ADJUSTABLE PARAMETERS (Configuration editor)
Front Panel Configuration Editor
Se tion
Parameter as shown on display
Fa tory Settings
DISPLAY Contrast 53%
Language English
LCD Page Timer 5m
Auto Scroll Delay 2s
Current Date and time hh:mm
EDITOR Alt Config Default Config
ENGINE Oil Pressure Low Shutdown 1.03bar
Oil Pressure Low Pre Alarm 1.17bar
Coolant Temperature Low Warning 70ºC
Coolant Temperature High Pre Alarm 90ºC
Coolant Temperature High Shutdown 95ºC
Start Delay Timer 5s
Pre Heat Timer 0s
Crank Duration Timer 10s
Crank est Timer 10s
Safety On Delay 10s
Smoke Limiting 0s
Smoke Limiting Off 0s
Warm Up Timer 0s
Cool Down Timer 1m
Engine Under Speed Shutdown Inactive
Engine Under Speed Shutdown 1200RPM
Engine Under Speed Warning Inactive
Engine Under Speed Warning 1350RPM
Engine Over Speed Warning Inactive
Engine Over Speed Warning 1650RPM
Engine Over Speed Shutdown 1710RPM
Engine Speed Overshoot Delay 2s
Engine Speed Overshoot 0s
Fail To Stop Delay 30s
Battery Under Voltage Warning Active
Battery Under voltage Warning Delay 1m
Battery Under Voltage 10V
Battery Over Voltage Warning Active
Battery Over Voltage Warning Delay 1m
Battery Over Voltage Warning 30V
Charge Alternator Failure Warning Active
Charge Alternator Failure Warning 6V
Charge Alternator Warning Delay 5s
Charge Alternator Failure Shutdown Active
Charge Alternator Failure Shutdown 4.0V
Charge Alternator Shutdown Delay 5s
Droop control Inactive
Droop control 4%
(Compatible engine ECUs only)
GENERATOR Generator Under Voltage Shutdown 184V
Generator Under Voltage Pre Alarm 196V
Generator Voltage Nominal 230V
Generator Over Voltage Pre Alarm 265V
Generator Over Voltage Shutdown 276V
Generator Under Frequency Shutdown 40Hz
Generator Under Frequency Pre Alarm 42Hz
Generator Frequency Nominal 50.0Hz
Generator Over Frequency Pre Alarm 55Hz
Generator Over Frequency Shutdown 57Hz
Full Load ating 500A
Kw Overload Trip 100%
Delayed Over Current Active
Delayed Over Current 100%
AC System 3 Phase, 4 Wire
CT Primary 600A
CT Secondary 5A
Generator Transient Delay 0s
CONFIGURATION EDITOR
• The ‘running’ e itor can be entere while the engine is running. All protections remain active if the
engine is running while the running e itor is entere .
• Press an hol the button to enter the running e itor.
EDITING A PARAMETER
• Enter the e itor as escribe above.
•
Press the left or right buttons to cycle to the section you wish to view/change.
•
Press the up
or own
buttons to select the parameter you wish to view/change within the currently
selecte section.
• To e it the parameter, press to enter e it mo e. The parameter begins to flash to in icate that
you are e iting the value.
• Press the up
or own
buttons to change the parameter to the require value.
• Press to save the value. The parameter ceases flashing to in icate that it has been save .
• To exit the e itor at any time, press an hol the button.