DSE 7220 User manual

D E E P S E A E L E C T R O N I C S
7 2 2 0 I N S T A L L A T I O N I N S T R U C T I O N S
053-027
ISSUE 4
TYPICAL WIRING DIAGRAM
ACCESSING THE FRONT PANEL CONFIGURATION EDITOR
•
Ensure the engine is at rest an the mo ule is in STOP mo e by pressing the Stop/Reset button.
• Press the Stop/Reset an Info buttons simultaneously.
• If a mo ule security PIN has been set, the PIN number request is then
shown :
• Press , the first ‘#’ changes to ‘0’. Press
(up) or
( own) to a just it to the
correct value.
• Press (right) when the first igit is correctly entere . The igit you have just entere will now
show ‘#’ for security.
•
Repeat this process for the other igits of the PIN number. You can press
(left) if you nee to
move back to a just one of the previous igits.
•
When is presse after e iting the final PIN igit, the PIN is checke for vali ity. If the number is
not correct, you must re-enter the PIN.
•
If the PIN has been successfully entere (or the mo ule PIN has not been
enable ), the e itor is isplaye :
EDITING A PARAMETER
• Enter the e itor as escribe above.
•
Press the left or right buttons to cycle to the section you wish to view/change.
•
Press the up
or own
buttons to select the parameter you wish to view/change within the currently
selecte section.
• To e it the parameter, press to enter e it mo e. The parameter begins to flash to in icate that
you are e iting the value.
• Press the up
or own
buttons to change the parameter to the require value.
• Press to save the value. The parameter ceases flashing to in icate that it has been save .
• To exit the e itor at any time, press an hol the button.
Deep Sea Ele troni s Pl .
Tel:+44 (0)1723 890099
Fax: +44 (0)1723 893303
LO CALL (from UK BT lan lines) :
Telephone 0845 260 8933
Email: support@ eepseaplc.com
Web:
www. eepseaplc.com
Deep Sea Ele troni s in .
Phone: +1 (815) 316-8706
Fax: +1 (815) 316- 8708
TOLL FREE (USA only) : Tel: 1 866 636 9703
Email: sesales@ eepseausa.com
Web: www. eepseausa.com
Deep Sea Ele troni s Pl .
(Far East)
Tel:+66 2 670 6228
Fax: +66 2 678 3028
Email: support@ eepseaplc.com
Web: www. eepseaplc.com
NOTE: When the editor is visible, it is automatically exited after 5 minutes of inactivity to ensure
security.
NOTE: The PIN number is automatically reset hen the editor is exited (manually or automatically) to
ensure security.
NOTE: More comprehensive module configuration is possible using the 7xxx series PC configuration
soft are. Please contact us for further details
http://bestgenerator.spb.ru/?page_id=6765

DIMENSIONS
240.0mm x 181.1mm x 41.7mm
(9.4” x 7.1” x 1.6”)
PANEL CUTOUT
:
220mm x 160mm
(8.7” x 6.3”)
ADJUSTABLE PARAMETERS (Configuration editor)
Front Panel Configuration Editor
Se tion
Parameter as shown on display
Fa tory Settings
DISPLAY Contrast 53%
Language English
LCD Page Timer 5m
Auto Scroll Delay 2s
Current Date and time hh:mm
EDITOR Alt Config Default Config
ENGINE Oil Pressure Low Shutdown 1.03bar
Oil Pressure Low Pre Alarm 1.17bar
Coolant Temperature Low Warning 70ºC
Coolant Temperature High Pre Alarm 90ºC
Coolant Temperature High Shutdown 95ºC
Start Delay Timer 5s
Pre Heat Timer 0s
Crank Duration Timer 10s
Crank est Timer 10s
Safety On Delay 10s
Smoke Limiting 0s
Smoke Limiting Off 0s
Warm Up Timer 0s
Cool Down Timer 1m
Engine Under Speed Shutdown Inactive
Engine Under Speed Shutdown 1200RPM
Engine Under Speed Warning Inactive
Engine Under Speed Warning 1350RPM
Engine Over Speed Warning Inactive
Engine Over Speed Warning 1650RPM
Engine Over Speed Shutdown 1710RPM
Engine Speed Overshoot Delay 2s
Engine Speed Overshoot 0s
Fail To Stop Delay 30s
Battery Under Voltage Warning Active
Battery Under voltage Warning Delay 1m
Battery Under Voltage 10V
Battery Over Voltage Warning Active
Battery Over Voltage Warning Delay 1m
Battery Over Voltage Warning 30V
Charge Alternator Failure Warning Active
Charge Alternator Failure Warning 6V
Charge Alternator Warning Delay 5s
Charge Alternator Failure Shutdown Active
Charge Alternator Failure Shutdown 4.0V
Charge Alternator Shutdown Delay 5s
Droop control Inactive
Droop control 4%
(Compatible engine ECUs only)
GENERATOR Generator Under Voltage Shutdown 184V
Generator Under Voltage Pre Alarm 196V
Generator Voltage Nominal 230V
Generator Over Voltage Pre Alarm 265V
Generator Over Voltage Shutdown 276V
Generator Under Frequency Shutdown 40Hz
Generator Under Frequency Pre Alarm 42Hz
Generator Frequency Nominal 50.0Hz
Generator Over Frequency Pre Alarm 55Hz
Generator Over Frequency Shutdown 57Hz
Full Load ating 500A
Kw Overload Trip 100%
Delayed Over Current Active
Delayed Over Current 100%
AC System 3 Phase, 4 Wire
CT Primary 600A
CT Secondary 5A
Generator Transient Delay 0s
ACCESSING THE ‘RUNNING’
CONFIGURATION EDITOR
• The ‘running’ e itor can be entere while the engine is running. All protections remain active if the
engine is running while the running e itor is entere .
• Press an hol the button to enter the running e itor.
EDITING A PARAMETER
• Enter the e itor as escribe above.
•
Press the left or right buttons to cycle to the section you wish to view/change.
•
Press the up
or own
buttons to select the parameter you wish to view/change within the currently
selecte section.
• To e it the parameter, press to enter e it mo e. The parameter begins to flash to in icate that
you are e iting the value.
• Press the up
or own
buttons to change the parameter to the require value.
• Press to save the value. The parameter ceases flashing to in icate that it has been save .
• To exit the e itor at any time, press an hol the button.
ADJUSTABLE PARAMETERS (Running editor)
Running Editor
Se tion
Parameter as shown on display
Fa tory Settings
DISPLAY Contrast 53%
Language English
ENGINE
Manual Frequency Trim (Electronic engines only) 0.0Hz
Front Panel Configuration Editor
Se tion
Parameter as shown on display
Fa tory Settings
MAINS
Mains Under Voltage Trip 184V
Mains Over Voltage Trip 276V
Mains Under Frequency Trip 45Hz
Mains Over Frequency Trip 55Hz
Mains Transient Delay 2s
eturn Delay 30s
Mains Transfer Time 0.7s
TIMERS LCD Page Timer 5m
Auto Scroll Delay 3s
Start Delay Timer 5s
Pre Heat Timer 0s
Crank Duration Timer 10s
Crank est Timer 10s
Safety On Delay 10s
Smoke Limiting 0s
Smoke Limiting Off 0s
Warm Up Timer 0s
Cool Down Timer 1m
Speed Overshoot Delay 2s
Fail To Stop Delay 30s
Battery voltage Low Warning Delay 1m
Battery Voltage High Warning Delay 1m
eturn Delay 30s
Generator Transient Delay 0s
Mains Transient Delay 2s
Mains Transfer Time 0.7s
http://bestgenerator.spb.ru/?page_id=6765
Table of contents
Other DSE Control Panel manuals
Popular Control Panel manuals by other brands

Satel
Satel CA-6-P Installer manual

Matrix Switch Corporation
Matrix Switch Corporation MSC-CP8X1E product manual

Flexit
Flexit CI 60 Installation manual & quick start guide

Saunier Duval
Saunier Duval SR 92f/3 manual

Raven
Raven SCS 460 Installation & service manual

Immergas
Immergas Code 3.030863 Instruction and warning book