Sync DIN Rail Power
Supply
12V 50W 1
Phase (NEC Class 2)
/ DRS-12V50W1N
□
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (March 2016, Rev. 00)
Specifications
Input Ratings / Characteristics
Nominal Input Voltage 100-240Vac
Input Voltage Range 85-264Vac
Nominal Input Frequency 50-60Hz
Input Frequency Range 47-63Hz
DC Input Voltage Range* 120-375Vdc
Input Current < 0.9A @ 115Vac, < 0.55A @ 230Vac
Efficiency at 100% Load > 88% @ 115Vac, > 89% @ 230Vac
Max Power Dissipation 0% load
100% load < 0.3W @ 115Vac, < 0.4W @ 230Vac
< 6W @ 115Vac & 230Vac
Max Inrush Current (Cold Start) < 25A @ 115Vac, < 50A @ 230Vac
Leakage Current
(Neutral to PE terminal) < 0.5mA @ 264Vac
*Fulfills test conditions for DC input. Safety approval for DC input can be obtained upon request.
Output Ratings / Characteristics**
Nominal Output Voltage 12Vdc
Factory Set Point Tolerance 12Vdc ± 2%
Output Voltage Adjustment Range 12-15Vdc
Output Current 4A (48W max.)
Output Power 48W
Line Regulation < 0.5% (@ 85-264Vac, 100% load)
Load Regulation < 1.0% (@ 85-264Vac, 0-100% load)
PARD*** (20MHz) < 50mVpp @ > 0°C to 70°C
< 100mVpp @ 0°C to -20°C
Rise Time < 30ms @ nominal input (100% load)
Start-up Time < 2,000ms @ 115Vac (100% load)
< 1,000ms @ 230Vac (100% load)
Hold-up Time > 20ms @ 115Vac (100% load)
> 100ms @ 230Vac (100% load)
Dynamic Response (Overshoot & Undershoot O/P Voltage) ± 5% @ 85-264Vac input, 0-100% load
(Slew Rate: 0.1A/μs, 50% duty cycle @ 5Hz to 1KHz)
Start-up with Capacitive Loads 3,000µF Max
Functional DC OK Relay Contact
(for DRS-12V50W1NR) 30V / 1A, resistive load
The relay contact are normally “ON” (closed) when the output
(Vout) is greater than 75% of its rated value and “OFF”
(opened) when the output (Vout) is less than 75% typ.
**For power de-rating from < -10°C to -20°C, and 55°C to 70°C, see power de-rating on page 3.
***PARD is measured with an AC coupling mode, 5cm wires, and in parallel with 0.1μF ceramic capacitor & 47μF electrolytic capacitor.