CliQ II DIN Rail Power
Supply
24 V 240 W 2
Phase
/ DRP-24V240W2BN
All parameters are specified at 25°C ambient and AC x 2 input unless otherwise indicated.
www.DeltaPSU.com (September 2021, Rev. 06)
Specifications
Input Ratings / Characteristics
Nominal Input Voltage 2 x 200-500 Vac (2-Phase)
200-277 Vac (Single Phase)
Input Voltage Range 2 x 180-550 Vac (2-Phase)
180-305 Vac (Single Phase)
Nominal Input Frequency 50-60 Hz
Input Frequency Range 47-63 Hz
DC Input Voltage Range* 254-780 Vdc
Input Current < 2.00 A @ 2 x 230 Vac, < 1.00 A @ 2 x 400 Vac
Efficiency at 100% Load > 90.0% @ 2 x 400 Vac
Max Power Dissipation 0% load < 8.5 W @ 2 x 200 Vac, < 9.5 W @ 2 x 500 Vac
100% load < 26.5 W @ 2 x 200 Vac, < 21.5 W @ 2 x 500 Vac
Max Inrush Current (Cold Start) < 50 A @ 2 x 200 Vac & 2 x 500 Vac
Leakage Current < 3.5 mA @ 500 Vac
*Safety approval according to IEC/EN/UL 60950-1 and IEC/EN/UL 62368-1.
Output Ratings / Characteristics**
Nominal Output Voltage 24 Vdc
Factory Set Point Tolerance 24 Vdc ± 2%
Output Voltage Adjustment Range 24-28 Vdc
Output Current 10.0 A (continuously operating at 24 V)
12.0 A (Power Boost for 3 seconds at 24 V, refer to the details
in the Functions section)
Output Power 240 W (continuously operating at 24 V)
288 W (Power Boost for 3 seconds at 24 V, refer to the details
in the Functions section)
Line Regulation < 0.5% (@ 200-550 Vac input, 100% load)
Load Regulation < 1.0% (@ 200-550 Vac input, 0-100% load)
PARD*** (20 MHz) < 150 mVpp @ -10°C and above
< 200 mVpp @ below -10°C
Rise Time
< 100 ms @ nominal input (100% load)
Start-up Time < 1,000 ms @ nominal input (100% load)
Hold-up Time > 18 ms @ 2 x 230 Vac,
> 30 ms @ 2 x 400 Vac (100% load)
Dynamic Response
(Overshoot & Undershoot O/P Voltage)
± 5% @ 180-550 Vac input, 0-100% load
(Slew Rate: 0.1 A/μs, 50% duty cycle @ 5Hz)
Start-up with Capacitive Loads 10,000 µF Max
Functional DC OK Relay Contact 30 V / 1 A Max
The relay is usually closed when the output is normal
**For power de-rating from 50°C to 70°C, see power de-rating on page 3.
***PARD is measured with an AC coupling mode, 5cm wires, and in parallel with 0.1 μF ceramic capacitor & 47 μF electrolytic capacitor.