Please strictly obey all the instructions in this manual and pay attention to all the warning and operation
information. It is not advisable to install or operate the machine before read this manual.
1. Safety Instructions
●The power outlet voltage may still have 220V even not connect to the mains power.
●For the battery cable or power cord replacement, please contact our service station or dealer to
purchase, in order to avoid fire caused by inadequate capacity or heat ignition.
●Do not place the battery or battery pack in the fire, that will injure due to explosion.
●Please do not open the UPS case as you will, there is risk of electric shock.
●Do not touch the battery connection terminals. Battery loop and input voltage loop is without
isolation, which may cause high voltage risk between the battery terminal and ground.
●Should not connect the equipment like hair dryer or electric heater, to ensure the safety for the UPS.
Attention:
UPS has high voltage inside, for thepersonal safety, please do not repair by yourself. If any questions,
please contact local service center or dealer.
2. Installation Instructions
2.1. Unpacking Inspection
●Open the UPS package, please check the enclosed accessories including a user manual,
communication cable, support feet, CD-ROM, the cable for connection to battery bank.
●Check the UPS if any damage in transport. If found damaged or parts missing, do not power on,
please turn to the carrier and dealer.
●To determine whether this UPS is the model you want to buy. Check the model name showed both
on the front panel and rear panel of UPS to confirm.
Model
Type
Model
Type
1KVA RTS
1KVA Standard model
1KVA RTH
1KVA Long backup model
1.5KVA RTS
1.5KVA Standard model
1.5KVA RTH
1.5KVA Long backup model
2KVA RTS
2KVA Standard model
2KVA RTH
2KVA Long backup model
3KVA RTS
3KVA Standard model
3KVA RTH
3KVA Long backup model

- 3 -
Note:
Please save the packaging box and packaging materials for future transport use. As heavy product,
please transit the UPS with care.
2.2. Attention items of installation
●The UPS location circumstance must be with good ventilation, away from water, flammable gases
and corrosive entities.
●Do not lie down the UPS against the wall so that front and side panel air intake hole, rear panel air
outtake hole unobstructed.
●The peripheral environment temperature around the UPS should be within 0 ℃~ 40 ℃.
●If dismantling the machine at low temperatures, there may be condensation droplets, users can not
install or operate it before completely getting dry both inside and outside, otherwise there will be
danger of electric shock.
●Place the UPS near the mains socket to cut off AC mains without any delay at any emergent case.
Attention:
●Make sure the load after the UPS is off when user start wiring the load to UPS, then turn on them
one by one later.
●Please connect the UPS with the socket which is over-current protected.
●All the power socket should be configured with earthling devise for safety.
●UPS could be electrified or powered whether the input power cable is tied on or not, even when the
UPS is off. The only way to cut off the output is switching off the ups and disconnecting the
mains power supply first and second.
●For all standard type UPS, it is advised to charge the battery over 8 hours before virginally used.
Once the AC mains power energizes the UPS, it will auto-start the charging work. If without prior
charging, UPS output remains as usual but with shorter back up time than normal.
●When connect motor, display equipment, laser printer etc, UPS power selection should be based on
the startup power of the load which is usually twice as rated power.
2.3 UPS and Battery Pack rear panel view
USB
TEL/MODEM/FAX
IN OUT
-
+-
+
24VDC 40A
EXT.BATTERY
RESET
FUSE 250VAC,8A
INPUT
OUTPUT SOCKET
INTELLIGENT SLOT
EPO
RS232
R
E
S
E
T
R
E
S
E
T
T
O
124
5
6
7
3
8
11
9
10
Figure 1. 1KVA rear panel

- 4 -
RESET
FUSE 250VAC,15A INPUT
OUTPUT SOCKET
EPO
USB
RS232
INTELLIGENT
SLOT
R
E
S
E
T
R
E
S
E
T
T
O
-
+-
+
48VDC 40A
EXT.BATTERY
TEL/MODEM/FAX
IN OUT
17
3 2
11 5
10
94
6
Figure 2. 1.5KVA & 2KVA rear panel
RESET
FUSE 250VAC,20A INPUT
-
+-
+
72VDC 40A
EXT.BATTERY
OUTPUT SOCKET
EPO
USB
TEL/MODEM/FAX
IN OUT
INTELLIGENT
SLOT
R
E
S
E
T
R
E
S
E
T
T
O
RS232
3 2 10 6
17
11 594
8
Figure 3. 3KVA rear panel
+-
DC OUTPUT
+ -
DC OUTPUT
72VDC 72VDC
11
Figure 4. Battery Pack rear panel
⑴Battery Slot;⑵Input Power Terminals;⑶Over Current Protector;⑷Intelligent Slot;
⑸Surge Protection for Network/Fax/Modem;⑹RS232 Communication Interface;
⑺Output Socket;⑻Fan;⑼Emergency Power Off;⑽USB;⑾Ground.
2.4 UPS output connection
Type
Connectors (The socket type is selectable)
1KVA RTS & 1KVA RTH
Multi-purpose Socket (3)
1.5KVA RTS & 1.5KVA RTH
Multi-purpose Socket (3)
2KVA RTS & 2KVA RTH
Multi-purpose Socket (3)
3KVA RTS & 3KVA RTH
Multi-purpose Socket (3)
Output connection of 1~3KVA type is configured with sockets,end user can plug the load cable on
the UPS socket to energize the load .

- 5 -
2.5 External battery connection procedure for long back up type
●As per different UPS type, end user are instructed to configure different battery voltage as below
sheet. More or less units are forbidden or else something abnormal or faulty will appear.
Type
Battery Quantity (unit)
Battery Voltage (volt)
1KVA
2
24
1.5KVA
4
48
2KVA
4
48
3KVA
6
72
●One end of battery cable is for UPS terminals while the other end with triple cables is for battery
terminals. Correct installation procedure is highly vital or else probable electric shock will arise.
Users are strictly required to follow the below procedure.
●Connect battery in correct way and make sure the total battery voltage is available for UPS.
●Correctly connect the long battery cable to battery terminals first, red wire is to positive plate while
black is to negative. If users connect the UPS first, electric shock or other danger could not be
avoided.
●Before connect load after UPS, users should supply main power to UPS and energize it.
●Connect long battery cable to UPS terminals with correct poles link (red is for “+”,black is
for“-”), UPS will auto start the charging work.
The connection view is like below figures:
USB
TEL/MODEM/FAX
IN OUT
-+ -+
24VDC 40A
EXT.BATTERY
RESET
FUSE 250VAC,8A
INPUT
OUTPUT SOCKET
INTELLIGENT SLOT
EPO
RS232
R
E
S
E
T
R
E
S
E
T
T
O
+-
RED
BLACK
+-
Figure 5. 1KVA long back up connection

- 6 -
RESET
FUSE 250VAC,15A INPUT
OUTPUT SOCKET
EPO
USB
RS232
INTELLIGENT
SLOT
R
E
S
E
T
R
E
S
E
T
T
O
-+ -+
48VDC 40A
EXT.BATTERY
TEL/MODEM/FAX
IN OUT
RED
BLACK
-
+
-
+-
+
-
+
Figure 6. 1.5KVA &2KVA long back up connection
RESET
FUSE 250VAC,20A INPUT
-+ -
+
72VDC 40A
EXT.BATTERY
OUTPUT SOCKET
EPO
USB
TEL/MODEM/FAX
IN OUT
INTELLIGENT
SLOT
R
E
S
E
T
R
E
S
E
T
T
O
RS232
RED
BLACK
-
+
-
+-
+
-
+
-
+-
+
Figure 7. 3KVA long back up connection
2.6 Installation
●UPS installation work should comply with local electrical standard and only can be done by
professional technician. 1KVA~3KVA units could use wall socket as input power connection.
●For all type UPS, it is advised to charge the battery over 8 hours before virginally used. Once the AC
mains power energizes the UPS, it will auto-start the charging work. If without prior charging, UPS
output remains as usual but with shorter back up time than normal.

- 7 -
Installation steps:
1) Please take out two groups of supports, assemble by embedding them with each other as shown
below.
2) Place the two supports in parallel, then put the machine into two supports.
3) It also can be placed horizontally if you like, please remember not to put the machine upside
down.
4) Machine and battery pack, can be put together, as two ways are showed in the pictures below, the
battery pack should be put under the machine.
3. Panel function and operation
The operation is simple, operators only need to read the manual and follow the operation
instructions listed in this manual without any special training.

- 8 -
3.1 Keys function
※ON/OFF key (+)
Press and hold this key for more than half a second to turn on/off the UPS.
※TEST/MUTE key (+)
Press and hold the key for more than 1 second in mains mode or economical mode: UPS runs the
self-test function.
Press and hold the key for more than 1 second in battery mode: UPS runs the mute function.
※ROTATE key (+)
Press and hold and for more than half a second (less than 2 seconds): Change the direction to
display items.
ON/OFF ROTATE
TEST/MUTE
25% 50% 75% 100%
25% 50% 75% 100%
VAC
HZ
LINE
OUTPUT
ON/OFF ROTATE
TEST/MUTE
25% 50% 75% 100%
25% 50% 75% 100%
OUTPUT
LINE
VAC
HZ
ON/OFF ROTATE
TEST/MUTE
25% 50% 75% 100%
25% 50% 75% 100%
VAC
HZ
LINE
OUTPUT
Press and hold
keys for more than
half a second.
The direction has
been changed in
the picture.
Inverter LED
Battery LED
Bypass LED
Warning LED

- 9 -
After finish that, the machine can be placed flat, as shown in the picture below
ON/OFF ROTATE
TEST/MUTE
OUTPUT
VAC
HZ
LINE
25% 50% 75% 100%
25% 50% 75% 100%
※INQUIRING key (,)
I. Non-function setting mode:
1) Press and hold or for more than half a second (less than 2 seconds): display the items
orderly.
2) Press and hold for more than 2 seconds: Circularly and orderly display the items every 2
seconds, when press and hold the key for some time again, it will turn to output status.
II. Function setting mode:
Press and hold the key for more than half a second (less than 2 seconds): Select the set option.
※FUNCTION SETTING key
I. Non-function setting mode:
Press and hold the key for more than 2 seconds: Function setting interface.
II. Function setting mode:
Press and hold the key for more than half a second (less than 2 seconds): Affirm the set option.
Press and hold the key for more than 2 seconds, exit from this function setting interface.
3.2 LED Function
From left to right is Inverter LED, Battery LED, Bypass LED and warning LED.
Warning red LED is on: UPS is fault. For example: Overload beyond the allowed time, inverter fault,
BUS fault, over temperature fault etc.
Bypass yellow LED is on: UPS is alarming. For example: Bypass mode supply power and etc.
Battery yellow LED is on: UPS is alarming. For example: Battery mode supply power and etc.
Inverter green LED is on: UPS is normally powered by mains or ECO mode or battery mode.
PS: LED display detail in different mode is listed in 5 item.

- 10 -
3.3 LCD display function
LCD displays as following Figure.
OUTPUT LOADTEMP
BATTERYINPUT
OUTPUT LOADTEMP
BATTERY
INPUT
VDC
KW
VAC
℃
%
KVA
HZ
VDC
KW
VAC
℃
%
KVA
HZ
LINEBYPASSBATT FAULT
STDBY ECO BAT
※Icon display area:
i. The top diagram is for load, battery, fan, fault and buzzer icon. When UPS is over loaded, the load
light will blink as same as the battery light blink when the capacity of battery get low or battery
disconnected. The left icon and right icon are for load and battery capacity indication, each grid of
which represents 25%.
ii. The fan icon is for fan working indication; when fan normally runs, the icon will display rotation;
if the fan is not connecting or faulty, the icon blinks;
iii. Press the mute button under the battery mode, buzzer icon will blink; it will disappear under other
cases.
iv. Fault icon will be on when UPS on fault mode, otherwise it will not.
※Digital display area:
i. Under none setting mode, it will display UPS output information when UPS normally runs in AC
mode; other information like input, battery, load and temperature will be showed after pressing the
inquiring key; Instead of this, fault code will be told in fault mode.
ii. Under setting mode, user could adjust different output voltage as well as activate ECO and bypass
mode by operating function setting key and inquiring keys.
※Mode display area:
After over 20 seconds, this area will display the work mode of the machine. e.g. STDBY(Standby
Mode),BYPASS(Bypass Mode), LINE(AC mode), BAT(Battery mode), BATT(Battery Self Test
Mode ),ECO(Economic Mode),SHUTDN(Shutdown Mode).
Icon display area
Digital display area
Battery capacity
display area
Load capacity
display area
Working mode
display area

- 11 -
3.4 Turn On/Off operation
3.4.1 Turn On operation
i. Turn on the UPS on Line mode
①Once mains power is plugged in, the UPS will charge the battery, at the moment, LCD shows that
the output voltage is 0, which means UPS has no output as default condition. If it is expected to
have output of bypass, you can set the bps “ON” by LCD setting menu.
②Press and hol d the ON key for m ore than hal f a second to start the U PS, then i t w i l l start the
inverter.
③Once started, the U PS w i l l perform a sel f-test function, LED will light and go out circularly and
orderly. When self-test finishes, it will come to line mode, the corresponding LED lights, UPS is
working on line mode.
ii. Turn on the UPS by DC without mains power
①When mains power is disconnected, press and hold the ON key for more than half a second to start
UPS.
②The operation of UPS in the process of start is almost the same as that when mains power is in.
After finishing the self-test, the corresponding LED lights and UPS is working on battery mode.
3.4.2 Turn Off operation
i. Turn off the UPS on line mode
①In the UPS boot state, press and hold the OFF key for more than half a second to turn off the UPS
and inverter.
②After UPS shutting down, LED go out and there is no output. If output is needed, you can set bps
“ON” on LCD setting menu.
ii. Turn off the UPS by DC without mains power
①In the UPS boot state, press and hold the OFF key for more than half a second to turn off the UPS.
②When turning off the UPS, it will do self-testing firstly. LED light and go out circularly and orderly
until there is no display on the panel.
3.5 UPS self-test/mute test operation
①When UPS is on line mode, press and hold the self-test/mute key for more than 1 second, LED
light and go out circularly and orderly. UPS comes to self-test mode and tests its status. It will exit
automatically after finishing testing, LED resume.
②When UPS is on battery mode, press and hold the self-test/mute key for more than 1 second, the
buzzer stops beeping. If you press and hold the self-test/mute key for one more second, it will
restart to beep again.

- 12 -
3.6 Panel function setting
UPS has setting function. It can run the setting on any mode. After setting, it will become effective at
once when meets some standards. The set information can be saved only when the battery connected
and normally turning off the UPS.
The operation of setting is as following:
3.6.1 ECO mode setting
①Enter the setting interface. Press and hold the function setting key for more than 2 seconds,
then come to setting interface, the letters “ECO” will flash.
②Enter the ECO setting interface. Press and hold the function setting key for more than half a
second(less than 2 seconds), then come to setting interface of ECO, at this time, the letters “ECO”
will light for a long time. The “ON” (or OFF) will flash. Press and hold the inquiring key
(,)for more than half a second (less than 2 seconds) to determine whether the ECO
function is used or not. If used, the corresponding word is “ON”, if not, the word is “OFF”. It can
be determined by yourself.
③Confirm the ECO selecting interface. After selecting ON or OFF, press and hold the function
setting key for more than half a second (less than 2 seconds). Now, the ECO setting function
is completed and the “ON” or “OFF” will light without flash.
④Exit from the setting interface. Press and hold function setting key for more than 2 seconds,
exit from the setting interface and turn to main interface.
25% 50% 75% 100%
25% 50% 75% 100%
LINE
25% 50% 75% 100%
25% 50% 75% 100%
LINE
3.6.2 Bypass mode setting
①Enter the setting interface. Press and hold the function setting key for more than 2 seconds,
then come to setting interface, Press and hold the function setting key for more than half a

- 13 -
second(less than 2 seconds), select the function setting, choose the bypass output interface, at the
moment, the letters “BPS” will flash.
②Enter the Bypass output selecting interface. Press and hold the function setting key for more
than half a second(less than 2 seconds), then come to setting interface of BPS, at this time, the
letters “BPS” will light for a long time. The “ON” letter will flash. Press and hold the inquiring key
(,)for more than half a second (less than 2 seconds) to determine whether the BPS
function is used or not. If used, the corresponding word is “ON”, if not, the word is “OFF”. It can
be determined by yourself.
③Confi rm the Bypass output sel ecti ng i nterface. A fter sel ecti ng ON or OFF, press and hol d the
function setting key for more than half a second (less than 2 seconds), Now, the BPS setting
function is completed and the “ON” or “OFF” will light without flash.
④Press and hold function setting key for more than 2 seconds, exit from the setting interface and
return to main interface.
⑤After setting BPS as ON, when mains power plugged in without turning on the UPS or no mains
power plugged in, there is bypass output but no power down backup function.
25% 50% 75% 100%
25% 50% 75% 100%
LINE
25% 50% 75% 100%
25% 50% 75% 100%
LINE
3.6.3 Output voltage setting
①Enter the setting interface. Press and hold the function setting key for more than 2 seconds,
then come to setting interface, Press and hold the inquiring key(,)for more than half a
second(less than 2 seconds), select the function setting, choose output voltage setting interface, at
the moment, the letters “OPU” will flash.
②Enter the output voltage selecting interface. Press and hold the function setting key for more
than half a second(less than 2 seconds), then come to setting interface of output voltage OPU, at
this time, the letters “OPU” will light for a long time. The numerical value below the OPU will

- 14 -
flash. Press and hold the inquiring key(,)for more than half a second (less than 2 seconds),
select the numerical value in accordance with “OPU” function. The provided voltages are 208V,
210V, 220V, 230V, 240V, you can choose anyone by yourself (The default is 220V).
③Confirm the output voltage selecting interface. After selecting numerical value, press and hold the
function setting , for more than half a second (less than 2 seconds). Now, the OPU setting
function is completed and the numerical value will light without flash.
④Exit from the setting interface. Press and hold function setting key for more than half a second
(less than 2 seconds), exit from the setting interface and return to main interface.
25% 50% 75% 100%
25% 50% 75% 100%
LINE
3.7 Parameters inquiring operation
Press and hold the inquiring key or for more than half a second(less than 2 seconds) to inquire
about items. The inquired items include input, battery, output, load, temperature. The displayed items
on LCD screen are showed as following:
Output:Display the output voltage and output frequency of the UPS. As the following graphic shows,
the output voltage is 220V, the output frequency is 50Hz.
VAC
HZ
OUTPUT
25% 50% 75% 100%
25% 50% 75% 100%
LINE

- 15 -
Load: Display the numerical value of the active power(WATT) and apparent power(VA) of the load.
For example, as the following graphics shows: the WATT of the load is 800W, VA is 1000VA (when
disconnect load, it is a normal phenomenon to show a small numerical value of WATT and VA).
25% 50% 75% 100%
25% 50% 75% 100%
W
KVA
LOAD
LINE
Temperature: Display the maximum temperature of the components in the UPS. As the following
graphics shows: the maximum temperature is 40 ℃.
25% 50% 75% 100%
25% 50% 75% 100%
TEMP
LINE
℃
Input: Display the voltage and frequency of the input. As the following graphics shows: the input
voltage is 220V, input frequency is 50Hz.
VAC
HZ
25% 50% 75% 100%
25% 50% 75% 100%
LINE
INPUT

- 16 -
Battery: Display the voltage and capacity of the battery (determined by type).As the following
graphics shows: the battery voltage is 24V, the capacity of battery is 100%(the capacity of battery is
approximately reckoned according to the battery voltage).
25% 50% 75% 100%
25% 50% 75% 100%
VDC
%
LINE
BATTERY
Press and hold the inquiring key for more than 2 seconds, LCD begins to display the items
circularly and orderly which transfer to another every 2 seconds. Press and hold the key for some time
again within 30s, it will return to output status.
4. Working mode introduction
4.1 Bypass mode
LED indications on front panel on bypass mode are as following:
Bypass yellow LED is on, the buzzer beeps once every 2 minutes . The warning red LED is on when
beeping, LCD displays are according to the exact load and battery capacity.
Turn to bypass mode under the following two conditions:
①Turn off the UPS on line mode while start the bypass output.
②Overload on line mode.
NOTE: When UPS is working on bypass mode, it has no back up function.
4.2 Line mode
LED indications on front panel on line mode are as following: The inverter green LED is on.
When input AC mains is in line with the working conditions, UPS will work on line mode.

- 17 -
4.3 Battery mode
LED indications on front panel on battery mode are as following: both the inverter green LED and
battery yellow LED are on, the buzzer beeps once every 4 seconds. The warning red LED is on when
beeping.
When the mains power down or instable, UPS will turn to battery mode at once.
4.4 ECO mode
LED indications on front panel on ECO mode are as following: both the inverter green LED and
bypass yellow LED are on.
When the input mains meets the input range of the ECO mode and start the ECO function, the UPS
will works on ECO mode. If inputAC mains exceeds the range of ECO several times in a row in a
minute but stays in inverter input range, UPS will work on AC inverting mode automatically.
4.5 Fault mode
LED indications on front panel on Fault mode are as following: warning red LED is on and LCD
display fault code and related icon.
FAULT
Fault mode (LCD interface on which the fault code display)
When UPS has fault. The warning LED is on and the buzzer beeps. UPS will turn to fault mode. UPS
cuts off the output and LCD display fault codes. At the moment, you can press the mute key to make
the buzzer stop beeping temporarily to wait for maintenance. You can also press the OFF key to shut
down the UPS when confirm that there is no serious fault.

- 18 -
5. The warning list of the LED light and display panel
Appendix 1: The table of the fault code
Fault reason Fault code
BUS voltage fault 00-14
Power soft start fault 15-24
Inverter voltage fault 25-39
Overheat 40-44
Output short circuit 45-49
Overload 50-54
Input NTC fault 55-59
Power fault 60-64
Input FUSE fault 65-69
Other 88
Appendix 2: Table for working status
S/N Working status
LED on Front panel
Alarm
beep Note
Normal Battery Bypass Fault
1 Inverter mode (mains power)
Mains power
voltage
●N
Mains power
high/low voltage
protection, switch
to battery mode
●●★One beep /
4 sec
2 Battery mode
Battery voltage -
normal
●●★
One beep /
4 sec
Warning for
abnormal voltage
of battery ●★
★One beep /
sec
3 Bypass mode
Mains power –
normal(under
Bypass)
●★One beep /
2 mins

- 19 -
Mains power –
high voltage
warning (under
Bypass)
★One beep /
4 sec
Mains power –
low voltage
warning (under
Bypass)
★One beep /
4 sec
4 Warning for battery disconnected
Bypass mode ●★
One beep /
4 sec
Inverter mode ●★
One beep /
4 sec
Power on / Switch
on
6 beeps
5 Output overload protection
Warning for mains
power overload ●★2 beeps /
sec
Protect operation
for mains power
mode overload
●●Long beep
Warning for
battery overload ●●★2 beeps /
sec
Protect operation
for battery mode
overload
●●●Long beep
6
Warning for
bypass mode
overload
●★One beep /
2 sec
7
Fans fault(fan
icon)▲▲▲★One beep /
2 sec
8 Faults mode ●Long beep
● LED Indicator lights long time
★L ED I ndi cator fl i cker
▲ LED indicator status depends on other conditions
Note: End user need to provide below information when require to maintain the UPS.
UPS Model No. & Serial No.
Date of fault occurrence.
Fault detail (LED status, noise, AC power situation, load capacity, for long back up type, battery

- 20 -
capacity configuration is also necessary.)
6. Trouble shooting
When the system runs in failure mode, the LCD will show as below:
FAULT
Explicit Troubleshoot Introduction Sheet
Trouble indication Failure point Solution
Fault LED on, audible buzzer
Persistently alarm, the fault code
is 00-14
Bus bar voltage fault
Please test the bus bar voltage or contact
the supplier.
Fault LED on, audible buzzer
persistently alarm, the fault code
is15-24 Soft start fault
Please check the soft start up circuit,
especially the soft start resistance or
contact the supplier directly.
Fault LED on, audible buzzer
persistently alarm, the fault code
is 25-39 Inverter voltage fault
Please contact the supplier.
Fault LED on, audible buzzer
persistently alarm, the fault code
is 40-44
Over temperature
inside
Please make sure the UPS didn’t get
overload, and the fan vent was not
obstructed, as well as the indoor
temperature is not high.
Leave alone the UPS 10 minutes for
cooling, and restart it. If failure remains,
please contact the supplier.
Fault LED on, audible buzzer
Persistently alarm, the fault code
is 45-49 Output short-circuit
Turn of the UPS and disconnect all the
load, make sure there no any fault or
internal short circuit of the load.
And then restart the UPS, if failure still,
please contact the supplier.
Fault code
Fault icon
This manual suits for next models
3
Table of contents
Other East UPS manuals
Popular UPS manuals by other brands

Regulus
Regulus PG 500 Compact Installation and operator's manual

Huawei
Huawei UPS2000-G-3 kVA user manual

Powercom
Powercom AP-1026 user manual

Sanyo Denki
Sanyo Denki SANUPS E11A102A instruction manual

Furman
Furman F1500-UPS E owner's manual

Toshiba
Toshiba Satellite 5000 Series Installation and operation manual