manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Eaton
  6. •
  7. Monitor
  8. •
  9. Eaton PXM468K-DISP-6-XV User manual

Eaton PXM468K-DISP-6-XV User manual

Other Eaton Monitor manuals

Eaton PXMP Series User manual

Eaton

Eaton PXMP Series User manual

Eaton MFD-XM-80 Manual

Eaton

Eaton MFD-XM-80 Manual

Eaton MFD-Titan MFD-80 Series Manual

Eaton

Eaton MFD-Titan MFD-80 Series Manual

Eaton XV360 User manual

Eaton

Eaton XV360 User manual

Eaton XV-102 Series Manual

Eaton

Eaton XV-102 Series Manual

Eaton EASY-RTD-DC-43-03B1-00 Manual

Eaton

Eaton EASY-RTD-DC-43-03B1-00 Manual

Eaton XV400 10.4" User manual

Eaton

Eaton XV400 10.4" User manual

Eaton BreakerVisu NZM-XMC-MDISP35-MOD Manual

Eaton

Eaton BreakerVisu NZM-XMC-MDISP35-MOD Manual

Eaton PDI WaveStar Manual instruction

Eaton

Eaton PDI WaveStar Manual instruction

Eaton VFX Series User manual

Eaton

Eaton VFX Series User manual

Eaton E5324E Series User manual

Eaton

Eaton E5324E Series User manual

Eaton PXM4/6/8K User manual

Eaton

Eaton PXM4/6/8K User manual

Eaton Cutler-Hammer PanelMate Power Pro 5585... User manual

Eaton

Eaton Cutler-Hammer PanelMate Power Pro 5585... User manual

Eaton Power Xpert Multi-Point User manual

Eaton

Eaton Power Xpert Multi-Point User manual

Eaton MFD4-5-XRC-30 Manual

Eaton

Eaton MFD4-5-XRC-30 Manual

Eaton SG48-RC-LCD-30 Service manual

Eaton

Eaton SG48-RC-LCD-30 Service manual

Eaton POW-R-COMMAND 1000 User manual

Eaton

Eaton POW-R-COMMAND 1000 User manual

Eaton XV400 User manual

Eaton

Eaton XV400 User manual

Eaton Cutler-Hammer Pow-R-Command 750 User manual

Eaton

Eaton Cutler-Hammer Pow-R-Command 750 User manual

Eaton Cutler-Hammer IQ DP-4000 Programming manual

Eaton

Eaton Cutler-Hammer IQ DP-4000 Programming manual

Eaton PanelMate Power Series Operation manual

Eaton

Eaton PanelMate Power Series Operation manual

Eaton EASY-RTD-DC-43-03B1-00 User manual

Eaton

Eaton EASY-RTD-DC-43-03B1-00 User manual

Eaton PXBCM-DISP-6-XV User manual

Eaton

Eaton PXBCM-DISP-6-XV User manual

Eaton MFD-Titan User manual

Eaton

Eaton MFD-Titan User manual

Popular Monitor manuals by other brands

Samsung ME32C user manual

Samsung

Samsung ME32C user manual

ViewSonic VA926-LED user guide

ViewSonic

ViewSonic VA926-LED user guide

Furuno Mu 120c Operator's manual

Furuno

Furuno Mu 120c Operator's manual

Asus VB171D - 17" LCD Monitor Service manual

Asus

Asus VB171D - 17" LCD Monitor Service manual

AOC 9GLR Technical specifications

AOC

AOC 9GLR Technical specifications

DMG RAFFAELLO manual

DMG

DMG RAFFAELLO manual

AOC LM720 - 17" Technical specifications

AOC

AOC LM720 - 17" Technical specifications

Sony Trinitron GDM-F500 Service manual

Sony

Sony Trinitron GDM-F500 Service manual

Memorex MT1701 user guide

Memorex

Memorex MT1701 user guide

ViewSonic VE510s-4 Service manual

ViewSonic

ViewSonic VE510s-4 Service manual

Farenheit T-1503CM instruction manual

Farenheit

Farenheit T-1503CM instruction manual

Ditel DINOS DN129/AT Quick installation guide

Ditel

Ditel DINOS DN129/AT Quick installation guide

Sony SDM-S51 Specifications

Sony

Sony SDM-S51 Specifications

Kenwood DMX1025BT quick start guide

Kenwood

Kenwood DMX1025BT quick start guide

Dell S2409WFP user guide

Dell

Dell S2409WFP user guide

EverFocus EN-7517E instruction manual

EverFocus

EverFocus EN-7517E instruction manual

Dell P3222QE user guide

Dell

Dell P3222QE user guide

Panasonic TH152UX1 - 152" PLASMA TV Service manual

Panasonic

Panasonic TH152UX1 - 152" PLASMA TV Service manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

For detailed information concerning the operation and features
available in the PXM4/6/8K meter display - 6” color touchscreen
(PXM468K-DISP-6-XV), please refer to PXM4/6/8K meter color touch-
screen display features (IB150021EN) available on the Eaton website
(www.eaton.com/meters).
Figure 1. Color touchscreen display for PXM4/6/8K series meter.
Figure 2. Dimensions of the PXM4/6/8K meter display - 6” color
touchscreen (PXM468K-DISP-6-XV).
Installation
1. Disconnect and lockout all power to the enclosure.
2. Inspect the enclosure door to determine the best mounting loca-
tion for the PXM4/6/8K meter color touchscreen display.
ote:N A minimum clearance of 1.18 in. (30.0 mm) must be maintained
between the ventilation holes in the back of the display and any other
component within the enclosure.
3. Use the mounting template to mark the cutout area on the enclo-
sure door. Cut out the marked area.
Effective June 2019
Technical Data TD150029EN
PXM4/6/8K meter color touchscreen
display quick start guide
Figure 3. Cut out dimensions.
4. Ensure proper gasket placement on the PXM4/6/8K meter color
touchscreen display.
5. Insert the PXM4/6/8K meter color touchscreen display through
the cutout.
6. Fit the supplied threaded pins in the retaining brackets. The tips
of the threaded pins must point towards the wider ends of the
retaining brackets. Clip on the retaining brackets in the recesses
provided for them on the device.
Figure 4. Mounting the PXM4/6/8K meter display.
7. Check for proper alignment of the PXM4/6/8K meter color touch-
screen display. Then fix the device by torquing the threaded pins
to 0.1 Nm (0.86 lb-in) with a 2 mm hexagonal screwdriver. The
front of the display should be flush with the surface of the con-
trol cabinet at the fixing points.
Connections
To use the PXM4/6/8K meter color touchscreen display, provide
24 Vdc and connect the power cable between the color touchscreen
display and the PXM4/6/8K meter.
The display’s plug-in terminals provide connections for +24, GND
and common (0).
2
Technical Data TD150029EN
Effective June 2019
PXM4/6/8K meter color touchscreen
display quick start guide
EATON www.eaton.com
Figure 5. Power and COM port connections for the PXM4/6/8K meter display touch screen display.
PXM display power cable
PXMCM-1
COM 1 RS485
Display connection
PXM display data cable
PIN 2
PIN 1
RED
WHITE
BLACK&BARE
PIN 3
PHOENIX CONN.
TERMINATION
PIN 2
PIN 3
PIN 1
PHOENIX CONN.
TERMINATION
RED
WHITE
BLACK&BARE
H11 (XV)
PXM468K-DISP-6-XV
Eaton P/N 67A2180Hx1
YY-MM-DD
1.5"1.5"
72.0"
PIN 1
PIN 1
Eaton P/N 67A2181HXX
YY-MM-DD
1.5"
72.0"
PIN 1
PIN 2
PIN 3
RED
WHITE
BLACK&BARE
PIN 1
PHOENIX CONN.
TERMINATION
PIN 3
PIN 5
PIN 7
RED
BLACK
WHITE
DB9 SHELL
DB9 TERMINATION
H11 (XV)
SHIELD WIRE TERMINATED to
CM3
CM4
67A2181H02
67A2180H11
Included with the PXM4/6/8K meter color touchscreen display is a
data cable to connect the DB9 of the color touchscreen display to
3-terminal COM 1 (RS485) of the PXM4/6/8K meter.
The supplied cables are designed to connect the meter to the
PXM4/6/8K meter color touchscreen display as follows:
• Data cable: CM3
• Power cable: CM4
Figure 6. Meter web server configuration screen COM 1 & 2 setup.
PXMCM-1
COM 1 RS485
Display connection
In order to communicate with the display, the meter must be config-
ured as “Slave (RTU).” This can be set using the meter’s web server
configuration page for COM 1 & 2.
3
Technical Data TD150029EN
Effective June 2019
PXM4/6/8K meter color touchscreen
display quick start guide
EATON www.eaton.com
For best results, use the default communication settings for the
PXM4/6/8K meter and PXM4/6/8K meter color touchscreen display
(115.2 kbps, 1 start bit, 1 stop bit, no parity).
ote:N By default, the PXM4/6/8K meter color touchscreen display is pre-
set for a PXM4/6/8K meter slave address of “01”. To accommodate a dif-
ferent slave address, the user MUST change the PXM4/6/8K meter color
touchscreen display’s “Modbus ID”. This number MUST match the rotary
switch located on the side of the meter. This setting can be found under
Settings > Meter ID.
Figure 7. Changing the Modbus ID.
Meter firmware requirements
• The minimum meter firmware version required for compatibility is
13.3.6.1.
Technical information
• 640 x 480 pixel backlit VGA touch screen display.
• Power: 24 Vdc input.
• Recommended: PXM display power cable (67A2180H11)
between the display and PXM4/6/8K’s CM3 source
• Optonal: PSG60E (85-264Vac), PSG60F (320-576Vac)
Display measurements
• Height: 5.24 in. (133 mm);
• Width: 6.81 in. (173 mm);
• Depth: 1.54 in. (39 mm);
• Weight: 1.32 lb (600 g);
• Cutout dimensions: 4.61 in. x 6.18 in.(117.0 x 157.0 mm).
Ratings
• Front bezel IP rating: IP65;
• Operating temperature: 0 ~ 50°C (32 ~ 122°F);
• Storage temperature: -20 ~ 60°C (-4 ~ 140°F);
• Ambient humidity: 10% ~ 90% RH (0 ~ 40°C [32 ~ 104°F]),
10% ~ 55% RH (41 ~ 50°C [105.8 ~ 122°F]).
Technical Data TD150029EN
Effective June 2019
PXM4/6/8K meter color touchscreen
display quick start guide
Eaton
Electrical Sector
1000 Eaton Boulevard
Cleveland, OH 44122
United States
877-ETN-CARE (877-386-2273)
Eaton.com
© 2019 Eaton
All Rights Reserved
Printed in USA
Publication No. TD150029EN / TBG001461
June 2019
Eaton is a registered trademark.
All other trademarks are property of their
respective owners.
DISCLAIMER OF WARRANTIES AND
LIMITATION OF LIABILITY
The information, recommendations, descriptions and safety nota-
tions in this document are based on Eaton’s (“Eaton”) experience
and judgment and may not cover all contingencies. If further infor-
mation is required, an Eaton sales office should be consulted. Sale
of the product shown in this literature is subject to the terms and
conditions outlined in appropriate Eaton selling policies or other con-
tractual agreement between Eaton and the purchaser.
THERE ARE NO UNDERSTANDINGS, AGREEMENTS,
WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING
WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR
MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET
OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES.
ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF
EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT
BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE
PARTIES.
In no event will Eaton be responsible to the purchaser or user in
contract, in tort (including negligence), strict liability or other-wise
for any special, indirect, incidental or consequential damage or loss
whatsoever, including but not limited to damage or loss of use of
equipment, plant or power system, cost of capital, loss of power,
additional expenses in the use of existing power facilities, or claims
against the purchaser or user by its customers resulting from the
use of the information, recommendations and descriptions con-
tained herein. The information contained in this manual is subject to
change without notice.