Econex VSB Series User manual

Gas safety solenoid shut-off valve series VSB and VSA, ap-
proved according to the norm EN 161 with product iden-
tication and manufactured according to regulation EU
2016/426, are suitable for the automatic control of gases
belonging to the rst, second and third family.
On request there are versions for biogas and air. These val-
ves, normally closed for continuous and cyclic operation,
open by powering the coil and close quickly when there is
no tension.
Safety Shut-off Valves
series VSB and VSA
• Class A, Group 2 according to EN161
• Electromagnetic Compatibility – Directive 2004/108/CE
• Low voltage – Directive 2006/95/CE
• SIL 2 for single solenoid valves, if 2 valves are installed in series with tightness control, they reach SIL 3
• Quick and slow opening and quick closing
• Quiet operation
• Poliammidic resin encapsulated coils and metallic frame for anged bodies
• Pressure test points at inlet by both sides
• Accessories on request: by-pass, limit switch, manual max. ow adjustment
Valve body Brass OT-58 and die-cast aluminium
Pipe connections for valves with brass body Rp 3/8, Rp 1/2, Rp 3/4 according to EN 10226
Pipe connections for valves with aluminium body Rp1/2÷2accordingtoEN10226
Pipe anged connections for valves with aluminium body DN65÷200 PN16accordingtoISO7005
Inlet pressure 200 mbar, 360 mbar and 500 mbar
Opening/closing time on quick version < 1 second
Standard supply voltage 230V ac, 110V ac, 24V and 12V ac and dc
Frequency 50÷60 Hz, 50 Hz per 12V and 24V ac
Enclosure IP 65 - IEC 529
Supply voltage tolerance -15% - +10%
Duty cycle Continuous
Ambient temperature -20 / +60 °C
FEATURES
TECHNICAL FEATURES

Max. pressure
2 = 200 mbar
Supply voltage
A = 24V ac/50 Hz
B = 110V ac/50 - 60 Hz
C = 230V ac/50 - 60 Hz
VSB R 2 15 C
VSB = Safety shut-off valve in brass
Operation
R = Quick
RP = Quick with max. ow adjustament
Nominal diameter
10 = Rp 3/8
15 = Rp 1/2
20 = Rp 3/4
SHUT-OFF VALVES SERIES VSB...
FLOW CHART
Molle di taratura pressione
E = 24V dc
F = 12V dc
G = 12V ac / 50 Hz
VN(m3/h)
Aria
Metano
Gas di città
Propano
Butano
G.P.L.
dv=1
dv=0,64
dv=0,45
dv=1,56
dv=2,09
dv=1,70
Air
Methane
Town gas
Propane
Butane
L.G.P.

Max. pressure
2 = 200 mbar
5 = 500 mbar
Supply voltage
A = 24V ac/50 Hz
B = 110V ac/50 - 60 Hz
C = 230V ac/50 - 60 Hz
VSA R 2 15 C
VSA = Safety shut-off valve in aluminium
Operation
R = Quick
RP = Quick with max. ow adjustment
L = Slow
LP = Slow with max ow adjustment
LSP = Slow with max ow adjustment + rapid stroke
Nominal diameter
15 = Rp 1/2
20 = Rp 3/4
25 = Rp 1
E = 24V dc
F = 12V dc
G = 12V ac/ 50 Hz
Other accessories
BP = By-pass
I = signal lamp by valve feeding (in the connector)
M = limit micro-switch
F = Flanged (only for Rp 1)
BK = Black cataphoresis
BK
FLOW CHART
SHUT-OFF VALVES SERIES VSA... Rp 1/2 - 3/4 - 1

SHUT-OFF VALVES SERIES VSA... Rp 1.1/4 - 1.1/2 -2
FLOW CHART
Max. pressure
2 = 200 mbar
3 = 360 mbar
5 = 500 mbar
Supply voltage
A = 24V ac 50 Hz
B = 110V ac 50-60 Hz
C = 230V ac 50-60 Hz
E = 24V dc
VSA R 3 40 E
VSA = Safety shut-off valve in aluminium
Operation
R = Quick
RP = Quick with max. ow adjustment
L = Slow
LP = Slow with max ow adjustment
LSP = Slow with max ow adjustment + rapid stroke
Nominal diameter
32 = Rp 1.1/4
40 = Rp 1.1/2
50 = Rp 2
Other accessories
BP = By-pass
I = signal lamp by valve feeding (in the connector)
M = limit micro-switch
F = Flanged
BK = Black cataphoresis
BK

FLOW CHART
Max. pressure
3 = 360 mbar
Supply voltage
A = 24V ac 50 Hz
B = 110V ac 50-60 Hz
C = 230V ac 50-60 Hz
E = 24V dc
VSA R 3 80 E
VSA = Safety shut-off valve in aluminium
Operation
R = Quick
RP = Quick with max. ow adjustment
L = Slow
LP = Slow with max ow adjustment
LSP = Slow with max ow adjustment + rapid stroke
Nominal diameter
65 = DN 65
80 = DN 80
100 = DN 100
Other accessories
BP = By-pass
I = signal lamp by valve feeding (in the connector)
M = limit micro-switch
BK = Black cataphoresis
BK
125 = DN 125
150 = DN 150
200 = DN 200
SHUT- OFF VALVES SERIES VSA... FLANGED DN65÷DN200

Pipe
Rp
Max
pressure
(mbar)
Rating at
230 V
(VA)
Dimensions
(mm) Weight
(Kg) Model
ABC
R RP L - LP/LSP
1/2 200 18 70 135 150 200 74 0,85 VSA 215C...
500 18 VSA 515C...
3/4 200 18 70 135 150 200 74 0,85 VSA 220C...
500 18 VSA 520C...
1200 18 70 135 150 200 74 0,80 VSA 225C...
500 18 VSA 525C...
DIMENSIONI
MODELS AND RATING
Pipe
Rp
Max
pressure
(mbar)
Rating at
230 V
(VA)
Rating at
230 V with
Green conn.
(VA)
Dimensions
(mm) Weight
(Kg) Model
A B C
3/8 200 9 3 55 90,5 37 0,6 VSBRP210C...
1/2 200 9 3 55 90,5 37 0,6 VSBRP215C...
3/4 200 9 3 55 90,5 37 0,6 VSBRP220C...
SERIES VSB... QUICK OPENING
SERIES VSA….. QUICK / SLOW OPENING THREADED Rp 1/2, 3/4, 1
An energy saving connector Green for valuable reduction of energy consumption is also available (3 VA).

SERIES VSA… QUICK / SLOW OPENING THREADED Rp 1.1/4, 1.1/2, 2
SERIES VSA… QUICK / SLOW OPENING FLANGED
Pipe
DN
Max
pressure
(mbar)
Rating at
230 V
(VA)
Dimensions
(mm) Weight
(Kg) Model
ABC
R RP L LP/LSP
65
360
105 / 29 290 321 321 432 480 211 17 VSA 365C...
80 310 328 328 439 486 211 17,60 VSA 380C...
100
124 / 36
350 389 389 500 547 254 29,60 VSA 3100C...
125 480 570 570 681 728 322 34,00 VSA 3125C...
150 480 570 570 681 728 552 45,00 VSA 3150C...
200 47 / 5 600* ---- 920 1162 1162 ---- 101,00 VSA 3200C...
* Opening time 13 seconds ± 20%.
Pipe
Rp
Max
pressure
(mbar)
Rating at
230 V
(VA)
Dimensions
(mm) Weight
(Kg) Model
ABC
R RP L LP/LSP
1.1/4
200
89 / 25 160
185 200 260 260
140
3,4 VSA 232C...
360 210 225 285 285 3,6 VSA 332C...
500
1.1/2
200
89 / 25 160
185 200 260 260
140
3,4 VSA 240C...
360 210 225 285 285 3,6 VSA 340C...
500 210 285 285 285
2
200
89 / 25 160
210 225 288 288
140 3,6
VSA 250C......
360 235 235 295 295 VSA 350C...
500 235 235 295 295

Installation, adjustment and maintenance of the valve must be carried out exclusively by skilled and authorized service
technicians
1. Before electric wiring, check that the main voltage matches with the power supply voltage stated on the product label.
2. Disconnect power before wiring.
3. By wiring connector, use terminals and cables as reported in the Instruction leaet in the package.
4. Connect the power supply to terminals 1 and 2 and the ground wire to terminal .
5. Using energy saving Green connector with 12 and 24 Vdc comply with polarity.
1. Make sure that all operating data indicated on the safety shut-off valve label correspond to those of the system.
2. Before installing the safety shut-off valve, quit the gas supply and make sure that the pipeline is free from impurities. The pipeline
must be vibration-free.
3. The ow direction indicated by the arrow on the valve body must be respected, facing towards the user appliance. The safety valve
can be installed either horizontally or vertically, provided that the coil is not turned downwards.
4. When installing the safety shut-off valve in pipework do not use the coil as a lever, but use the correct wrench.
5. The sealing material must be applied to the external thread of the pipeline only and not to the internal thread of the safety shut-
off valve.
ADJUSTMENT OF FLOW RATE - OPENING TIME AND RAPID STROKE
1. Coil fastening nut
2. Flow rate adjustment
Unscrew the nut and spin the internal screw clockwise to reduce
and counter clockwise to increase the ow rate.
All the reported data are subject to be changed without notice. from 180911
Econex s.r.l. - Via Francesco De Sanctis, 53 - I-20141 Milano
Tel. +39 0289502912 - Fax +39 028463084 - www.econex.it - [email protected]
QUICK OPENING SLOW OPENING
WIRING INSTRUCTIONS
INSTALLATION AND OPERATING INSTRUCTIONS
1. Flow rate adjustment. Loosen screw A and rotate cylinder
B to the desired position. Tighten screw A to x the position.
2. Opening time adjustment. Turn screw C clockwise to
reduce the opening time or turn counter clockwise to increa-
se values.
3. Rapid stroke adjustment.
This manual suits for next models
1