INSTALLATION INSTRUCTIONS
! IMPORTANT SAFEGUARDS !
WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE
FOLLOWED, INCLUDING THE FOLLOWING:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. To prevent high voltage from being present on red & yellow output leads prior to installation,
inverter connector must be open. Do not join inverter connector until installation is complete and
AC power is supplied to the emergency ballast.
2. This product is for use with most 2’ through 8’ (17 W - 215 W) single pin or bipin fluorescent lamps,
including energy saving, circline, U-shaped and rapid-start (4-pin) long compact fluorescent
lamps.
3. Make sure all connections are in accordance with the National Electrical Code and any local
regulations.
4. To reduce the risk of electric shock, disconnect both normal and emergency power supplies and
inverter connector of the emergency ballast before servicing.
5. This emergency ballast is for factory or field installation in either the ballast channel or on top of
the fixture.
6. This product is suitable for damp locations where the ambient temperature is 0°C minimum,
+50°C maximum. Product is also suitable for installation in sealed and gasketed fixtures. Product
is not suitable for heated air outlets and wet or hazardous locations.
7. An unswitched AC power source is required (120 or 277 VAC, 60 Hz).
8. Do not install near gas or electric heaters.
9. Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field
replaceable. Contact the manufacturer for information on service.
10. The use of accessory equipment not recommended by the manufacturer may cause an unsafe
condition.
11. Do not use this product for other than intended use.
12. Servicing should be performed by qualified service personnel.
SAVE THESE INSTRUCTIONS
11/21/08
©
Hubbell Lighting, Inc. • 701 Millennium Blvd • Greenville, SC 29607 • (864) 678-1000 • FAX (864) 678-1415 • www.dual-lite.com
76000023
UFO-5AW
Ni - Cd
CONTAINS NICKEL-CADMIUM
RECHARGEABLE BATTERY.
MUST BE RECYCLED OR
DISPOSED OF PROPERLY.
WARNING – This product contains chemicals known to the State of California to cause cancer, birth defects and/or other
reproductive harm. Thoroughly wash hands after installing, handling, cleaning, or otherwise touching this product.
INSTALLATION
NOTE: Make sure the necessary branch circuit wiring is available. An unswitched source of power is
required. The emergency ballast must be fed from the same branch circuit as the AC ballast.
1. Disconnect AC power from the fixture. Remove the ballast channel cover and install the emergency ballast
either in the ballast channel (see Illustrations 1 & 2) or on top of the fixture* (see Illustration 3).
2. Select the appropriate wiring diagram to connect the emergency ballast to the AC ballast and lamp. Make sure
all connections are in accordance with the National Electrical Code and any local regulations.
3. Install the test switch through the ballast channel cover of a troffer or through the side of a strip fixture. Drill
a 1/2" hole and install the switch as shown (see Illustration 1 & 2). Wire the test switch so that it removes AC
power from both the emergency ballast and the AC ballast at the same time (see Illustration 4).
4. Refer to Illustration 5 and install the charging indicator light so that it will be visible after the fixture is installed.
5. In a readily visible location, attach the label “CAUTION–This Unit Has More Than One Power Connection Point.
To Reduce The Risk Of Electric Shock, Disconnect Both The Branch Circuit-Breakers Or Fuses And Emer-
gency Power Supplies Before Servicing.”
WARNING: TO PREVENT HIGH VOLTAGE FROM BEING PRESENT ON RED AND YELLOW
OUTPUT LEADS PRIOR TO INSTALLATION, INVERTER CONNECTOR MUST BE OPEN. DO
NOT jOIN INVERTER CONNECTOR UNTIL INSTALLATION IS COMPLETE AND AC POWER
IS SUPPLIED TO THE EMERGENCY BALLAST.
2
ILLUSTRATION 2
ILLUSTRATION 4
ILLUSTRATION 1 ILLUSTRATION 3
NOTE: After installing the charging indicator light and test switch, mark each with the appropriate label. If
a detached charging indicator light is used, connect by matching wire colors and install as shown
in Illustration 5.
double pole option
*For installation on top of the xture, wire bundle covers may be required by state or local codes. These covers are available from the
manufacturer as an accessory kit and must be ordered separately. Call your local distributor or the factory for complete infomation.
BLACK
WHITE
HOT
COM
WALL
SWITCH
AC
BALLAST
BLACK
EMERGENCY
BALLAST
WHITE
WHT/BLK
HOT
COM
AC
BALLAST
WHT/RED
WHITE
BLACK 120V
OR
ORANGE 277V
EMERGENCY
BALLAST
WHT/BLK
WHT/RED
WHITE
BLACK 120V
OR
ORANGE 277V
BLK
RED RED
BLK
DOUBLE POLE
TEST SWITCH
BLK BLK
DOUBLE POLE
TEST SWITCH
RED RED
unswitched fixtureswitched fixture
6. After installation is complete, supply AC power to the emergency ballast and join the inverter connector.
7. A short-term discharge test may be conducted after the emergency ballast has been charging for one hour.
Charge for 24 hours before conducting a long-term discharge test. Refer to OPERATION.
OPERATION
When AC power is applied, the charging indicator light is illuminated, indicating the battery is being charged. When
power fails, the emergency ballast automatically switches to emergency power, operating one or two lamps at
reduced illumination. When AC power is restored, the emergency ballast returns to the charging mode and delays AC
ballast operation for approximately three seconds to prevent false-tripping of AC ballast (end-of-lamp-life) shutdown
circuits. This emergency ballast will operate the rated lamp load for a minimum of 90 minutes.
MAINTENANCE
Although no routine maintenance is required to keep the emergency ballast functional, it should be checked
periodically to ensure that it is working. The following schedule is recommended:
1. Visually inspect the charging indicator light monthly. It should be illuminated.
2. Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds. Either one or two
lamps should operate at reduced illumination.
3. Conduct a 90-minute discharge test once a year. Either one or two lamps should operate at reduced illumination
for at least 90 minutes.
REFER ANY SERVICING INDICATED BY THESE CHECkS TO QUALIFIED PERSONNEL.
ILLUSTRATION 5
NOTE: After installing the charging indicator light and test switch, mark each with the appropriate label.
3
troffer style fixture strip style fixture
Charging
Indicator
Light
1/2" White
Bushing
Violet (+)
Brown (–)
Violet (+)
Brown (–)
1/2" White
Bushing
5/8" Black
Bushing
5/8" Black
Bushing
1/2" Punch
Fixture Fixture
Charging
Indicator
Light
EMERGENCY BALLAST AND AC BALLAST MUST BE FED FROM THE SAME BRANCH CIRCUIT.
TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLASTS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS.
WIRING DIAGRAMS for 1-LAMP emergency operation
4
FIG 105 THREE (3) LAMP RAPID START BALLAST
FIG 124 TWO (2) LAMP RAPID START BALLAST
FIG 104 TWO (2) LAMP INSTANT START BALLAST
FIG 106 THREE (3) LAMP INSTANT START BALLAST
WIRING DIAGRAMS for 2-LAMP emergency operation (2'-4', 17-40 W lamps only)
FIG 125 TWO (2) LAMP INSTANT START BALLAST FIG 140 TWO (2) LAMP RAPID START BALLAST
FIG 127 THREE (3) LAMP INSTANT START BALLAST FIG 126 FOUR (4) LAMP INSTANT START BALLAST
WIRING DIAGRAMS for Emergency-Only fixtures
FIG 109 ONE (1) 17-215 W LAMP WITHOUT AC BALLAST FIG 110 TWO (2) 17-40 W LAMPS WITHOUT AC BALLAST
FIG 120 FOUR (4) LAMP RAPID START BALLAST
FIG 121 FOUR (4) LAMP INSTANT START BALLAST
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
WALL SWITCH
WHT/RED
RED
WHITE
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
COMMON
(CAP UNUSED LEAD) BLACK 120V
OR
ORANGE 277V
TEST
SWITCH
INVERTER
CONNECTOR
CHARGING
INDICATOR
BLK
HOT
BLK
BLUE
2 LAMP
INSTANT
START
BALLAST
BLUE
BLACK
WHITE
BLU/WHT
BLUE
LAMP 2
LAMP 1
RED
RED
YELLOW
YEL/BLK
( )
EMERGENCY
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
WALL SWITCH
WHT/RED
RED
WHITE
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
COMMON
(CAP UNUSED LEAD) BLACK 120V
OR
ORANGE 277V
TEST
SWITCH
INVERTER
CONNECTOR
CHARGING
INDICATOR
BLK
HOT
BLK
( )
EMERGENCY
2 LAMP
RAPID START
BALLAST
BLUE
BLACK
WHITE
BLU/WHT
BLUE
LAMP 2
LAMP 1
RED
YELLOW
YEL/BLK
BLUE RED
RED
YELLOW
YELLOW
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
WALL SWITCH
WHT/RED
RED
WHITE
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
COMMON
(CAP UNUSED LEAD) BLACK 120V
OR
ORANGE 277V
TEST
SWITCH
INVERTER
CONNECTOR
CHARGING
INDICATOR
BLK
HOT
BLK
BLUE
BLUE
3 LAMP
INSTANT
START
BALLAST
BLUE
BLACK
WHITE
BLU/WHT
BLUE
LAMP 2
LAMP 1
LAMP 3
RED
( )
EMERGENCY
RED
YELLOW
YEL/BLK
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
WALL SWITCH
WHT/RED
RED
WHITE
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
COMMON
(CAP UNUSED LEAD) BLACK 120V
OR
ORANGE 277V
TEST
SWITCH
INVERTER
CONNECTOR
CHARGING
INDICATOR
BLK
HOT
BLK
BLUE
BLUE
RED
RED
3 LAMP
RAPID START
BALLAST
BLACK
WHITE
RED
YELLOW
YEL/BLK
BLU/WHT
BLUE
LAMP 2
LAMP 1
LAMP 3
BLU/WHT
BLU/WHT
YELLOW
YELLOW
( )
EMERGENCY
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
WALL SWITCH
WHT/RED
RED
WHITE
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
COMMON
(CAP UNUSED LEAD) BLACK 120V
OR
ORANGE 277V
TEST
SWITCH
INVERTER
CONNECTOR
CHARGING
INDICATOR
BLK
HOT
BLK
YELLOW
BLUE
4 LAMP
INSTANT
START
BALLAST
BLUE
BLACK
WHITE
BLU/WHT
BLUE
LAMP 2
LAMP 1
LAMP 3
RED
( )
EMERGENCY
RED
YELLOW
YEL/BLK
LAMP 4
RED
YELLOW
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
WALL SWITCH
WHT/RED
RED
WHITE
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
COMMON
(CAP UNUSED LEAD) BLACK 120V
OR
ORANGE 277V
TEST
SWITCH
INVERTER
CONNECTOR
CHARGING
INDICATOR
BLK
HOT
BLK
4 LAMP
RAPID START
BALLAST
RED
RED
BLACK
WHITE
RED
YELLOW
YEL/BLK
BLU/WHT
BLUE
LAMP 2
LAMP 1
LAMP 3
LAMP 4
BLU/WHT
BLU/WHT
YELLOW
BRN
BRN
BLUE
BLUE
YELLOW
( )
EMERGENCY
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
WALL SWITCH
WHT/RED
RED
WHITE
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
COMMON
(CAP UNUSED LEAD) BLACK 120V
OR
ORANGE 277V
TEST
SWITCH
INVERTER
CONNECTOR
CHARGING
INDICATOR
BLK
HOT
BLK
BLUE
2 LAMP
INSTANT
START
BALLAST
BLUE
BLACK
WHITE
BLU/WHT
BLUE
LAMP 2
LAMP 1
RED
RED
YELLOW
YEL/BLK
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
WALL SWITCH
WHT/RED
RED
WHITE
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
COMMON
(CAP UNUSED LEAD) BLACK 120V
OR
ORANGE 277V
TEST
SWITCH
INVERTER
CONNECTOR
CHARGING
INDICATOR
BLK
HOT
BLK
2 LAMP
RAPID START
BALLAST
BLUE
BLACK
WHITE
BLU/WHT
BLUE
LAMP 2
LAMP 1
RED
YELLOW
YEL/BLK
BLUE RED
RED
YELLOW
YELLOW
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
WALL SWITCH
WHT/RED
RED
WHITE
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
COMMON
(CAP UNUSED LEAD) BLACK 120V
OR
ORANGE 277V
TEST
SWITCH
INVERTER
CONNECTOR
CHARGING
INDICATOR
BLK
HOT
BLK
BLUE
BLUE
3 LAMP
INSTANT
START
BALLAST
BLUE
BLACK
WHITE
BLU/WHT
BLUE
LAMP 2
LAMP 1
LAMP 3
RED
( )
EMERGENCY
( )
EMERGENCY
RED
YELLOW
YEL/BLK
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
WALL SWITCH
WHT/RED
RED
WHITE
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
COMMON
(CAP UNUSED LEAD) BLACK 120V
OR
ORANGE 277V
TEST
SWITCH
INVERTER
CONNECTOR
CHARGING
INDICATOR
BLK
HOT
BLK
BLUE
BLUE
RED
RED
3 LAMP
RAPID START
BALLAST
BLACK
WHITE
RED
YELLOW
YEL/BLK
BLU/WHT
BLUE
LAMP 2
LAMP 1
LAMP 3
BLU/WHT
BLU/WHT
YELLOW
YELLOW
( )
EMERGENCY
( )
EMERGENCY
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
WHT/RED
RED
WHITE
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
COMMON
(CAP UNUSED LEAD) BLACK 120V
OR
ORANGE 277V
TEST
SWITCH
INVERTER
CONNECTOR
CHARGING
INDICATOR
BLK
HOT
BLK
(CAP)
(CAP)
LAMP
RED
YELLOW
YEL/BLK
BLU/WHT
BLUE
(CAP)
(CAP)
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
WHT/RED
RED
WHITE
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
COMMON
(CAP UNUSED LEAD) BLACK 120V
OR
ORANGE 277V
TEST
SWITCH
INVERTER
CONNECTOR
CHARGING
INDICATOR
BLK
HOT
BLK
(CAP)
(CAP)
LAMP 1
LAMP 2
RED
YELLOW
YEL/BLK
BLU/WHT
BLUE
(CAP)
(CAP)

Popular Work Light manuals by other brands

Stanley SXLS31322E instruction manual

Stanley

Stanley SXLS31322E instruction manual

Hilti SL 2-A12 Original operating instructions

Hilti

Hilti SL 2-A12 Original operating instructions

DS Produkte 1725 operating instructions

DS Produkte

DS Produkte 1725 operating instructions

DeWalt DCL050 instruction manual

DeWalt

DeWalt DCL050 instruction manual

Urrea LRU6A quick start guide

Urrea

Urrea LRU6A quick start guide

Anslut 018971 operating instructions

Anslut

Anslut 018971 operating instructions

honle UVAHAND LED operating instructions

honle

honle UVAHAND LED operating instructions

NightSearcher GALAXY-1000 user manual

NightSearcher

NightSearcher GALAXY-1000 user manual

Solar Light-N-Carry LNC1541 Operator's manual

Solar

Solar Light-N-Carry LNC1541 Operator's manual

Opti-Med JM026-002 user manual

Opti-Med

Opti-Med JM026-002 user manual

SP tools SP81479 user manual

SP tools

SP tools SP81479 user manual

Craftsman 315.114071 Operator's manual

Craftsman

Craftsman 315.114071 Operator's manual

Faithfull FPP SLLED36U instruction manual

Faithfull

Faithfull FPP SLLED36U instruction manual

DVA BLUE ELECTRIC Manual instruction

DVA

DVA BLUE ELECTRIC Manual instruction

Husky K40068 Use and care guide

Husky

Husky K40068 Use and care guide

Deluce Lighting DLPLLED7BLK instructions

Deluce Lighting

Deluce Lighting DLPLLED7BLK instructions

Gardner Bender GWL-20BT operating instructions

Gardner Bender

Gardner Bender GWL-20BT operating instructions

LUCCI LEDLux MERIDIAN II installation instructions

LUCCI

LUCCI LEDLux MERIDIAN II installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.