Instructions for
Model SS-4 Water Alert ®
To adjust sensor height, hold straight edge across
pads (B1 & B2). Turn sensors (A & A) out or until
distance to straight edge equals the desired water
detection level. See Figure 2.
Connect battery leads (E-E) to terminals of batteries
(C-C). Then insert the batteries into retainer clips.
Wait ten seconds, then test unit by touching wet
ngers to both sensors(A-A). The Relay should
transfer.
Position Water Alert in desired location and retest it
by placing wet ngers across the heads of the two
screws on which sensors are mounted The Relay
should transfer.
To reset the unit, simply remove it from water. If
necessary, dry o the sensor area if it is excessively
wet (if the unit was submerged).
1.
2.
3.
4.
5.
SETUP AND ADJUSTMENTS
1.
2.
3.
4.
CAUTION
BATTERIES
Two 9-volt alkaline batteries (NEDA size 1604A) are
required.
The Alkaline batteries should be replaced once a year.
If the unit is activated often, the batteries might need
to be replaced sooner.
Whenever the batteries are replaced, it is a good
practice to wipe clean the top surface of the Water
Alert and its sensors.
A Dorlen Power Supply, such as the PSW-3, may be
used in place of batteries. If so, follow the furnished
instructions for wiring.
BOTTOM VIEW
FIGURE 2
NOTE
Do Not Use Batteries
Other Than Alkaline!
Not For Explosive Environments!
For Absolute Safety: DO NOT Connect
line voltage to the relay contacts !
For controlling Voltage higher than 28vdc,
contact Dorlen for information on the Model
PR-WM Power Relay.
B1 B2
B3
A
A
SS-4 WATER ALERT
EE
CC
BLUE
Normally
Closed
WHITE
Normally
Open
RED
Common
RED
Common
BLUE
Normally
Closed
WHITE
Normally
Open
INTERNAL ISOLATED RELAY CONTACTS.
DPDT - ( 2-Form C)
28VDC, 24VAC RATED @ 1 AMP.
CONTACT RATINGS:
1. Resistive - (a) 10,000,000 operations (typical) at low level.
(b) 1,000,000 operations min. at 0.5 amp/28VDC
(c) 100,000 operations min. at 1.0 amp/28VDC.
2. Inductive - 100,000 operations min. @ 200 ma. 320 mn, 28VDC
3. Lamp - 100,000 operations min. @ 100 madc, 28VDC.
OVERLOAD: 2 AMPS AT 28VDC.
CONTACT RESISTANCE:
0.1 ohm max. before life
0.2 ohm max. after life
(At max. rated current, measured 1/8" from header)
6615 West Layton Avenue, Milwaukee, WI. 53220