Instruction Leaflet IL0102002E
Effective April 2018
Ring Main Unit Operation Instruction
4 EATON CORPORATION www.eaton.com
1. General description
Chapter 1 Product introduction
The RVAC indoor fixed AC metal enclosed switchgear (hereafter
as RMU) is a new generation of SF6 gas insulated switchgear
developed by Cooper Power Systems, relying on the Edison R&D
center of powerful technical advantages, adopting the computer
simulation technology, aimed to provide high quality products for
electric network. This product is mainly used for the secondary
electrical distribution system of 3-phase AC 50Hz, with the rated
voltage of 12kV and 24kV, especially applicable for capturing and
distributing electric power in power systems such as small-sized
secondary distribution substations, switching stations, industrial
and mining enterprises, urban residential areas, airports, railways,
tunnels, and high rise buildings, greatly improving the reliability
and utilization rate of the power supply.
This product adopts a three-phase common enclosure structure,
using SF6 gas of excellent insulation and arc extinguishing
performance as medium, and achieving the goal of miniaturization
and light weight with optimized design; the product also uses
interface insulation structure, allowing flexible plug-in and
expansion of high voltage components. The product offers a range
of advantages such as simple structure, compact size, low price,
small floor space, high power supply quality and high power
supply safety. The basic module is a one-circuit load switch
cabinet and a one-circuit load switch plus current limiting fuse
combination cabinet module. In addition, several additional
modules are offered, including 3-circuit common enclosure RMU
(two incomings and one outgoing), one incoming and one
outgoing, bus tie cabinet, metering cabinet, voltage transforming
cabinet. The circuit breaker cabinet is also developed and
equipped, to expand the usage scope of the RMU. On the basis of
the indoor cases, the corresponding outdoor cases are supplied to
expand the use in outdoor environments.
The RUM has been equipped separately with primary circuit
devices inside the sealed enclosure, including the load switch or
load switch plus current limiting fuse. The load switch is used to
control the circuits to open and close load current and overload
current, while the load switch plus current limiting fuse is used to
control, open and close, and isolate the transformer and its
distribution circuit, as well as to offer protections against short
circuit current and overload current at the medium voltage side of
the medium voltage transformer, the transformer and low voltage
distribution circuits.
2. Operating conditions
2.1. Ambient air temperature:
Upper limit: +40°C, and the average temperature measured
within 24 hours ≤35°C;
Lower limit: -40°C;
2.2. Humidity
Relative humidity: daily average ≤95%,
monthly average ≤90%.
Vapor pressure: daily average ≤2.2kPa,
monthly average ≤1.8kPa.
2.3. Altitude: ≤1000m.
2.4. The ambient air is not apparently affected by dust, smoke,
corrosive or flammable gas, vapor or salt mist pollutions.
2.5. The vibration or quake external to the switchgear and
controlgear is negligible.
2.6. The amplitude of the electromagnetic interference induced in
the secondary system does not exceed 1.6kV.