Electrical Connections
Caution: Connect signal only to terminals B(+) & 2(–). Connect 8 to 40 Vdc power
to A(+) and 1(–). Remove the external jumper across terminals 1 and 2 if there is
someexternaldcpathbetweensignalandpower,e.g.,signalandpowerreferenced
FOR INTRINSICALLY SAFE APPLICATIONS
Two CSA certified Zener barriers (not supplied by Dynalco) with the following
specifications are required. (Refer to drawing B8008843, other side of card).
Power Supply: A maximum voltage rating of +37 Vdc, an internal minimum
impedance of 874 ohms, and a maximum fuse rating of 160 milliamps.
Signal Input: A maximum voltage rating of +6, –6 Vdc, a minimum internal
impedance of 69 ohms, and a maximum fuse rating of 160 milliamps.
Calibration Instructions
Zero input always equals “0000” display with
power applied. With 1.000 mA input, adjust the
span adjust
for desired reading. For readings
below 200, set up four digits and a decimal point
to achieve higher accuracy. Example: set up 0 to
150 as 0 to 1500 and add a decimal point to
achieve 0 to 150.0 with 0.1 increments. For
readingsbeyond1999,add thefifthdummyzero.
• Calibration controls under plug (rear)
• Switches 1, 2, and 3 control decimal
points as shown
• Switch 4 adds a dummy zero (fifth digit,
fixed zero) to extend range beyond 1999
to 19990 View from Back of Meter
with Plug Removed
© 2000 Dynalco Controls 0100F
DPM-105
Universal Digital Panel Meter
Installation and Calibration Instructions
to the same dc supply, signal and power both
grounded, etc. Retain jumper if the signal is
isolated from the power, i.e. signal and power
fromseparate (isolated) supplies,only the power
is grounded, only the signal is grounded, etc.