Ei Electronics Ei450 User manual

1
Instruction Manual
Read and retain carefully for as long as the product is being used. It contains vital information on the operation and installation of your
Alarm Controller. The manual should be regarded as part of the product.
If you are just installing the unit, the manual must be given to the householder. The manual is to be given to any subsequent user.
Model: Ei450
Alarm ControllerAlarm Controller
Fire and CO

2
Contents
1. Overview .................................................................................................................................................
2. Installation .............................................................................................................................................
3. House Coding ........................................................................................................................................
4. Operation ...............................................................................................................................................
5. Guarantee .............................................................................................................................................
6. Troubleshooting the RF ....................................................................................................................
7. Technical Specification .....................................................................................................................
8. Getting your Alarm Controller Serviced ......................................................................................
9. System Diagnostics ............................................................................................................................
10. Contact Us ...........................................................................................................................................
3
6
7
12
15
16
17
18
19
24
Page

3
1. Overview
The Ei450 single button Alarm Controller tests and controls Fire, CO and combined (Fire + CO) Ei Electronics
RF Alarm systems.
Alarm Controller functionality
Function Description
Test All the Alarms can be tested from a centralised location
LocateThis will silence all the Alarms in the system except the one sensing Fire or CO
Silence This will silence the source Alarm(s)
Fire Indicator Indicates that a Fire Alarm has been activated
CO IndicatorIndicates that a CO Alarm has been activated
EOL Indicator Indicates that the Alarm Controller battery has reached its end of life (EOL)
Memory
The memory feature only works with some RF Alarms -
Contact us or visit our website for details.
The memory feature is confined to the system diagnostic mode and is not visible to the end user.

4
Fire / CO Alarm Controller
Fire
Indicator
House Code
Button
Front View of ControllerRear View of Controller
On / Off
Switch
System
Diagnostics
Mode
Button
Low Battery
Indicator
CO
Indicator
Light
Segments (4)
Test /
Control Button
MODE POWER H.CODE
OFFON

5
2. Installation
Install the Alarm Controller mounting plate at an accessible point on the
wall 1.4m +/- 0.2m from floor level. Consider an alternative location if
the controller will be operated by a disabled person.
Also consider security and chose a location where it will not be accidently
or otherwise operated.
Turn on the system by sliding the switch to the on position & check the
power up sequence.
A video of the Alarm Controller installation, house coding & operation is
available on our website - see ‘Contact Us’ section.
MODE POWERH.CODE
OFFON

6
Power up sequence
FIRE, BATTERY & CO indicators flash
Each individual segment lights up red
Each individual segment lights blue
Each individual segment lights green
After power up sequence all lights will go off to indicate standby mode.

7
3. House Coding
It is essential to House Code the Alarm Controller to all the other RF
Alarms and devices in the system to ensure they will not communicate
with nearby systems. Failure to house code the system may also result
in a system malfunction.
Press and hold the House Code button (H CODE) on the back of the
controller until all segments light up blue, then release. The segments
will flash rapidly for a moment on entering house code.
House code all other RF Alarms and devices in the system. Consult the
instruction manuals on how to house code the Alarms and devices. It
is essential that each individual alarm / device is put into house code
mode in it’s actual location.
WARNING
Fire / CO Alarm Controller
MODE POWERH.CODE
OFFON

8
Return to the Alarm Controller and check that all segments are
flashing blue. The number of flashes should equal the number of RF
Alarms and devices in the system. A system with 3 x Smoke Alarms, 1 x
CO alarm and 1 x Alarm Controller will result in 5 blue flashes. It may
take up to 10 minutes before all 5 flashes are seen.
The flash pattern will repeat every 5 to 10 seconds while the Alarm
Controller remains in house code.
If it fails to flash the correct number of times, then consult the
‘Troubleshooting the RF’ section of this instruction manual.
Now, walk around the house to verify that all the other RF Alarms and
devices are giving the correct amount of flashes.
If any of these fail to flash the correct number of times, then consult
the ‘Troubleshooting the RF’ section of this instruction manual.
Fire / CO Alarm Controller

9
To complete the commissioning, the system must exit house code
mode.
The units will automatically exit house code after 30 minutes. Once
coded the system will not communicate with any other RF Alarms and
devices outside the house coded group.
To manually exit house code press the house code (H CODE) button on
the back of the Alarm Controller. When all the segments light up blue,
release the button. This unit will then send an exit house code signal to all
the other RF Alarms and devices to exit house code.
After a short period the blue light will turn off and the system will return
to standby mode (normal). Depending on the number of RF Alarms and
devices in the system this period could vary from 5 to 20 seconds.
If you choose to make the Alarm Controller tamper proof remove the
pip (plastic post) using a pliers or similar tool.
Do not do this until the house coding procedure has been completed!
MODE PO
W
ON
Fire / CO Alarm Controller
MODE POWERH.CODE
OFFON

10
Slide the Alarm Controller onto the mounting base on the wall.
Check that the RF system is working by pressing the button on the Alarm
Controller until the TEST segment lights blue. This indicates a RF test
signal has been activated.
All the Alarms in the system will sound for a short period and then stop.
If the test fails, consult the ‘Troubleshooting the RF’ section.
Fire / CO Alarm Controller
Fire / CO Alarm Controller

11
Reset the house code
Sometimes in order to resolve an RF communication issue, e.g. Alarms have to be relocated, it may be
necessary to reset and house code all RF Alarms and devices in the system again.
To reset the Alarm Controller press and hold the house code button.
All segments will flash blue briefly and then go solid. After 5 seconds
approx. the segments will start flashing blue. At this point release
the house code button. The Alarm Controller has now been reset.
To reset the other RF Alarms and devices in the system consult the
appropriate instruction manuals.
Fire / CO Alarm Controller
MODE POWERH.CODE
OFFON

12
4. Operation
Frequent testing of the system is advised to ensure its continued and safe operation.
Guidelines and best practices for testing are as follows:
1. After the system is installed.
2. Once monthly thereafter.
3. After prolonged absence from the dwelling (e.g. after holiday period).
4. After repair or servicing of any of the systems elements or household electrical works.
Press and hold the button on the Alarm Controller until the TEST segment lights
up blue. When all the alarms in the system are sounding release the button. The
alarms will stop sounding after a period and the TEST segment will flash blue to
indicate the test has been completed.
WARNING
Testing the alarm system
Fire / CO Alarm Controller Fire / CO Alarm Controller

13
Remove the Alarm Controller from its cradle. If the unit has
been tamper proofed you will need to release the latch with
a screwdriver.
With the Alarm Controller in your hand press and hold the
button. Walk around the house and verify that each Alarm
is sounding. When testing is complete release the button
and replace the controller in its cradle. If the test fails go to
‘Troubleshooting the RF’ section.
If there is a fire, immediately evacuate the premises and telephone the fire brigade.
If the source of the alarm is not obvious go to the Alarm Controller and check to
see which indicator is illuminated, Fire or CO.
If the CO indicator is flashing, open doors & windows while evacuating the premises.
Contact the appropriate authorities to report the incident.
When the alarm system sounds
Fire / CO Alarm Controller
Walk round test (optional)
Fire / CO Alarm Controller
Fire / CO Alarm Controller

14
If the FIRE indicator is lighting and there is no obvious fire, press
the button. The LOCATE segment will change from red to blue.
After a 10 to 40 seconds period, all the Alarms in the system will
stop sounding except the source Alarm(s).
If you are satisfied there is no fire but the Smoke/
Heat Alarm is still continuing to alarm you may now
silence the system. Wait until the SILENCE segment is
flashing red and then press the button. The SILENCE
segment will turn blue, after a delay the Alarm(s) will
stop sounding and all segments on the controller will
flash green momentarily to indicate that the Alarm
Controller is back in standby.
Temporary Alarm Activation:
Your alarm system could be activated by a false or
temporary alarm condition and then return to normal
Fire / CO Alarm Controller Fire / CO Alarm Controller Fire / CO Alarm Controller
Fire / CO Alarm Controller Fire / CO Alarm Controller
Locate the source Alarm(s)
Silence the source Alarm(s)
Fire / CO Alarm Controller Fire / CO Alarm Controller

15
standby mode without being noticed. Should this happen the Ei450 will continue to flash either the Fire or CO
icon rapidly for a two minute period. If the system has been activated by a CO alarm the Ei450 will continue to
flash the CO Icon for a 24 hour period but at a lower rate of 1 flash every 60 seconds.
Should you observe this condition contact the appropriate authorities immediately.
5. Guarantee
Ei Electronics guarantees this device for five years from the date of purchase against any defects that are due
to faulty materials or workmanship. If this device should become defective within the guarantee period, we shall
at our discretion repair or replace the faulty unit.
This guarantee only applies to normal conditions of use and service, and does not include damage resulting
from accident, neglect, misuse, unauthorised dismantling, or contamination howsoever caused. This guarantee
excludes incidental and consequential damage.
This guarantee does not apply to any product that has been modified in any way by a third party or has been
fitted with a third party element.
Do not interfere with the device or attempt to tamper with it. This will invalidate the guarantee and may result
in malfunction.
This guarantee is in addition to your statutory rights as a consumer.

16
6. Troubleshooting the RF
If, when checking the RF interconnection, some of the Alarms do not respond to the Alarm Controller
remote control test, then:
(i) Ensure the Alarm Controller has been activated correctly. Check that the power on procedure operates
as described in the ‘Installation’ section.
(ii) Repeat House Code procedure (see ‘House Coding’ section).
(iii) Relocate the Alarm Controller and/or rotate/relocate the RF Alarms. There are a number of reasons why
the RF signals may not reach all the Alarms in your system. Try rotating the Alarms or relocating the
Alarms (e.g. move them away from metal surfaces or wiring) as this can significantly improve signal
reception.
Rotating and/or relocating the Alarms may move them out of the range of existing units even though
they may have already been House Coded correctly in the system. It is therefore important to check that
all Alarms are communicating in their final installed positions. If Alarms are rotated and/or relocated,
we recommend that all Alarms are returned to the factory settings (see the respective use and care
instructions). Then House Code all Alarms again in their final positions. The RF interconnection should
then be checked again.

17
7. Technical Specification
Supply Voltage: Powered for life Lithium battery
Battery Capacity: 1600 mAh
RF Frequency: 868.499Mhz
Temperature Specification: -10oC to 40oC
Humidity: 15% - 95% (Non Condensing)
Receiver Category: Cat 2
RF Performance: EN 300-220-2
EMC Performance: EN 301 489-1, EN 301 489-3
Safety Testing: EN 60065
RF Power: -11dBm
Interconnection: Up to 12 devices *
* We recommend, for ease of installation and RF communication, that up to 12 RF devices can be installed
in any one RF coded system. Please contact us for further advise if additional RF devices are required.

18
8. Getting the Alarm Controller serviced
If your Alarm Controller fails to work after you have carefully read all the instructions and checked that
the unit has been installed correctly contact Customer Assistance at the nearest address given at the end
of this booklet.
If it needs to be returned for repair or replacement, slide the switch to the
off position, place it in a padded box and send it to ‘Customer Assistance
and Information’ at the nearest address given on the unit or in this booklet.
State the nature of the fault, where the Alarm Controller was purchased and
the date of purchase.
MODE POWERH.CODE
OFFON

19
9. System Diagnostics
The system diagnostic mode does not work with all RF alarms and accessories. If the system diagnostic
features are required for your installation please contact technical support to verify that all your RF
components are compatible with these features.
The System Diagnostic features are intended to assist professional installation and maintenance
personal to install, commission and maintain the RF Fire and CO systems utilising the Alarm Controller.
These features are not intended for the home owner / tenant and should only be used by personnel
described above.
The system diagnostic mode allows the user to access:
1. A two minute “Long Test”. This is an alternative to the walk round
test described previously.
2. The alarm memory and identify an Alarm that has been previously
activated.
WARNING
WARNING
System Diagnostic Mode
MODE
Fire / CO Alarm Controller
MODE
Fire / CO Alarm Controller

20
First of all, press the button to perform a simple test of your system. Then, to enter the system diagnostic mode use
a small screwdriver to press the MODE button on the back of the unit until all segments light up in green. Quickly
release the MODE button, the system diagnostic mode is now activated.
If there has been no previous alarm memorized, the Test Segment will flash green and you can perform the two
minute long test.
If there has been a previous alarm memorized, the Memory Segment will flash green. Please proceed to the “Check
Alarm memory” section.
On entering the system diagnostic mode the TEST segment will flash green
inviting you to press the button.
When you press the button the TEST segment will turn blue and all the
Alarms in the system will sound for 2 minutes.
This will allow you to walk around the house and verify that each individual
Alarm is sounding. During the test you may notice the TEST segment flash
blue periodically indicating that a refresh signal is being transmitted.
The test will cease:
1. Automatically after 2 minutes. Once the 2 minutes have lapsed, all
segments will flash green indicating that the test has been completed
and that the Ei450 has exited the diagnostic mode.
Two minute - Long test
Fire / CO Alarm Controller Fire / CO Alarm Controller
Other manuals for Ei450
2
Table of contents
Other Ei Electronics Controllers manuals
Popular Controllers manuals by other brands

ICP DAS USA
ICP DAS USA 7188XA Hardware user manual

Icop
Icop VDX-6372RD user manual

Rockwell Automation
Rockwell Automation micrologix 1200 installation instructions

Ingersoll-Rand
Ingersoll-Rand TS900 Series Installation and maintenance information

DELTA DORE
DELTA DORE TYXIA 641 installation instructions

Xylem
Xylem McDonnel & Miller 157S-RBP-MD instruction manual

Worldsemi
Worldsemi WS2821 manual

Crystop Display Gmbh
Crystop Display Gmbh AutoSat 2 Control user manual

Enttec
Enttec OCTO MK2 user manual

Mitsubishi
Mitsubishi MELSEC-AnS Series Handbook

Mitsubishi Electric
Mitsubishi Electric MELFA BFP-A8787-F instruction manual

Hydrofarm
Hydrofarm Autopilot PX1 instructions