Explosion-proof
Loadresistancerange
(Example:GC95Digitalmeterrelay,etc.)
1000
800
600
400
200
00 10 12 20 24 32 Voltage(V)
Loadresistance(Ω)
K□41
K□43 Powersource12-32VDC
−
−+
+
−
+
Receiver
Loadresistancetolerance
Explosion-proofconstruction:
Explosion-proofconstructionisatotally-enclosed
constructionsuchthatevenifanexplosivegasexplodes
insidethecontainer,thecontainerwillwithstandtheforce
oftheexplosionandthereisnodangerofignitionby
externalexplosivegases.Ourpressureanddifferential
pressuretransmittermanufacturedunderthispolicyare
usedinpressuremeasurementswhereinflammablegasor
theinflammablegasvaporsmayexistinfactoriesand
businessoffices.
Explosion-prooftypeapproval:
ConformstoMinistryofHealth,LabourandWelfare
Notificationstructuralstandardandnewengineering
standardandnewexplosion-proofpolicyadjustedbyIEC
internationalstandard.
KD41,43 Explosion-proofconstructiond2G4
KD41,43Puressuretransmitter
Applicationrange:d2G4
Explosion-proofconstruction:d
Explosionclass:2(Minimumgapwhichpermitsflame
propagationatagapdepthof25mmis
0.4mmto0.6mm)
Ignitability:G4(Containerwithanignitionpointof135to
200°Candwhoseoutsidesurfacetemperature
riselimitis70degs)
Hazardousareas:Zone1orZone2
Objectiveindustries:Petrochemical,chemicalfiber,
ethylene,ethanol,methanol,dielectric
productsmanufacturing,liquefiedgas,
electricfurnace,pharmaceuticals,
paints,ammoniumsulfate,soda,other
measurementmediumorindustriesin
whichthereisthedangerofexplosion.
Classificationofhazardousarea:
Hazardousarea
Zone0
Zone1
Zone2
Areaswherehazardousatmosphereis
likelytooccurunderabnormal
circumstances
Areaswherehazardousatmosphereis
likelytooccurunderordinary
circumstances
Areaswhereahazardousatmosphereis
continuouslypresentorpresentforalong
periodunderordinarycircumstances
Contents
Model Typeapprovalnumber
No.T54934
No.T54935
No.T55046
KD41
KD43 -0.1to0.3→0to3.5MPa
0to5→0to20MPa
KH41・43, KD41・43
Process Applications Pressure Transmitter
Wiring
2