Eaton ELC-GP02 User manual

IL05003005E.pdf
ELC-GP02
GRAPHIC PANEL SERIES
Instruction Sheet
WARNING
•DANGER - DC input power must be disconnected before any maintenance. Do not connect or
disconnect wires and connectors while power is applied to the circuit. Maintenance must be
performed by qualified technicians.
•DANGER - The ELC-GP02 requires 24VDC input power. The 24VDC input power should not be
connected to the RS-485 communication port. The unit may be destroyed or can’t be repaired if
the input power is improperly applied. Please always check the correctly input power wiring
before apply power.
•DANGER - An electrical charge will remain on the DC-link capacitors for 1 minute after power
has been removed. Do not conduct any wiring or investigation on the ELC-GP02 until 1 minute
after power has been removed. Do NOT touch terminals when power on.
•CAUTION - Always ground the ELC-GP02 by using the grounding terminal. Not only this acts as
a safety, but also filter out electrical noise. The ground method must comply with the laws of the
country where the unit is to be installed.
•CAUTION - ELC-GP02 may be damaged if the fixed support (shipped with the pack) is adjusted
too tight.
•Please carefully read this instruction before using the ELC-GP02.
•The ELC-GP02 display panel is waterproof. But please prevent grease, corrosive liquids and
sharp objects from contacting the ELC-GP02.
•Do not disconnect while circuit is live unless area is known to be non-hazardous.
•This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or Non-Hazardous
Locations only.
•Explosion Hazard – Substitution of components may impair suitability for class I, Division 2.
•Explosion Hazard – Do not disconnect equipment unless power has been switched off or the
area is known to be Non – Hazardous.
•Power, input and output (I/O) wiring must all be in accordance with Class I, Division 2 wiring
methods, Article 501-4 (b) of the National Electrical Code, NEPA 70,or as specified in Section
18-152 of the Canadian Electrical Code for units installed within Canada, and in accordance
with that location’s authority.
1 INTRODUCTION
1.1 Model Explanation
Thank you for choosing Eaton Logic Controler (ELC) GP series products. The features of ELC-GP02
are: resolution is 160*32, display 10*2 Chinese characters max. and Multilanguage support. Built-in
two communication ports (RS-232 and RS-485/RS-422, can be used simultaneously).
Communication and alarm indication LEDs. Extension slot for ELC-GPXFERMOD to copy settings
and programs rapidly and save download time. Built-in variety objects to meet your requirements.
1.2 Outline
1.3 Panel Function Explanation
PANEL COMPONENT EXPLANATION
Alarm Indication LED
Status 1: When power is on, the LED will flash three times slowly.
Status 2: When there is an abnormal situation, the LED will flash quickly along with an
alarm sound.
RS-232 Indication LED
(Yellow) It will be flashing when transmitting program and communicating by using RS-232.
RS-485 Indication LED
(Green) It will be flashing when communicating by using RS-485.
LCM display Area Liquid Crystal Module display area used to display current program state.
Esc Escape/Exit) Used to cancel an incorrect input, or to Exit a programming step.
Arrow Keys
UP/Pg Up: Used to increase the value or move up one page.
Pg Dn/DOWN: Used to decrease the value or move down one page.
Left: Left direction key. (move curser to left)
Right: Right direction key. (move cursor to right)
Enter Key Used to input a value or accept a programming command.
Function Keys
F0/0: It is used to be constant 0 and user can define the function of F0.
F1/1: It is used to be constant 1 and user can define the function of F1.
F2/2: It is used to be constant 2 and user can define the function of F2.
F3/3: It is used to be constant 3 and user can define the function of F3.
F4/4: It is used to be constant 4 and user can define the function of F4.
F5/5: It is used to be constant 5 and user can define the function of F5.
F6/6: It is used to be constant 6 and user can define the function of F6.
F7/7: It is used to be constant 7 and user can define the function of F7.
F8/8: It is used to be constant 8 and user can define the function of F8.
F9/9: It is used to be constant 9 and user can define the function of F9.
1.4 Back Panel
5-PIN terminals:
Wire gauge: 12-24 AWG
Torque: 4.5 lb.-inch
1.5 Dimension
Front panel (unit: mm [inch]) Right side diagram (unit: mm [inch])
Vertical view (Unit: mm)
1.6 Installation
Mounting ELC-GP02 into the opening is done by carefully fitting the unit into the opening and
pressing firmly on all four corners. You could fix it by using the fixed support packaged with
ELC-GP02. You should infix the fixed support in the back cover and turn the screw in to fix.
Warning: If you turn the screw exceeds torque: 4-5(kg-cm), ELC-GP02 may be damaged.
(Note:the flat surface shoud be a Type 4 “Indoor Use Only” enclosure or equivalent.)
Please leave sufficient space (more than 50mm) around the unit for heat dissipation.
Thickness:
0.5~9.0mm
50mm
50mm
Mounting dimension (unit: mm [inch])
Thickness Range 0.5~9mm
135~136.5[5.31~5.37]
85
[3.35]
2ELECTRICAL SPECIFIC
A
TION
2.1 Electrical Specification
ITEM ELC-GP02
Function Key / Digital Key F0/0~F9/9, ESC, ENTER and ARROW keys
External Input Power 24VDC (-15%~20%) 3W MAX.
Memory Capacity 256K Byte
CPU Hitachi MAX002
RAM of System 32K Byte
Communication Interface COM1: RS-232 and COM2: RS-485
Waterproof Class of Front Panel IP65/NEMA4/UL Type 4 (indoor use)
Environment Condition 0~50℃, relative humidity 20-90% RH(non-condensing)
Storage Temperature of Hardware -20~60 °C
Vibration 5Hz≦f<9Hz = Continuous: 1.75mm / Occasional: 3.5mm
9Hz≦f≦150Hz = Continuous: 0.5g / Occasional: 1.0g
Impact 15g peak, 11ms duration, half-sine, three shocks in each direction per
axis, on 3 mutually perpendicular axes (total of 18 shocks)
RF Radiation Test CISPR11, Class A
Static Electricity Discharge Test EN61000-4-2
RF Radiation Test EN61000-4-3
High Frequency Transient Test EN61000-4-4
Weight / Dimension 0.24kg / 147×97×35.5mm (Weight(W)×Height(H)×Deep(D))
Cooling Method Natural Air-Cooling
Temperature Code T6
Hazardous Location rating Class I, Division 2, Group A, B, C, and D
2.2 Function Specification
ITEM ELC-GP02
Display Screen
Screen STN-LCD
Color Monochromatic
Back-light
The back-light automatic turn off time is 1~99 minutes
(0 = do not to turn off)
(back-light life is about 50 thousand hours at 25℃)
Resolution 160X32 dots

■ELC-GP02 may connect to ELC using cable ELC-CBPCELC3
8 PIN MINI DIN
9 PIN D-SUB female
PC/HMI COM Port ELC COM1 Port
Rx
2
GND
1
2
3
4
5
6
7
8
Rx
GND
IL05003005E.pdf
6COMMUNICATION CONNECTION
■ELC-GP02 may connect to a PC by using cable ELC-CBPCGP3
ELC-CBPCGP3
1
5
6
9
9 PIN D-SUB
ON PC (RS-232) ON ELC-GP02/04
5
1
9
6
9 PIN D-SUB
9 PIN D-SUB female
RS-232:
3 Tx
5 GND
RS-232 9 PIN D-SUB male
PC COM Port
9 PIN D-SUB female
Rx 2
GND 5
3 Tx
5 GND
5V
ITEM ELC-GP02
Display Range 72 mm (W) X 22 mm (H)
Contrast Adjustment 15-step contrast adjustment
Language Font
ASCII: characters
Other: user define
Font Size (ASCII) 5 X 8, 8 X 8, 8 X 12, 8 X 16
ALARM Indication LED
1. Power on indication (Flash three times)
2. Flash for communication error or other alarm
3. Special Indication by user programming
RS-232 Indication LED Flashing when communicating by using RS-232.
RS-485 Indication LED It will be flashing when communicating by using RS-485.
Program Memory 256KB flash memory
External Interface
Serial Communication Port
RS-232 (COM1)
RS-232
Data length: 7 or 8 bits
Stop bits: 1or 2 bits
Parity: None/Odd/Even
Transmission speed: 4800bps~115200bps
RS-232: 9 PIN D-SUB male
Extension Communication
Port
RS-485 (COM2)
RS-485
Data length: 7 or 8 bits
Stop bits: 1 or 2 bits
Parity: None/Odd/Even
Transmission speed: 4800bps~115200bps
RS-485: 5-Pin Removal Terminal
Extension Slot The slot for program copy card
5-Pin Removal Terminal There are DC 24V input and RS-485 input
3 TRANSFER MODULE
The function of program copy card that ELC-GP02 provides to copy user program, system function
and passwords is different from the copy program. It is used to copy the whole HMI environment
settings and application programs to another HMI rapidly. It can save much time and manpower. The
operation is in the following.
Definition: ELC-GPXFERMOD = XMOD, GP Series = GP
Step GPÆXMOD XMODÆGP
1 Turn the switch on the XMOD to GPÆXMOD Turn the switch on the XMOD to XMODÆGP
2 Insert the XMOD into the extension slot of GP Insert the XMOD into the extension slot of GP
3 Input the power to GP Input the power to GP
4 It will display “remove XMOD” on the screen and
power on again
It will display “remove XMOD” on the screen and
power on again
HMI display message
Copy HMI program to XMOD (GPÆXMOD) Copy XMOD program to HMI (XMODÆGP)
If the model type of GP does not correspond with the
model type of program of XMOD, GP will display “GP
series and XMOD is different. Press Enter to Confirm
GP seriesÆXMOD. Press Esc to Exit”.
If there is no program in XMOD, GP will display “The
XMOD is Empty. XMODÆGP series is illegal”.
GP will display “GP ÆXMOD series Please wait!”
during transmission.
GP will display “GP ÆXMOD series Please wait!” during
transmission.
GP will display “Please Remove the XMOD and
Reboot” when completing transmitting.
GP will display “Please Remove the XMOD and Reboot”
when completing transmitting.
4 PASSWORD FUNCTION
1 If the password is forgotten, the password may be cleared using the following code: 8888. This
universal code will clear the password and all internal programs of ELC-GP02. The ELC-GP02
will be re-set to the factory settings.
2 Users may use 0~9 and A~Z as characters for the password. Users must use the function keys
F0~F4 to input the password characters.
F0: scrolls in a loop as follows 0 ÆA ÆB ÆC ÆD ÆE ÆF Æ0
F1: scrolls in a loop as follows 1 ÆG ÆH ÆI ÆJ ÆK Æ1
F2: scrolls in a loop as follows 2 ÆL ÆM ÆN ÆO ÆP Æ2
F3: scrolls in a loop as follows 3 ÆQ ÆR ÆS ÆT ÆU ÆV Æ3
F4: scrolls in a loop as follows 4 ÆW ÆX ÆY ÆZ Æ4
F5: it just can be used to be constant 5.
F6: it just can be used to be constant 6.
F7: it just can be used to be constant 7.
F8: it just can be used to be constant 8.
F9: it just can be used to be constant 9.
5 HARDWARE OPERATION
The steps to Startup the ELC-GP02:
1 Apply 24V DC power,
2 Enter into the startup display,
3 Enter the user-designed program,
4 Press Esc key and hold on for 5 seconds to return to system menu.
There are five selections in the system menu and are described below.
SELECTIONS EXPLANATION
Download
Program
Use the connection cable (ELC-CBPCTP3) to connect the serial communication port RS-232
of ELC-GP02 to a PC. Then use the ELCSoftGP software to download an application
program to the ELC-GP02.
Upload Program
Use the connection cable (ELC-CBPCTP3) to connect the serial communication port RS-232
of ELC-GP02 to a PC. Then use the ELCSoftGP software to upload an application program
from the ELC-GP02.
Copy Program
Transfer a program between two ELC-GP02 units.
1: transmit programs
2: receive programs
When transmitting programs and data between two ELC-GP02 unit. Set one ELC-GP02 to
“Receive Program” mode and the other ELC-GP02 to “Transmit Program” mode. Please use
twisted pair wires to connect the two units via the RS-485 ports.
GP02 Settings
Used to modify the ELC-GP02 system settings. There are 8 items that may be modified.
1. Communication protocol: Set the address of ELC-GP02 and the communication string for
either RS-232 or RS-485.
2. Contrast: Adjust the contrast of LCM display screen.
3. Back-light: adjust the automatic turn off time of LCM. Setting range is 00~99 seconds. If
set to 00, the LCM Back-light will not turn off.
4. Buzzer: Used to set the buzzer sound, normal mode or quiet mode.
5. Language Setting: Used to set the displayed language. English, Traditional Chinese,
simplified Chinese or user defined language.
6. Password setting: Used to set, enable, and disable the password function. If the
password function is enabled, it will require the user to input a password before the
system menu may be accessed. The factory password is 1234.
7. Startup display: Used to select the ELC-GP02 startup display.
8. Comm. Indicator : Used to select the communication Indicator enable or disable.
ELC Connection
There are two methods to connect to ELC:
1. Use the connection cable (ELC-CBPCELC3) to connect program communication I/O
RS-232C of ELC to serial communication port (COM1) RS-232 of ELC-GP02.
2. Use twisted cable to connect RS-485 of ELC to extension communication port (COM2)
RS-485.
Execution
Execute the internal program that download from ELCSoftGP or transmitted from other
ELC-GP02 units. When entering execution program, you can return to system menu by
pressing Escape/Exit (Esc) key for 5 seconds.
1
4
6
7
81,2
■The Pin definition of 9 PIN D-SUB
4
Other Eaton Industrial Monitor manuals
Popular Industrial Monitor manuals by other brands

Contemporary Research
Contemporary Research FeatherTouch FT6 product manual

Synergy Global Technology
Synergy Global Technology LCDR7U17-04 user manual

WAGO
WAGO WAGO-PERSPECTO 762 Series manual

Rockwell Automation
Rockwell Automation 6186-M12AL user manual

Lumel
Lumel N21 User Manual & Quick Start

Bowers
Bowers M1 user manual