DIEL ME 100 V3 Quick guide

TEMPERATURE CONTROL
ME100 V3
RS 422-485 – MODBUS-RTU
MANUALE DI INSTALLAZIONE ED USO
INSTALLATION AND INSTRUCTIONS MANUAL
MANUAL DE INSTALACIÓN Y USO


CARATTERISTICHE TECNICHE
• Contenitore 90X90X135 mm incluse morsettiere.
• Pannello frontale 96x96 mm.
• Peso 0,6 Kg.
• Contenitore in ABS auto estinguente.
• Alimentazione universale (24÷240) Volt AC/DC ± 10% 50/60 Hz
senza rispetto della polarità.
• Collegamenti elettrici su morsettiere estraibili polarizzate.
• Otto ingressi analogici, rilevamento e controllo della temperatura
con sensori PT100 a tre li nel range da -10 a +200 °C.
• Filtro d’ ingresso contro i disturbi a normativa .
• Precisione ± 1% sul valore di fondo scala ± 1 digit
• Risoluzione 1 °C.
• Uscite: 4 relè 250 VAC, 5 A massimi carico resistivo 1 contatto
di scambio pulito.
• Porta seriale RS485 full duplex modbus RTU.
• Controllo ventilazione ad isteresi con due soglie di temperatura
per ogni canale (H e L).
• Quattro modalità di funzionamento selezionabili.
• Massima essibilità di gestione e facilità di programmazione.
• Temperatura di lavoro centralina da -40 °C a +60 °C.
• Costruzione in accordo alle normative .
• Umidità ambiente ammessa massima 90% non condensante.
• Controllodellavaliditàdeidatiintrodottiinfasediprogrammazione.
• Possibilità di commutare manualmente i relè mediante il menù
di test relè.
• Memorizzazione permanente per più di dieci anni dei valori
programmati e delle massime temperature raggiunte.
• Visualizzazione automatica del valore e del numero della sonda
relativi al canale più caldo.
• Memoria dei massimi storici raggiunti da ciascun canale.
• Rigidità dielettrica 2.5 KVAC per 60”.
3
ITALIANO

MONTAGGIO
Eseguire nel pannello un foro da 91X91 mm, ssare la centralina
con i ganci in dotazione.
ALIMENTAZIONE
La centralina ME100 V3 può essere alimentata con (24÷240) Volt
AC/DC ±10% 50-60 Hz senza rispetto di polarità.
I morsetti di alimentazione sono riportati in tabella (TAB 1) alla ne
del manuale.
COLLEGAMENTI ELETTRICI
Eseguire i collegamenti sulle morsettiere estraibili seguendo lo
schema (TAB 1) alla ne del manuale.
Il relè FLt risulta normalmente eccitato durante il funzionamento
della centralina, in caso di guasto alle sonde o di mancanza di
alimentazione il relè si diseccita.
Il relè Fan è preposto alla gestione dei ventilatori di raffreddamento
delle macchine elettriche oppure per il condizionamento del locale
dove sono situate le macchine stesse.
I relè ALL e PrE vengono eccitati al superamento di un grado delle
rispettive soglie impostate.
Ogni sonda PT100 standard è dotata di tre li, uno bianco e due
rossi.
Collegare i li bianchi nei morsetti contrassegnati dal simbolo del
sensore nella serigraa, morsetti (3-6-9-12-15-18-21-24).
I ventiquattro morsetti di ingresso relativi alle otto sonde sono così
predisposti:
Sonda N. 1 morsetti 1-2-3, Sonda N. 2 morsetti 4-5-6.
Sonda N. 3 morsetti 7-8-9, Sonda N. 4 morsetti 10-11-12.
Sonda N. 5 morsetti 13-14-15, Sonda N. 6 morsetti 16-17-18.
Sonda N. 7 morsetti 19-20-21, Sonda N. 8 morsetti 22-23-24.
4
ITALIANO

Porta seriale RS485 full duplex:
• Trasmissione: positivo TX+ morsetto 25.
• Trasmissione: negativo TX- morsetto 26.
• Ricezione: negativo RX- morsetto 27.
• Ricezione: positivo RX+ morsetto 28.
Per un corretto utilizzo della porta seriale collegare due resistenze
di terminazione linea da 120 ohm in parallelo ai morsetti di ricezione
posti sicamente agli estremi della linea dati.
Tutti i cavi di trasporto dei segnali di misura devono necessariamente:
• essere separati da quelli di potenza
• essere twistati, meglio se anche schermati
• avere una sezione non inferiore a 1.0 mm2.
DESCRIZIONE SEGNALAZIONI
Le lettere che compaiono sul display a singola cifra assumono il
seguente signicato:
F: modo di funzionamento, assume valori da zero no a tre.
P: soglia di preallarme oltre la quale si eccita il relativo relè.
A: soglia di allarme oltre la quale si eccita il relativo relè.
L: soglia inferiore sotto la quale si diseccita il relè di ventilazione.
H: soglia superiore oltre la quale si eccita il relè di ventilazione.
t: tempo minimo di attivazione ventilazione espresso in minuti
che intercorre tra una accensione ed il successivo eventuale
spegnimento.
S: velocità di trasmissione porta seriale RS485 (vedere dettagli al
capitolo PROGRAMMAZIONE DELLA CENTRALINA).
d: ritardo risposta di comunicazione sulla porta seriale RS485
espresso in centesimi di secondo (vedere dettagli al capitolo
PROGRAMMAZIONE DELLA CENTRALINA).
U: indirizzo del dispositivo nella rete RS485.
5
ITALIANO

Le scritte che compaiono sul display a tre cifre assumono il seguente
signicato:
ICF: sonda PT100 in avaria (interruzione connessione oppure
assenza del sensore).
SCF: sonda PT100 in avaria (corto circuito).
rES: azzeramento memoria guasto sonde avvenuto.
FAn: ventilazione relativa ad uno specico canale.
CH(n): stato di uno specico canale n (1-8).
PrE: relè di preallarme.
ALL: relè di allarme.
FnA: primo relè ventilazione.
Fnb: secondo relè ventilazione.
FLt: relè di guasto.
PROGRAMMAZIONE DELLA CENTRALINA
Premendo a lungo e contemporaneamente i tasti UP e DOWN si
entra in modalità programmazione.
I tasti, in questa fase assumono le seguenti funzioni:
Tasto UP incrementa il valore proposto, tasto DOWN decrementa
il valore proposto, tasto ENTER conferma il valore e passa al
parametro successivo.
La programmazione inizia dalla scelta del modo di funzionamento F.
F=0: gruppo di otto canali attivi, una sola soglia di allarme e
preallarme valida per tutti i canali, funzione di ventilazione disattivata.
Con F=0 si impostano solo i due parametri Ped A.
F=1: gruppo di otto canali attivi, una sola soglia di allarme e
preallarme valida per tutti i canali, funzione di ventilazione attiva con
una sola soglia di accensione e spegnimento ventilazione valida per
tutti i canali e ventilatori.
Con F=1 si impostano solo i quattro parametri P, A, L, H.
F=2: gruppo di otto canali attivi, una sola soglia di allarme e
preallarme valida per tutti i canali, funzione di ventilazione attiva,
6
ITALIANO

una sola soglia di accensione e spegnimento ventilazione valida per
tutti i canali, controllo ventilazione anche a tempo (parametro t).
Con F=2 oltre ai parametri impostati con F=1 si imposta il parametro
tin minuti cioè il tempo in minuti che deve restare comunque
attiva la ventilazione prima di intervenire sullo spegnimento.
Questo garantisce un tempo minimo di attivazione ventilazione
indipendentemente dal valore impostato dalla soglia L.
F=3: programmazione indipendente per ogni canale di tutte le soglie
di allarme, preallarme, accensione e spegnimento ventilatore;
Con F=3 vengono chiesti in successione i seguenti parametri:
Tempo tin minuti, cioè il tempo che deve restare comunque
attiva la ventilazione prima di intervenire sullo spegnimento.
Questo garantisce un tempo minimo di attivazione ventilazione
indipendentemente dal valore impostato dalla soglia L.
Per ogni canale appare poi la scritta CH(n) con n (1-8), tramite i
tasti UP e DOWN è necessario decidere se rendere il canale attivo
oppure no, in caso affermativo, viene chiesto di introdurre le soglie
Pe A.
Appare di seguito la scritta FAn, tramite i tasti UP e DOWN è
necessario decidere se si desidera controllare la ventilazione
su quel canale oppure no, se affermativo, viene inoltre chiesto di
introdurre le soglie Le Hdi ventilazione, in caso il canale non sia
attivo o nel caso non si desideri la ventilazione, viene proposta la
scelta per il canale successivo.
Alla ne si accede alla congurazione dei parametri di comunicazione
seriale RS485.
La lettera Sindica la velocità di comunicazione in bit per secondo
(bps) come riportato di seguito.
S=6 4800 bps, S=7 9600 bps, S=8 14400 bps, S=9 19200 bps.
Gli altri parametri (non modicabili) di comunicazione sono parità
NONE, bit dati 8, bit stop 1.
Oltre a questi dati è possibile impostare un tempo di ritardo din
centesimi di secondo fra la ne della ricezione di un comando valido
7
ITALIANO

(dati ed indirizzo corretti) e la successiva trasmissione da parte del
dispositivo, questo per permettere al sistema di supervisione di
predisporsi per la ricezione.
Il ritardo di default è 25 centesimi di secondo.
Inne viene richiesto il parametro U che rappresenta l’indirizzo che
individua univocamente il dispositivo nella rete; il valore di default
per l’indirizzo è zero, risulta pertanto sconsigliabile utilizzare tale
indirizzo come indirizzo valido sulla rete al ne di evitare conitti
con altri dispositivi eventualmente presenti e non ancora congurati.
Congurazione di default:
F=0, P=140, A=160, L=90, H=100, t=0, d=25, S=9, U=0
Per motivi di sicurezza viene in ogni caso controllato il tempo
necessario per la programmazione. Oltre un minuto dall’inizio della
fase di programmazione, la stessa viene interrotta e non salvata
(restano attivi pertanto i parametri precedentemente presenti in
memoria). Alla ne della programmazione, vengono salvati i nuovi
dati in memoria, viene effettuato un test dei display, la centralina si
porta quindi in modalità di visualizzazione automatica.
VISUALIZZAZIONE DATI
Contestualmente alla modalità di funzionamento Fsi possono
visualizzare tutti i parametri di interesse mediante i tasti UP e
DOWN. Per visualizzare costantemente un dato oppure la lettura
di un canale, posizionarsi sullo stesso e premere il tasto AUTO/
MANUAL, il LED MANUAL si accenderà segnalando lo stato di
funzionamento manuale. Per ritornare a visualizzare il canale più
caldo in automatico premere nuovamente il tasto AUTO/MANUAL.
Per accedere alla visualizzazione dei massimi valori storici registrati
premere contemporaneamente ed a lungo i tasti AUTO/MANUAL e
ENTER/TEST, il LED PROG-TMAX segnalerà l’ingresso nel relativo
menù. Sempre utilizzando i tasti UP e DOWN si potranno vedere
i massimi relativi ai canali attivi. Per ritornare alla visualizzazione
normale premere AUTO/MANUAL. La memorizzazione dei
massimi viene cancellata ogni volta che si effettua una nuova
programmazione della centralina.
8
ITALIANO

PROTOCOLLO MODBUS-RTU
Registri MODBUS: Si rinvia alla ne del manuale.
TEST DEI RELE’
Premendo il tasto ENTER/TEST viene effettuato il test del display,
tenendolo premuto a lungo si entra nel menù di test relè. Utilizzando
i tasti UP e DOWN si possono far commutare i relè. Per passare
ai successivi relè premere ENTER/TEST, per uscire dal menù
premere AUTO/MANUAL.
DIAGNOSTICA SONDE TERMOMETRICHE
Gli stati di anomalia delle sonde sono segnalati nel seguente modo:
• commutazione del relè FLt (guasto),
• accensione del LED di FAULT,
• lampeggio del LED relativo al canale guasto e memorizzazione
permanente dello stesso.
In tali casi è possibile conoscere la natura dei guasti nel seguente
modo:
• se la sonda PT100 risulta essere interrotta, viene visualizzata la
scritta lampeggiante ICF con relativo numero di canale.
• se la sonda PT100 risulta essere in corto circuito, viene
visualizzata la scritta lampeggiante SCF con relativo numero di
canale.
Quando una sonda attiva viene rilevata guasta il dispositivo
memorizza il fenomeno mantenendo lampeggiante il relativo LED
anche se questa ultima ripristina il normale funzionamento; per
cancellare la memoria di guasto premere a lungo il tasto AUTO/
MANUAL no al comparire della scritta rES sul display.
NORME DI GARANZIA
La centralina ME100 V3 é coperta da garanzia per un periodo di 3
anni dalla data di consegna.
9
ITALIANO

La garanzia è ritenuta valida quando è stato accertato che le cause
del guasto sono imputabili a difetti di fabbricazione.
Non si risponde invece per guasti dovuti ad errato cablaggio delle
sonde o errata tensione di alimentazione (es. 400 Volt AC).
Non si risponde in ogni caso per danni provocati dal mal
funzionamento della centralina stessa.
Le riparazioni in garanzia, salvo diverso accordo tra le parti sono
effettuate presso la nostra sede di MONTECCHIO MAGGIORE (VI).
ATTENZIONE
Non effettuare prove di rigidità dielettrica o di scariche parziali sulle
macchine elettriche con la centralina inserita, evitare se possibile di
collegare direttamente la centralina al secondario del trasformatore
da proteggere, può accadere che, senza protezione, alla chiusura
dell’interruttore a valle del trasformatore ,si presentino sovratensioni
che possono danneggiare l’apparecchiatura. Questo è tanto più
evidente se la tensione di alimentazione della centralina è di 230 V
AC e se esistono condensatori di rifasamento.
CERTIFICATO DI COLLAUDO
La procedura di collaudo viene effettuata nel seguente modo:
• Funzionamento dei pulsanti.
• Prova dei contatti dei relè.
• Controllo meccanico generale.
• Calibrazione e linearizzazione a +30 ºC e +150 °C.
• Funzionamento per 48 h a tensione di alimentazione variabile.
• Controllo trasmissione seriale RS485 full duplex.
• Prova di isolamento tra alimentazione e contatti relè a 2.5KV AC
per 60”.
10
ITALIANO

TECHNICAL FEATURES
• Box 90x90X135 mm included terminal blocks.
• Front panel 96X96 mm.
• Weight 0,6 Kg.
• Self-extinguishable ABS Box.
• Power supply (24÷240) Volt AC/DC ± 10% 50/60 Hz without
polarity respect.
• Electrical connections on polarized fast connectors.
• Eight analogical input, temperature control and monitoring by
PT100 sensors from -10 °C to +200 °C.
• Input lter against interferences in accordance with rules.
• Precision ± 1% on full scale ± 1 digit.
• Resolution 1 °C.
• Output: 4 relays 250 VAC, 5 A max resistive load, 1 free switch
contact.
• Serial communication interface RS485 full duplex MODBUS-
RTU.
• Comparison of temperatures for cooling fan between two
different levels for each channel (Hand L).
• Four different function modes.
• Working temperature of device from -40°C to 60°C.
• Construction in accordance with rules.
• Max allowed dampness in the room 90% not condensing.
• Checking input data during programming phase.
• Possibility of manual relays switch through menu test relays.
• Storing of the programmed values and max temperature
achieved for more than ten years.
• Automatic visualisation of the value and number referring to the
hottest channel.
• Memorization of the max. reached temperature for each channel
• Dielectric isolation 2.5 KV for 60”.
11
ENGLISH

ASSEMBLY
Perform a square hole measuring 91x91 mm, fasten the device
through the special hooks.
POWER SUPPLY
ME100 V3 can be supplied with (24÷240) Volt AC/DC ±10% 50/60
Hz without respect of polarity.
Power supply connectors are indicated at the end of this manual on
table (TAB 1).
ELECTRICAL CONNECTIONS
Perform the connections on the terminal board as per schema on
(TAB 1) at the end of the manual.
FLt relay usually results excited during normal working of device,
in case of failure of probes or feeding absence the relay switch off.
Fan relay is used for drive fan cooling systems of electric machines
or for the conditioning of the environment where the machines are
situated.
The ALL and PrE relays switch on when the temperature is higher
than one degree of set level.
Each PT100 probe is gifted with three wires, one of them is white
and the other two are red.
Connect the white wire to the terminal board marked whit sensor
logo on plugs (3-6-9-12-15-18-21-24).
The twenty-four connectors relevant to the eight probes are divided
as follows:
Probe N. 1 connectors 1-2-3, Probe N. 2 connectors 4-5-6.
Probe N. 3 connectors 7-8-9, Probe N. 4 connectors 10-11-12.
Probe N. 5 connectors 13-14-15, Probe N. 6 connectors 16-17-18.
Probe N. 7 connectors 19-20-21, Probe N. 8 connectors 22-23-24.
Serial communication interface RS485 full duplex.
• Send: positive TX+ connector 25.
12
ENGLISH

• Send: negative TX- connector 26.
• Reception: negative RX- connector 27.
• Reception: positive RX+ connector 28.
For a correct use of RS485 communication interface, connect
two resistors 120 in parallel of receive connectors situated at the
beginning and at the end of the data line.
All transportation cables of the measurement signals must be
absolutely:
• be separated from the power ones.
• be twisted conductors, better if also screened.
• have a section not smaller than 1,0 mm2.
MESSAGES DESCRIPTION
The letters that appear on single digit display assume the following
meaning:
F: function mode (range 0-3).
P: pre alarm level, the PrE relay switch on when the temperature
exceeds the level set.
A: alarm level, the ALL relay switch on when the temperature
exceeds the level set.
L: low level for cooling system switch off, the FAn relay switch off
when the temperature gets lower than all Lvalues.
H: High level for cooling system switch on, the FAn relay switch on
when the temperature gets higher than any Hvalue.
t: min. time that must elapse before the device turn off the fan
cooling system (see programming details for more information).
S: RS485 speed (see details to chapter PROGRAMMING).
d: answer delay on RS485 serial communication interface in 1/100
seconds (see details to chapter PROGRAMMING).
U: Address of device on RS485 network.
13
ENGLISH

The words that appear on three digit display assume the following
meaning:
ICF: PT100 probe failure due to interruption or absence of probe.
SCF: PT100 probe failure due to electrical short circuit.
rES: memory resetting of the failure probe effected.
FAn: fan referred to a specic channel and fan.
CH(n): State of a specic channel n (1-8).
PrE: pre alarm relay.
ALL: alarm relay.
FAn: fan cooling system relay.
FLt: FAULT relay.
PROGRAMMING
Push and hold together the buttons UP and DOWN for programming
menu.
The functions of the buttons in this phase are indicated as follow:
button UP increases the proposed value, button DOWN decreases
the proposed value, button ENTER/TEST conrms and switches to
the next step.
The programming procedure begins with the choice of F parameter.
F=0: group of eight active channels, only one level for alarm and pre
alarm valid for all channels, fan cooling system function deactivated.
With F=0 is possible to set only Pand Aparameters.
F=1: group of eight active channels, only one level for alarm and pre
alarm valid for all channels, active fan cooling system with only one
level valid for lighting Hand switching off L.
With F=1 is possible to set only four parameters: P, A, L, H.
F=0: group of eight active channels, only one level for alarm and pre
alarm valid for all channels, fan cooling system function deactivated.
With F=0 is possible to set only Pand Aparameters.
F=1: group of eight active channels, only one level for alarm and pre
14
ENGLISH

alarm valid for all channels, active fan cooling system with only one
level valid for lighting Hand switching off L.
With F=1 is possible to set only four parameters: P, A, L, H.
F=2: group of eight active channels, only one level for alarm and pre
alarm valid for all channels, active fan cooling system with only one
level valid for lighting Hand switching off L, control of fan cooling
system also with time parameter t.
With F=2, in addition to the parameters set with F=1, is possible to
set a parameter tin minutes, tis the minimum time that must elapse
before the device turn off the fan cooling system. This guarantees
a minimum time of activation for fan cooling system independently
from the value of L.
F=3: Independent programming for each channel of all levels P, A,
L, H.
in this mode it is also possible to accede to RS485 section.
With F=3 the device asks in sequence the following parameters:
Time tin minute, tis the minimum time that must elaps before the
device turn off the fan cooling system. This guarantees a minimum
time of activation for fan cooling system independently from the
value of L.
For each channel appears the word CH(n) with n (1-8), by means of
the buttons UP and DOWN you choose if a channel is active or not,
in afrmative case, it is asked to put the Pand Aparameters.
Afterwards the word FAn appears, with the buttons UP and DOWN
you choose if fan cooling system is active or not for that channel, in
afrmative case, it is asked to put the Land Hparameters, in case
the channel is not active or fan cooling system is deactivated for that
channel the device asks the choice for the next channel.
At the end it is asked to congure a RS485 section.
The Sletter sets the communication speed in bit for second (bps),
see the following descriptions:
15
ENGLISH

S=6 4800 bps, S=7 9600 bps, S=8 14400 bps, S=9 19200 bps.
Others communications parameters (not settable) are parity NONE,
data bit 8, stop bit 1.
It is possible in addition to set a delay din 1/100 seconds between
the end of reception of a valid command (data and address right)
and the following ME100 V3 transmission, to permit to the supervisor
system to put it in receive mode.
The default delay is 25 1/100 seconds.
At the end the device asks an address Uto work correctly in a RS485
network; the default address is zero, for this reason it is better not
to use this address as a valid address on the network to avoid that
other devices, not yet congured, can cause a conict.
Default congurations:
F=0, P=140, A=160, L=90, H=100, t=0, d=25, S=9, U=0
Anyway the necessary time for programming is checked.
Over 1 minute from beginning of the programming phase, the same
is interrupted and not saved so the previous set limits remain active.
At the end of programming the new data will be saved in memory,
the device executes a display test and the system is prearranged in
automatic way and visualises the maximum measured temperature
and the relative channel.
DATA VISUALIZATION
Referring to Fit is possible to show all parameters of interest by
buttons UP and DOWN. To show one specic parameter, or one
specic measure of temperature, select it and push the button
AUTO/MANUAL, the MANUAL LED turns on to ag a manual
status mode. To return to the normal automatic mode push again
AUTO/MANUAL button.
During automatic working the higher temperature and the relative
number of channel appear on the display. To visualize the
maximum values of the machine push and hold the buttons AUTO/
MANUAL and ENTER/TEST at the same time. The visualisation of
16
ENGLISH

the maximum temperatures is signalised through the LED PROG.-
TMAX which is placed on the front-end panel.
With the buttons UP and DOWN it is possible to see the historical
maximum temperature achieved by all active channels. For exit
push button AUTO/MANUAL.
Please note that the maximum values are reset every time you
conrm a new program sequence.
COMMUNICATION PROTOCOL MODBUS-RTU
MODBUS register: refer to (TAB 2) at the end of the manual.
TEST RELAYS
Pushing ENTER/TEST, the device performs a display test, pushing
and holding the same buttons, the device enter in test relays mode.
With the buttons UP and DOWN it is possible to switch a relays
state. To test the other relays, push ENTER/TEST button, to exit
push AUTO/MANUAL button.
THERMOMETRICAL PROBES DIAGNOSTIC
Errors on probes are indicated as follows:
• FLt relay (FAULT relay) switch off.
• FAULT LED turns on.
• LED of the relative channel blinks and the fault state is stored.
In these case it is possible to know the type of failure:
• PT100 probe interrupted, the blinking word ICF appears on
display together with the number of the channel
• PT100 probe is in short circuit state, the blinking word SCF
appears on display together with the number of the channel.
When the device detects one channel in failure state, it stores the
situation and holds blinking the relative LED.
To clean the failure state in memory keep pushed the AUTO/
MANUAL button until a rES word appears on display.
17
ENGLISH

WARRANTY RULES
ME100 V3 has a warranty period time of three year from delivery
date.
The warranty is valid only whether damages are due to manufacturing
defects.
We aren’t liable for damages due to a wrong wiring of probes or to a
wrong power supply voltage (for example 400 Volt AC).
In any case we aren’t liable for damages due to the bad working of
the equipment.
The reparations in guarantee, except different agreement between
parts, will be effected in our factory in MONTECCHIO MAGGIORE
(VI).
ATTENTION
Don’t effect dielectrical test or partial discharge on the electric
machine with the device inserted, avoid if possible to connect
the device directly to the secondary of the transformer to protect,
otherwise the transient overvoltage can damage the device.
This is more evident if the power supply voltage of the device is
230 VAC and in case of capacitors for the remaking.
TESTING CERTIFICATE
The testing procedure is effected as follows:
• Push-buttons working.
• Relays testing contacts.
• Main mechanical checking.
• Calibration and linearization at +30 °C and +150 °C.
• Testing for 48 hours with variable power voltage supply.
• RS485 full duplex communication system control.
• Insulating testing between earth and relays at 2.5 KV for 60”.
18
ENGLISH

CARACTERÍSTICAS TÉCNICAS
• Contenedor 90X90X135 mm incluidas las regleta de bornes.
• Panel frontal 96X96 mm.
• Peso 0,6 kg.
• Contenedor en ABS autoextinguible.
• Alimentación universal (24÷240) voltios CA/CC ± 10% 50/60 Hz,
sin importar la polaridad.
• Conexiones eléctricas en regletas de bornes extraíbles
polarizadas.
• Ocho entradas analógicas, detección y control de la temperatura
con sensores PT100 de tres cables en el intervalo de -10 a +200
°C.
• Filtro de entrada contra las interferencias a norma .
• Precisión ± 1% sobre el valor límite de escala ± 1 dígito.
• Resolución 1 °C.
• Salidas: 4 relés 250 V CA, 5 A máximos carga resistiva 1 contacto
limpio de intercambio.
• Puerto serial RS485 full duplex modbus RTU.
• Control ventilación por histéresis con dos umbrales de temperatura
para cada canal (H y L).
• Cuatro modalidades de funcionamiento seleccionables.
• Máxima exibilidad de gestión y facilidad de programación.
• Temperatura de funcionamiento centralita de -40 °C a +60 °C.
• Fabricación de acuerdo con las normativas .
• Humedad ambiente admitida máxima 90% no condensante
• Control de la validez de los datos introducidos en fase de
programación.
• Posibilidad de conmutar manualmente los relés mediante el
menú de pruebas relés.
• Almacenamiento permanente por más de diez años de los valores
programados y de las temperaturas máximas alcanzadas.
• Visualización automática del valor y del número de la sonda
relativos al canal más caliente.
• Memoria de los máximos históricos alcanzados por cada canal.
• Rigidez dieléctrica 2.5 KV CA por 60”.
19
ESPAÑOL

MONTAJE
Realizar en el panel un oricio de 91X91 mm, jar la centralita con
los ganchos suministrados.
ALIMENTACIÓN
La centralita ME100 V3 podrá ser alimentada con (24÷240) voltios
CA/CC ± 10% 50-60 Hz, sin importar la polaridad.
Los bornes de alimentación se indican se encuentran en (TAB 1) al
nal del manual.
CONEXIONES ELÉCTRICAS
Efectuar las conexiones en las regletas de bornes extraíbles
siguiendo el esquema (TAB 1) al nal del manual.
El relé FLt está normalmente excitado durante el funcionamiento
de la centralita, en caso de avería en las sondas o de falta de
alimentación, el relé se desexcita.
El relé Fan es el encargado de la gestión de los ventiladores de
refrigeraciónde lasmáquinas eléctricas o bien del acondicionamiento
del local en el que están situadas las antedichas máquinas.
Los relés ALL y PrE se excitan al superar de un grado sus
respectivos umbrales congurados.
Cada sonda PT100 estándar está equipada con tres cables, uno
blanco y dos rojos.
Conectar los cables blancos en los bornes marcados con el símbolo
del sensor en la serigrafía, bornes (3-6-9-12-15-18-21-24).
Los veinticuatro bornes de entrada relativos a las ocho sondas
están distribuidos de la siguiente manera:
Sonda N. 1 bornes 1-2-3, Sonda N. 2 bornes 4-5-6.
Sonda N. 3 bornes 7-8-9, Sonda N. 4 bornes 10-11-12.
Sonda N. 5 bornes 13-14-15, Sonda N. 6 bornes 16-17-18.
Sonda N. 7 bornes 19-20-21, Sonda N. 8 bornes 22-23-24.
Puerto serial RS485 full duplex.
• Transmisión: positivo TX+ borne 25
20
ESPAÑOL
Other manuals for ME 100 V3
1
This manual suits for next models
1
Table of contents
Languages:
Other DIEL Control Unit manuals
Popular Control Unit manuals by other brands

Sierra Wireless
Sierra Wireless AirPrime MC7330 Product Technical Specification & Customer Design Guidelines

Burkert
Burkert 0283 operating instructions

M-system
M-system R3-SV8C instruction manual

Kessel
Kessel Pumpfix F Comfort Instructions for assembly, operation and maintenance

HBM
HBM TN Mounting instructions

TEC
TEC 100 Programming & installation manual