4.9 Parameter List and Breakdown Table
ELECTRONIC CONTROL FAULT TABLE:
Can be judged according to the remote controller failure code and troubleshooting
Protect/fault Fault
display
Reason Elimination methods
Inlet Temp. Sensor Fault P01 The temp. Sensor is broken or
short circuit
Check or change the temp. Sensor
Outlet Temp. Sensor
Fault
P02 The temp. Sensor is broken or
short circuit
Check or change the temp. Sensor
Ambient Temp. Sensor
Fault
P04 The temp. Sensor is broken or
short circuit
Check or change the temp. Sensor
Coil 1 Temp. Sensor
Fault
P05 The temp. Sensor is broken or
short circuit
Check or change the temp. Sensor
Coil 2 Temp. Sensor
Fault
P15 The temp. Sensor is broken or
short circuit
Check or change the temp. Sensor
Suction Temp. Sensor
Fault
P07 The temp. Sensor is broken or
short circuit
Check or change the temp. Sensor
Discharge Temp. Sensor
Fault
P081 The temp. Sensor is broken or
short circuit
Check or change the temp. Sensor
Exhaust Air over Temp
Prot.
P082 The compressor is overload Check whether the system of the compressor
is running normally
Antifreeze Temp. Sensor
Fault
P09 Antifreeze temp sensor is
broken or short circuited
Check and replace this temp sensor
Pressure sensor Fault PP The pressure Sensor is broken Check or change the pressure Sensor
or pressure
High Pressure Prot. E01 The high-pressure switch is
broken
Check the pressure switch and cold circuit
Low Pressure Prot. E02 Low pressure1 protection Check the pressure switch and cold circuit
Flow Switch Prot. E03 No water/little water in
water system
Check the pipe water ow and water pump
Waterway Anti-freezing
Prot.
E05 Water temp.or ambient temp.
is too low
Inlet and outlet temp.
too big
E06 Water ow is not enough
and low differential pressure
Check the pipe water ow and whether
water system is clogged or not
Anti-freezing Prot. E07 Water ow is not enough Check the pipe water ow and whether
water system is clogged or not
Winter Primary Anti-free-
zing Prot.
E19 The ambient temp. Is low in winter
Winter SecondaryA
nti-freezing Prot.
E29 The ambient temp. Is low in winter
Comp. Overcurrent Prot E051 The compressor is overload Check whether the system of the compressor
is running normally
Communication Fault E08 Communication failure between
wire controllerand main board
Check the wire connection between
remote wire controller and main board
Communication Fault
(speed control module)
E081 Speed control module and main
board communication fail
Check the communication connection
Low AT Protection TP Ambient temp is too low
EC fan feedback Fault F051 There is something wrong with fan
motor and fan motor stops running
Check whether fan motor is broken or locked
or not
Fan Motor1 Fault F031 1. Motor is in locked-rotor state
2.The wire connection between
DC-fan motor module and fan
motor is in bad contact
1.Change a new fan motor
2.Check the wire connection and make sure
they are in good contact
Fan Motor2 Fault F032 1. Motor is in locked-rotor state
2.The wire connection between
DC-fan motor module and fan
motor is in bad contact
1.Change a new fan motor
2.Check the wire connection and make sure
they are in good contact
Protection/fault Fault
display
Reason Elimination methods
Drv1 MOP alarm F01 MOP drive alarm Recovery after 150 seconds
Inverter ofine F02 Frequency conversion board and
main board communication failure
Check the communication connection
IPM protection F03 IPM modular protection Recovery after 150 seconds
Comp. Driver Failure F04 Lack of phase,step or drive
hardware damage
Check the measuring voltage check frequency
conversion board hardware
DC Fan Fault F05 Motor current feedback open
circuit or shortcircuit
Check whether current return wires connected
motor
IPM Overcurrent F06 IPM Input current is large Check and adjust the current measurement
Inv. DC Overvoltage F07 DC bus voltage > DC bus
overvoltage protection value
Check the input voltage measurement
Inv. DC Lessvoltage F08 DC bus voltage < DC bus
overvoltage protection value
Check the input voltage measurement
Inv. Input Lessvolt. F09 The input voltage is low, causing
the input current is high
Check the input voltage measurement
Inv. Input Overvolt. F10 The input voltage is too high, more
than outage protection current
RMS
Check the input voltage measurement
Inv. Sampling Volt. F11 The input voltage sampling fault Check and adjust the current measurement
Comm. Err DSP-PFC F12 DS Pand PFC connect fault Check the communication connection
Input Over Cur. F26 The equipment load is too large
PFC fault F27 The PFC circuit protection Check the PFC switch tube shortcircuit or not
IPM Over heating F15 The IPM module is overheat Check and adjust the current measurement
Weak Magnetic Warn F16 Compressor magnetic force is not
enough
Inv. Input Out Phase F17 The input voltage lost phase Check and measure the voltage adjustment
IPM Sampling Cur. F18 PM sampling electricity is fault Check and measure the current adjustment
Inv. Temp. Probe Fail F19 Sensor is short circuit or open
circuit
Inspect and replace the sensor
Inverter Overheating F20 The transducer is overheat Check and adjust the current measurement
Inv. Overheating Warn F22 Transducer temperature is too
high
Check and adjust the current measurement
Comp. OverCur. Warn F23 Compressor electricity is large The compressor overcu rrent protection
Input Over Cur. Warn F24 Input current is too large Check and adjust the current measurement
EEPROM Error Warn F25 MCU error Check whether the chip is damaged, replace
the chip
V15V over/under
voltage fault
F28 The V15V is overload or
undervoltage
Check the V15V input voltage in range