK: the instrument is defective.
•There is no output signal →check the input signal.
If the input signal is OK: the instrument is defective.
When the result of fault finding is that the instrument is
defective call the manufacturer service department.
6.2. Repairing
There is no user repairable part inside the instrument.
In accordance with Point 2.1.: For safety and warranty
reasons, any internal work on the instrument must be
carried out only by DATCON personnel.

DT1600 Ux xx xx
20180621-V0 15
7. Dismounting
7.1. Dismounting procedure
Before dismounting take note the warnings written in
Chapter 5.1.
The following figure shows the dismounting procedures:
Dismounting from the
rail
The dismounting procedure needs a screwdriver for slotted
screws.
Before dismounting disconnect all wires.
1. Put the screwdriver end into the fixing assembly’s hole
(figure step 1.).
2. Lift the screwdriver handle until it possible to open the
fixing assembly (figure step 2.).
3. Keeping the screwdriver in this position lift the instrument
bottom from the bottom edge of the rail (figure step 3.).
Lift the whole instrument (you may put out the screwdriver)
(figure step 4), the instrument will be free.
7.2. Disposal
According with the concerning EU directive, the
manufacturer undertakes the disposal of the instrument that
are manufactured by it and intended to be destroyed.
Please deliver it in contamination-free condition to the site
of the Manufacturer or to a specialized recycling company.

DT1600 Ux xx xx
16 20180621-V0
8. Calculation for application
8.1. Calculations
Calculating the input voltage from the transmitter output
signal.
UX[V]: voltage to be measured
n: voltage transformer ratio
(in case of direct connection n = 1)
UIN [V]: transmitter input voltage
IOUT [mA], UOUT [V]: transmitter output signal
In case of I0, U10 outputs:
UX= n * UIN * IOUT / 20 UX= n * UIN * UOUT / 10
1st example:
IIN = 250 V IOUT = 18 mA n = 10
IX= 10 * 250 * 18 / 20 = 2250 V
In case of I4 output:
UX= n * UIN * (IOUT - 4) / 16
2nd example:
IIN = 250 V IOUT = 12 mA n = 10
IX= 10 * 250 * (12-4) / 16 = 1250 V

DT1600 Ux xx xx
20180621-V0 17
9. Appendix
9.1. Technical specification
Safety data:
The connection terminals of the inputs, the outputs and the supply voltages are
galvanic isolated from each other. The isolation is in compliance with the standard
EN 61010-1, taking into consideration the following:
Pollution level: 2
Measurement category: III
Overcurrent protection in installation: 4 A
Input parameters:
Input voltage: see Chapter 3.2.
Continuous overdrive capability: 2 x U, 500 V (max.)
Input consumption: 0.5 VA (max.)
Frequency range: 40-400 Hz
Output parameters: Type Range [V] Rg [Ohm]
U5 0-5 250
Output voltage:
U10 0-10 500
Output current: see Chapter 3.2.
Burden: 500 Ohm (max.)
Overvoltage protection: 18 V (limiter)
Overcurrent protection: 40 mA (limiter)
Noise voltage: 0.2% p-p (max., FSR)
Settling time (1%): 200 ms (typical)
Output signal error: 0.2% (max.)
Temperature coefficient: 50 ppm / °C (typical)
Frequency-response: 0.5% (max., 40-400 Hz)
Supply-voltage effect: practically zero
Loading-effect: practically zero
Rectifying characteristic: TRMS value (R) or average value (F)
Additional error measuring non-sinusoidal
signal:
0.5% (max., R version, Fcrest < 3)

DT1600 Ux xx xx
18 20180621-V0
Power supply:
Supply voltage: DT1600 Ux xx xx:
18-40 VDC / 14-29 VAC
DT1600 Ux xx xx PS:
140-250 VAC / 180-250 VDC
Consumption: DT1600 Ux xx xx: 1 W / 1.5 VA
DT1600 Ux xx xx PS: 1.5 VA / 1 W
Ambient conditions:
Operating temperature range: 0-50 °C (-20 - +50 °C, on request)
Storage temperature range: -20 - +70 °C
Relative humidity: 90% (max. non condensing)
Place of installation: cabinet
Electromagnetic compatibility (EMC):
Accordance with the standard EN 61326-1:2004
Immunity: -A- criterion
Noise emission: -A- class
General data:
Housing: TS-35 rail mounting housing
material: polyamide PA6.6
Connection: screw-terminal
Connecting cable: 2.5 mm2(max.)
Dimensions: 22.5 x 99 x 115 mm (width x height x depth)
Weight: 0.2 kg
Protection: IP 20
The Manufacturer maintains the right to change technical data.

DT1600 Ux xx xx
20180621-V0 19
9.2. Application example

Table of contents