
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com326
Flowmeters,
Totalizers FLOW
RATE/TOTAL INDICATOR
Loop Powered,Converts Pulse Frequency to 4 to 20 mA,High/Low FlowAlarm
2-5/32
[54.92]
3-7/8 [98.57]
5
3-5/8
[92.08]
3-15/16
[100.02]
The SERIES RTI2 Rate & Total Indicator is an indicator/transmitter that takes the pulse
output signal from compatible owmeters, displays ow rate and total, and provides
output signals. It is compatible with the Series EFS2, IEFS, PDWS, and FLMG.
FEATURES/BENEFITS
• Can be mounted on a wall or mounted on the owmeter for added exibility
• Accessory mounting kits make it easy to change the mounting orientation
• High environmental protection with semi-exible urethane potted electrical
components
• Provides a pulse, 4 to 20 mA and dual-relay output
APPLICATIONS
• Water treatment
• Water utilities
• Industrial chemical handling
The SERIES BAT Analog Transmitters is a 4 to 20 mA transmitter for use with the
Series EFS2, IEFS, PDWS, PFT and FLMG.
FEATURES/BENEFITS
• Easy to set up and can be either wall or meter mounted
• Takes a pulse frequency output from the compatible ow meters and converts it into
a continuous 4 to 20 mA analog output signal
• The frequency for the owmeter output signal can be adjusted using four rotary
switches on the back of the transmitter and a microcontroller automatically scales all
other values accordingly
• The microcontroller averages inputs for more stable reading outputs and is adjustable
from 2 to 16 seconds
• Loop powered, 2 wire connection
• High environmental protection with semi-exible urethane potted electrical
components
APPLICATIONS
• Telemetry applications • Distributed control systems
• Data logging • Chart recording
SPECIFICATIONS
Input: 5 V pulse or contact closure; 1 to 15 pulses/s.
Temperature Limits: Process: -32 to 131°F (0 to 55°C); Storage: -40 to 158°F (-40
to 75°C).
Output: Current sinking square wave
pulse: Scaled pulse output (0.1 s duration 6.1 Hz max. or high alarm
output or low alarm output), sensor pass-through pulse output (un-scaled); Pulse
output range: 0.1 to 9999999.9 units/pulse; Analog: 4 to 20 mA, 24 to 30 VDC.
Power Requirements: 7 to 30 VDC @ 4 mA (4 to 20 mA when loop-powered).
Display: Rate: 8 digits, 1/2 H LCD; Total: 8 digits, 5/16 character height.
K-Factor Range: 0.001 to 999999.999.
Flow Alarm Output Range: 0.1 to 99999.99.
Enclosure Material Housing: Die-cast powder-coated aluminum; Faceplate
#HP92W Lexan.
Enclosure Rating: NEMA 4X (IP67).
Electrical Connection: Terminal blocks, #22 AWG, 3 conductor 18 (5.5 m) cable
(2000 max.).
Mounting: See model chart.
Weight: 3 lb (1361 g).
SPECIFICATIONS
Input: Open-collector solid state sensor. Averaging: 2, 4, 8, 16 s (DIP switch
selectable); Pulse Frequency: Min. 10 Hz @ 20 mA; Max. 999.9 Hz (rotary DIP
switch selectable).
Temperature Limits: 32 to 130°F (0 to 55°C).
Output: 4 to 20 mA.
Power Requirements: 24 to 36 VDC @ 4 to 20 mA when loop powered.
Response Time: 2 to 60 s; 90% FS (depends on input averaging).
Loop Resistance: 0 to 1300 Ω max.u
Enclosure Material: Die-cast powder-coated aluminum.
Enclosure Rating: NEMA 4X (IP66).
Electrical Connections: Terminal block.
Mounting: See model chart.
Weight: 3 lb (1361 g).
BLIND ANALOG TRANSMITTER
Converts Pulse Frequency to 4 to 20 mA,Loop Powered
BAT-M shown installed on Series
EFS2 meter. Meter sold separately.
BAT-W
uLoop Resistance: See Bulletin F-BAT
SERIES RTI2
SERIES BAT
®
4-7/64
[104.10]
4-7/64
4-23/64
[110.50]
3-3/8
[85.60]
2-1/2
[63.50]
ACCESSORIES
Model Description
MMK
WMK
Meter mounting kit
Wall mounting kit
MODEL CHART
Model Description
BAT-M
BAT-W
Blind analog transmitter, meter-mounted*
Blind analog transmitter, wall-mounted
*Compatible Series: EFS2, IEFS, PDWS, TBS and FLMG.
MODEL CHART
Model Description
RTI2-W
RTI2-M
RTI2-P
Wall-mounted
Meter-mounted
Panel-mounted
ACCESSORIES
Model Description
MMK2
WMK2
Meter mounting kit
Wall mounting kit