
2.3
TECHNICAL SPECIFICATIONS
2RE OPTION
Max. current (resistive load)
....................................
8 A
Max.
Power
........................................
2000 V @ 192 W
Max. Voltage
................................
.
250 V AC/ 150 V DC
Contact resistance
......................................
max. 3 m
Switching time
..........................................
max. 10 ms
4RE OPTION
Max. current (resistive load)
....................................
5
A
Max. Power
........................................
1
25
0
V A/ 1
5
0 W
Max. Voltage
................................
.2
77
V AC/
125
V DC
Contact resistance
....................................
max.
3
0 m
Switching tim
e
..........................................
max.
10
ms
4OP OPTION
Max. Voltage
...................................................
50 V DC
Max. current
.....................................................
50 mA
Leakage current
.....................................
100 A (max.)
Switching time
..........................................
1 ms (max.)
4OPP OPTION
Max. Voltage
...................................................
50 V DC
Max. current
.....................................................
50 mA
Leakage current
.....................................
100 A (max.)
Switching time
..........................................
1 ms (max.)
All options are opto-
isolated with respect to the input
signal and main supply.
CONNECTORS
To perform wiring connections, remove
the terminal block from the meter's
connector, strip the wire leaving
from 7 to 10mm exposed and insert it
into the proper term
inal while pushing the
fingertip down to open the clip inside
the connector as indicated in the figure.
Proceed in the same manner with all pins and plug the
terminal block into the corresponding meter's connector.
Each terminal can admit cables of sect
0.08mm² and 2.5mm² (AWG 26 ÷ 14).
The blocks provide removable adaptors into each terminal to
allow proper fastening for cable sections of <0.5 mm².
INSTALLATION
To meet the requirements of the directive EN61010
-
the unit is permanently connected to the mains supply it is
obligatory to
install a circuit breaking device easy reachable
to the operator and clearly marked as the disconnect device.
WARNING
In order to guarantee electromagnetic compatibility, the
following guidelines for cable wiring must be followed:
- Power supply wires must b
signal wires.
Never
run power and signal wires in the
same conduit.
-
Use shielded cable for signal wiring and connect the
shield to ground of the indicator (pin2 CN1).
-
The cable section must be
0.25 mm
I f not installed and used ac
instructions, protection against hazards may be
impaired.
2.3
TECHNICAL SPECIFICATIONS
2RE OPTION
Max. current (resistive load)
...................................
8 A
Max. Power
........................................
2000 V @ 192 W
Max. Voltage
................................
.
250 V AC/ 150 V DC
Contact resistance
......................................
max. 3 m
Switching time
...........................................
max. 10 ms
4RE OPTION
Max. current (resistive load)
...................................
5
A
Max. Power
........................................
1
25
0
V A/ 1
5
0 W
Max. Voltage
................................
. 2
77
V AC/ 1
25
V DC
Cont
act resistance
.....................................
max. 3
0 m
Switching time
...........................................
max.
10
ms
4OP OPTION
Max. Voltage
...................................................
50 V DC
Max. current
.....................................................
50 mA
Leakage current
.....................................
100 A (max.)
Switching time
..........................................
1 ms (max.)
4OPP OPTION
Max. Voltage
...................................................
50 V DC
Max. current
.....................................................
50 mA
Leakage current
.....................................
100 A (max.)
Switching time
..........................................
1 ms (max.)
All options are opto-
isolated with respect to the input
signal and main supply.
CONNECTORS
To perform wiring connections, remove
the terminal block from the meter's
connector, strip the wire leaving
from 7
to 10mm exposed and insert it
into the proper terminal while pushing the
fingertip down to open the clip inside
the connector as indicated in the figure.
Proceed in the same manner with all pins and plug the
terminal block into the corresponding meter'
s connector.
Each terminal can admit cables of section comprised between
0.08mm² and 2.5mm² (AWG 26 ÷ 14).
The blocks provide removable adaptors into each terminal to
allow proper fastening for cable sections of <0.5 mm².
INSTALLATION
To meet the requirements of the directive EN61010
-
the unit is permanently connected to the mains supply it is
obligatory to install a circuit breaking device easy reachable
to the oper
ator and clearly marked as the disconnect device.
WARNING
In order to guarantee electromagnetic compatibility, the
following guidelines for cable wiring must be followed:
-
Power supply wires must be routed separated from
signal wires.
Never
run power and si
same conduit.
-
Use shielded cable for signal wiring and connect the
shield to ground of the indicator (pin2 CN1).
-
The cable section must be
0.25 mm
I f not installed and used according to these
instructions, protection against hazards ma
impaired.