Douglas Lighting Controls WSP-2718 Instruction manual

Technical Data
C-3.7,8 -W-2000 System, Satellite Panel
Interfaces 3.7 www.DouglasLightingControls.com
W-2000 Satellite Panel WSP-2718
WINK
LED
Service
Switch
Power
24VAC
Com
1
2
24VD C
Inputs
-Connect 24V DC Occupancy
det ectors to t hese ter minals.
-Dougl as WRM- 5104 detec tor
can also be connected to
these input s.
-See user manual for
c onnectio n diagrams and
how to p r o gr a m se tt in g s
f oroccupancydetection.
Black
+24v Red
24VD C
Power
Source
1
2
3
4
5
6
7
8
9
10
24VD C Power &
24VDC Inputs
1
2
Black
Yellow
Black
Yellow
12
PhotoSens ors
-Conne ct Dougl as WPS-5527 or
WPS-5533PhotoSensors.
-Use systemsoftwaretoset
s et-poi nts and desired
ac tion f or phot o sensor s.
LonWorks Controls
Pleaseref er t o user m anual for
operationof thesecontr ols.
PhotoSens ors
NetA
NetB
NetA
NetB
Data
Signal
1
2
Service
LED
LocatorBuzzer
Tohelp lo cate Satellite panels
installed in plenums, use system
soft wa r e to ma ke th i s buz z e r bee p.
1
2
3
4
5
6
7
8
9
10
-LonWorks FTT-10Signal
-Data Signalis polarity i nsensitive
-Two pairs of terminalsprovided
for convenience.
Reset
Switch
White
Blue
WSP-2718
SatellitePanel
ControlCard
24VACBlueReturn
Pressandhold for5 secondst o cl ear
all setti ngs and res tore f act ory def aults.
PART No. SPECIFICATIONDESCRIPTION
DIMENSIONS & MOUNTING
Satellite Panel Ratings
n
Eight latching relays are installed in a
Satellite Panel. The latching relays are
designed for all types of lighting loads and
are rated for 20 Amp 120/277/347VAC.
n
Each relay is equipped with a manual
lever to permit easy control at the panel.
This is especially useful during the
installation phase for testing and
convenient override.
Satellite Panel Inputs
n The Satellite Panel has several input
types available. They are:
- Ten configurable inputs* that are
compatible with all standard Douglas 2-
wire switches and occupancy sensors.
Alternatively, the inputs can be set to
accept signals from contact devices that
are either momentary or maintained.
- Two photo sensor connections compatible
with Douglas WPS-5527K (outdoor) and
WPS-5533K (indoor) photo sensor modules.
- One 250ma/24VDC power supply and
24VDC inputs to support applications
that use 24VDC motion sensors by other
manufacturers.
* Input Configuration options:
- Douglas 2-wire control (default)
- Douglas 2-wire control, inverted
- Momentary contact, ON only
- Momentary contact, OFF only
- Maintained contact, Close=ON, Open=OFF
- Maintained contact, Close=OFF, Open=ON
Satellite Panel Programming
n The Satellite Panel is programmed via
the WNP-2150 Network Manager.
Basic features available include:
- Time-of-day scheduling
- Photo sensor setting levels
- Variable photo sensor settings
- Switch input assigned to any output
- Combination logic involving photo
sensors, occupancy and switches.
n
The WNP-2150 uses Web Technology,
so the connecting PC requires no
software other than an internet browser to
view/edit system settings.
Plan View Side View
4.0"
(102)
20.0"
(508)
14.0"
(355)
Momentary
Maintained
Ten Programmable Inputs
Each of the 10 inputs can be
programmed to control any
relay or group of relays.
Each of the 10 inputs can be
configured for control by
contact closure(s) and/or by
Douglas 2-wire devices.
Sw
Occupancy
Sensors
Switches
Two Digital Photo
Sensor Connections
Each of the 2 digital photo sensor
inputs can be used to monitor
light levels at a location.
WPS-5527K
Exterior
Photo Sensor
Digital
Photo
Sensors
WPS-5533K
Interior
Photo Sensor
Two 24VDC Occupancy
Detector Inputs
A 24VDC power supply and
2 inputs are available to support
occupancy detectors by other
manufacturers.
24VDC
Occupancy
Sensors
Input Options
Douglas
2-wire devices
Contact
devices
Outputs
Eight Lighting Relays
Latching relays, lighting
load rated. Rating: 20A
120/277/347 VAC.
Manual override lever
Included.
Data Signal
The Satellite Panel is a part
of the W-2000 system which
uses a 2-conductor LonWorks
Data Signal for network-wide
communication and control.
WSP-2718
8-Relay Satellite Panel
n Digital connection to W-2000
System for building-wide
control and monitoring.
n Local controls are standard
Douglas 2-wire control
devices.
n Satellite Panels can be
programmed to provide
various combinations of
switching, occupancy and
photo sensor control.
WSP-2718-S2-SIP
WSP-2718-S2-FIP
WSP-2718-S3-SIP
WSP-2718-S3-FIP
n The WSP-2718 Satellite Panel is
designed for applications that require
small panels to be located close to the
load(s) being controlled. A Satellite Panel
has 8 relays.
n
Typical applications are school
classrooms or office spaces.
n
The primary advantage of a Satellite
Panel is reduced wiring. Typically, a line
voltage circuit from the breaker panel
is connected to the Satellite Panel
which distributes it to several smaller
loads. Low voltage controls such as
sensors or switches are wired directly
to the Satellite Panel instead of being
run back to a main panel.
n
To control and program a network of
Satellite Panels, a 2-conductor data
signal is connected to each of the
panels. The data signal then connects
to the WNP-2150 Network Manager.
The WNP-2150 Network Manager is
accessed with any internet browser
software to view and edit switch
functions, sensor actions and time
schedules set for each Satellite Panel.
N
Lamp
N
Lamp
N
Lamp
N
Lamp
N
Lamp
N
Lamp
N
Lamp
N
Lamp
WINK
LED
Service
Switch
Power
24VAC
Com
1
2
24VDC
Inputs
-Co nne ct 24V DC Oc cu pancy
d etecto rs to these terminals.
-Do uglas WRM -51 04 d etecto r
c a n also be con nec te d to
th ese i n puts.
-See user manual f or
c o nnect ion di ag ram s and
h ow top rog ram sett ings
f o roc c upan cy det e ction.
Black
+24vRed
24VDC
Power
Source
1
2
3
4
5
6
7
8
9
10
24VDC Power &
24VDCInputs
1
2
Black
Yellow
Black
Yellow
12
PhotoSensors
-Co nne ct D oug las W PS- 5527 or
W P S -553 3P hot oSens or s.
-Use system software to set
s e t-po ints an d de s ired
a c tion fo r ph oto sens or s.
LonWorksC ontrols
Please referto user manual for
operatio n of these cont rol s.
PhotoSensors
NetA
NetB
NetA
NetB
Data
Signal
1
2
Service
LED
LocatorBuzzer
Tohelp locate Satellite p ane ls
installedinplenums,usesystem
software to ma ke th is buzzer be ep.
1
2
3
4
5
6
7
8
9
10
-LonWor ks FTT-10 S ignal
-DataSign al is polarityinsensitive
-Two p airs ofter mina ls pr ov ided
for convenienc e.
Reset
Switch
White
Blue
WSP-2718
Satellite Panel
ControlCard
24VACBlueReturn
Press and hold for 5 sec ond s to cle ar
alls ettin gs an d r estore f actoryd efau l ts.
Technical Data
C-3.7,8 -W-2000 System, Satellite Panel
www.DouglasLightingControls.comInterfaces 3.8
W-2000 Satellite Panel WSP-2718
24VAC
Installation
n Install Satellite Panel near loads to be controlled. Bring branch
circuit(s) to Satellite Panel as required. Typically, this would be 1 or 2
branch circuits. (There can be 8 branch circuits if needed.) Each relay
is lighting load rated to 20A 120/277VAC (347VAC Canada).
n Connect switches and sensors as needed. Schematic above shows the
low voltage wiring for the devices shown.
n Connect data signal to Satellite Panel.
Operation
n
The list below includes various schemes that can be relevant, and are
available for, this application.
- The 4 switches and the occupancy sensor (Douglas WRM-5104)
work in parallel. The occupancy sensor can automatically switch
lights OFF/ON or just OFF. The switches provide occupant control to
accommodate events such as an AV presentation.
- Switch "d" and the occupancy sensor can be associated with the
photo sensor so that the light can only be switched ON should there
be insufficient natural light. Otherwise, the light remains OFF
regardless of switch or occupancy action.
- The photo sensor can control several circuits at different light levels.
For example, should natural light become very bright, circuit "c" could
then be turned off.
- Occupancy sensor control can be linked to the photo sensor so that
the photo sensor does not switch lights when the room is unoccupied.
- Should no occupancy sensor exist, time control (7-day and holiday
date scheduling) can be used for automated switching.
- Should no photo sensor exist, astronomic functions are available.
- A switch can be programmed for group function and can operate
more than one relay.
n
The above is a partial list to describe various combinations that are
available. Attaching the optional dimming ballast control card permits
variable controls for dimming ballasts that operate in scenarios similar
to those described above.
W-2000 System
n
The Satellite Panel is part of the W-2000 system. Use the WNP-2150
Network Manager to configure the Satellite panel. Up to 60 network
devices can be controlled by a WNP-2150. A Satellite Panel counts as
ONE network device.
Data
Signal
Ethernet Access via
Internet Browser
All low voltage 24V
wiring shown for
devices illustrated.
Satellite Panel
Classroom A
Classroom B
CONNECTIONS & APPLICATION
Sw
Sw
Sw
Sw
Sw
Sw
Sw
Sw
WNP-2150 Network Manager
Internet browser access for system view/edit functions.
Satellite
Panel
Classroom A
Classroom B
Full-Size Douglas Panels
Capacity 12-72 loads each. Install by breaker panels.
Satellite Panels
Complete with 8 relays. Install near the loads they control.
Sw
Sw
2-wire
switches
WNS-2300 Data Line Switch Modules (optional)
Permit system-wide programmable control.

This manual suits for next models

4

Popular Control Panel manuals by other brands

Daikin DCM601A51 Commissioning manual

Daikin

Daikin DCM601A51 Commissioning manual

Siemens SIMATIC HMI OP3 Equipment manual

Siemens

Siemens SIMATIC HMI OP3 Equipment manual

Eaton DF6100 Installation and operation manual

Eaton

Eaton DF6100 Installation and operation manual

VTS Medical Systems 1-4-2801-0155 manual

VTS Medical Systems

VTS Medical Systems 1-4-2801-0155 manual

Tecnoalarm Evolution EV LCD manual

Tecnoalarm

Tecnoalarm Evolution EV LCD manual

Tylo Elite quick start guide

Tylo

Tylo Elite quick start guide

AirTechnic AIRZONE UNO installation manual

AirTechnic

AirTechnic AIRZONE UNO installation manual

OSF TOUCH 310.000.0700 Installation and operation manual

OSF

OSF TOUCH 310.000.0700 Installation and operation manual

Halma ZoneSense Plus AS manual

Halma

Halma ZoneSense Plus AS manual

BFT LIBRA-C-LX installation manual

BFT

BFT LIBRA-C-LX installation manual

Philips RC9800I Specification sheet

Philips

Philips RC9800I Specification sheet

Ross NK Routing Systems RCP-QE user guide

Ross

Ross NK Routing Systems RCP-QE user guide

Maple Systems cMT3092X Series Installation instruction

Maple Systems

Maple Systems cMT3092X Series Installation instruction

Winterwarm SmartBox ECO Heater manual

Winterwarm

Winterwarm SmartBox ECO Heater manual

ITV DLK642 installation manual

ITV

ITV DLK642 installation manual

AKO PROPlus AKO-1565 Series quick guide

AKO

AKO PROPlus AKO-1565 Series quick guide

Tekmar D 262 Data brochure

Tekmar

Tekmar D 262 Data brochure

Engineering Incorporated PMA6000 Pilot's guide and operation manual

Engineering Incorporated

Engineering Incorporated PMA6000 Pilot's guide and operation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.