Range Selection
The range selection allows you to select one of four ranges in either feet per minute
(FPM) or meters per second (MPS).
Ranges:
FPM: 250, 500, 1000, 2000
MPS: 1.25, 2.5, 5, 10
Select the RANGE indicator by pressing ENTER when the RANGE LED indicator
is illuminated. The A,B,C LED indicators will display which range setting is currently
active. Press ENTER to enable adjustment. Turn the ADJUST until the desired range
indication is achieved. If you want to discard the adjustment press SELECT. If you
want to save the range press and hold ENTER. The RANGE LED will blink at a faster
rate for about 2.5 seconds then all of the LEDs will ash indicating the value was
saved.
The range setting is displayed with the LED indicators. The function of these indicators
is summarized on the control label inside the unit. The following table summarizes the
indicator status for each range setting.
Span Setting
The 641B has been calibrated for standard sea level conditions. As a mass ow device
it will always read the air velocity for standard conditions. Density changes due to
barometric or absolute pressure are not corrected automatically. The span setting
allows correction for altitude or other static pressure conditions that affect the density
of the process air. This parameter allows for a ±50% adjustment in the span value.
To make the span adjustment you will need to know either the absolute static pressure
or the corrected velocity of the process air. Set the air velocity to a known value, ideally
about 3/4 of the full-scale range value. Press SELECT until the SPAN LED indicator is
illuminated then press ENTER. The SPAN LED will begin to blink. Adjust the control for
the desired velocity then press and hold the ENTER button until all of the LED’s ash,
indicating the new value was saved. If you know the absolute static pressure you can
compute the corrected velocity using the following equation:
Vcor = Vrdg
Where:
P0 is the standard pressure of 29.9 in Hg or 760 mm Hg.
PA is the absolute pressure reading
Vrdg is the indicated velocity
Vcor is the corrected velocity
4 mA Setting
To make this setting you will need a milliammeter connected in the current loop.
Press SELECT until the 4 mA LED indicator is illuminated then press ENTER. The
milliammeter will now read approximately 4.0 mA. Adjust the control for a 4.0 mA
reading on the milliammeter. Press and hold ENTER to save the new setting. Pressing
SELECT before pressing ENTER will restore the previous calibration value.
20 mA Setting
With the milliammeter connected in the current loop, press SELECT until the 20-mA
LED indicator is illuminated. Press ENTER to begin adjustment of the 20-mA set point.
The 20 mA LED will now be blinking. Adjust the control until the milliammeter reads
20.0 mA. Press and hold ENTER to save the new setting. Pressing SELECT before
pressing ENTER will restore the previous calibration value.
Restoring Factory Default Settings
The 4 mA, 20 mA, and Range settings override factory default values. To restore these
to the factory default settings, start with the unit in the RUN mode. Press and hold the
ENTER button. The RUN LED indicator will begin to blink. After about 2.5 seconds all
LED indicators will ash indicating the factory settings have been restored. Range and
Filter settings are not affected by this operation. If you are unsure whether any have
been altered, press the SELECT button six times to sequence through all settings.
When you return to the RUN mode, the RUN LED indicator will blink several times
if either the 4 mA, 20 mA, or span settings have been changed. The RUN LED will
otherwise remain on.
MAINTENANCE
In general the 641B should require very little maintenance. In some installations dust
may accumulate on the sensor over time. This can be removed by carefully brushing
the probe with a small camel hairbrush. A jet of air may also dislodge the accumulated
buildup. Technical grade denatured or isopropyl alcohol may be used where the dust
accumulation does not respond to brushing. Always disconnect the power when
performing a cleaning operation.
Aside from the adjustments described above, the 641B cannot be eld calibrated.
Because of specialized computer instrumentation required, these units must be
returned to Dwyer Instruments for factory calibration.
TRANSMITTER SETUP
The 641B has been designed for easy setup. It has ve conguration parameters that
may be adjusted by the user. These parameters are Output Filter, Range (In English or
Metric), span, 4 mA set-point and 20 mA set-point. All of these may be adjusted at any
time in the eld. These adjustments may also be easily returned to factory default.
A set of controls and indicators are provided within the unit consisting of the select
button, enter button, adjustment control, and six LED indicators. When operating
normally, only the RUN LED indicator will be illuminated. During the setup operation
the LED indicators will indicate the parameter selected, when it is being adjusted,
and status of the adjustment process. If the unit is left in the setup mode for several
minutes without any activity it will return to the normal operating mode.
Two buttons and a potentiometer control the setup process.
The SELECT button is used to scroll between the setup parameters.
The ENTER button allows access to each parameter for adjustment.
The ADJUST potentiometer is used to change the value of the parameters.
Holding the ENTER button for 2.5 seconds saves the new parameter value.
Making Adjustments
The adjustment process has three steps: select the parameter, adjust the parameter,
save the new value. These are described in the following steps.
1. Select the Parameter: Each time the SELECT button is pressed the LED
indicator will advance to the next parameter. When the last parameter, SPAN, is
selected, the next time the SELECT is pressed the unit will return to RUN mode.
Press the SELECT button until the LED indicator illuminates the desired
parameter. Press ENTER. The selected indicator will begin to blink, showing the
parameter may now be adjusted. If the unit is left in the setup mode, after several
minutes it will reset to the operate mode.
2. Adjust the Parameter: Turn the ADJUST potentiometer until the desired setting
is made. This may be adjusted using a small screwdriver or similar tool. Be
careful not to force the control past its stops or damage will result.
3. Save the Parameter: To save the new parameter press and hold the ENTER
button. The LED indicator will begin to ash at a faster rate. After about 2.5
seconds all of the LED indicators will ash when the parameter is saved. If
you do not want to save the parameter press the SELECT button without entering
the parameter. The adjusted value will be discarded and next LED indicator will
be illuminated.
Adjusting the Output Filter
The output lter may be adjusted to smooth the readings when measuring turbulent
ow. The time constant may be adjusted from 0.5 seconds to 15 seconds. To adjust the
lter time constant, select the FILTER indicator. Press ENTER to enable adjustment.
Turn the ADJUST until the desired amount of damping is achieved. To save the value
press and hold the ENTER button until the LED indicators all ash, indicating the value
was saved. To discard the adjustment press SELECT before pressing the ENTER
button.
RANGE
FPM
250
500
1000
2000
MPS
1.25
2.5
5
10
MPS
15
25
50
75
FPM
3000
5000
10000
15000
ABC
000
001
010
011
ABC
100
101
110
111
Interior label diagram
OUTPUT FILTER RESPONSE (VALUES IN SECONDS)
% of Full Velocity
Filter Setting on Adjust Dial
Min. Mid. Max.
63%
90%
95%
99%
0.5
1.1
1.5
2.3
7.5
17.3
22.5
34.5
15
34.5
44.9
69.0
Range/Units Run Filter Range
Span 4 mA 20 mA
A B C
250 FPM
500 FPM
1000 FPM
2000 FPM
1.25 MPS
2.5 MPS
5 MPS
10 MPS
1
1
1
1
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
1: Indicator on
0: Indicator off