GS300M GasDetection Controller
t: 01905 797989
GS300M 3 Channel Gas Detection Controller
FEATURES
■Three channel protection
■230VAC supply
■Wall or panel mounted
■Positive safety option
■Detection of Toxic 0-300ppm / Explosive Gas(es)
0-20%LEL
■4-20mA signal sensor input
■3 alarm stages - 1st & 2nd pre-alarm and main alarm
■IP44 protective rating
■CE certied and approved to EN 61010-1, EN 50270,
EN 50271, EN 45544-3, EN 60079-29-1
■2 year guarantee - 3 year by registering at duomo.co.uk
OVERVIEW
The GS300M is a 230V three channel and sensor wall or panel
mounted gas detection controller. It can be connected to toxic and
explosive sensors. An LED display indicates sensor status and
faults.
If the remote sensor senses the presence of gas, it sends a
proportional 4-20mA signal back to the GS300M. When the rst
alarm level is reached the pre-alarm relay is activated (See Alarm
Settings). If the level continues to rise the main alarm relay will be
energised.
For explosive or toxic gases, the electrical supply to the safety shut
o valve is broken when the main alarm threshold is reached. A
general alarm is sounded.
Should the controller enter fault condition the safety shut o valve
closes to fail safe. A self-diagnostic feature looks for return sensor
voltage and ensures correct functionality.
The GS300M controller is compatible with all the Duomo
conventional sensors.
SPECIFICATION
Power
Power Supply 230VAC 50Hz ± 10%
Secondary Battery 12VDC ± 10% Max 2.2Ah
Battery Charger Charger Capacity 2.2Ah
Power Consumption 11W Maximum @ 13.8V
Relay Contact Range 10A resistive
Alarm Settings
Pre-Alarm No.1 8% LEL / 120ppm
Pre-Alarm No.2 13% LEL / 200ppm
Main Alarm Fixed at 20% LEL / 300ppm
Sensor Fault Short circuit, interruption, sensor deterioration
Technical Specication
Dimensions Width 144mm |Height 144mm |Depth 110mm
Display N/A
Mounting Wall or panel mounted
Input Signal 4-20mA
Device Precision 1% FS
Reaction Time <10 seconds
Working Temperature -10°C to 40°C
Start-up Self-Diagnostic Delay 90 seconds
Protective Rating IP44
Conguration
Positive Safety Yes (ON/OFF)
Main Alarm Relay Actuation Yes (Latching/Temporary Alarm)
Gas Type Selection Yes (Toxic/Explosive)
Timed Sensor Test Facility No
Emergency Stop Connections No
O2Compatibility as Standard No
Perhipheral Specication
No. of Remote Sensors 1-3
Maximum Sensor Distance 100m
Cable Diameter for Sensors 1mm2CSA
(Screened and earthed at the controller end)
Compatibility
Sensor Compatibility All Duomo Sensors
Approvals, Certications and Guarantee
Approvals EN 61010-1, EN 50270, EN 50271, EN 45544-3,
EN 60079-29-1
Guarantee 2 year as standard
3 year by registering at www.duomo.co.uk
3
Channel
Conventional
4-20mA
IP44
Positive
Safety