PAR. DESCRIPTION M.U. RANGE DEFAULT
dOn
Delayed start. The parameter indicates that a protection is active on the general compressor relay
actuations. At least the indicated time must elapse between the request and the actual activation of the
compressor relay.
sec 0 ... 255 2
dOF Delay time after power-off: the delay time indicated must elapse between deactivation of the compressor
relay and the next power-on. min 0 ... 255 0
dbi Delay between switch-ons; the delay time indicated must elapse between two consecutive compressor
power-ons. min 0 ... 255 2
OdO Delay in activating outputs after the instrument is switched on or after a power failure.
0 = Not active min 0 ... 255 0
dS2 DEFROST (dEF)
dtY
Defrost mode
0= Electric defrost (OFF Cycle defrost), i.e. compressor not running during defrost);
NOTE: electrical defrost + air defrost, when the fans are connected in parallel to the defrost output relay
1= cycle inversion defrost (hot gas, or compressor on during defrost);
2 = “Free” mode defrost (independent from the compressor)
num 0 ... 2 0
dit
Interval between defrost cycles
Interval between the start of two consecutive defrost cycles.
0= Function disabled (defrost NEVER performed).
hours/mins/
secs 0 ... 255 6 hours
dCt
Defrost interval count mode
0= Compressor running time (DIGIFROST® method);
defrost active ONLY when the compressor is on.
N.B.: compressor running time is counted separately from the evaporator probe (count active also when
evaporator probe missing or faulty).
1= Appliance running time; defrost counting is always active when the machine is on and starts at each
power-on;
2= Compressor stopped. Every time the compressor stops, a defrost cycle is performed according to
parameterdtY;
3= With RTC. Defrost at specific times set by parameters dE1...dE8, F1...F8
num 0 ... 3 1
dOH Defrost cycle enabling delay from request
Delay preceding start of first defrost after call. min 0 ... 59 0
dEt Defrost timeout
Determines the maximum defrost time on Evaporator 1.
hours/mins/
secs 1 ... 255 30 min
dSt Defrost end temperature
Defrost 1 end temperature (determined by evaporator probe 1). °C/°F -302.0 ...
1472.0 6.0
dPO
Defrost enabling request from power-on
Determines whether or not the instrument must defrost at power-up
(provided that the temperature measured at the evaporator will allow defrost).
n(0) = No, no defrost at power-on; y(1) = Yes, defrost at power-on.
flag n/y n
FANS (FAn)
FSt Fans lockout temperature; if the value read is greater than FSt, the fans will be stopped.The value may
be positive or negative. °C/°F -58.0...302 0.0
FAd Fans activation differential °C/°F 0.1 ... 25.0 0.1
Fdt Fans activation delay after a defrost cycle min 0 ... 250 0
dt dripping time. Dripping time. min 0 ... 250 0
dFd Operating mode of evaporator fans during defrost.
n (0) = no (depending on the FCO parameter); y(1) = yes (fan off). flag n/y y
FCO Evaporator fans operating mode.The status of the fans will be:
With the compressor ON, the fans are thermostat-controlled.With the compressor OFF, it depends on FCO
FCO=0, fans OFF
FCO=1-2, fans thermoregulated
FCO=3-4, fans in duty cycle
Dutycycle: controlled by way of parameters “FOn” and “FOF”.
num 0 ... 4 1
ALARMS (ALr)
AFd Alarms cut-in differential. °C/°F 0.1 ... 25.0 1.0
HAL Probe 1 maximum alarm. Temperature value (intended either as distance from setpoint or as an absolute
value based on Att) above which the probe will trigger activation of the alarm signal. °C/°F LA1...302 5.0
LAL Probe 1 minimum alarm. Temperature value (intended as distance from setpoint or as an absolute value
based on Att) beneath which the probe will trigger activation of the alarm signal. °C/°F -58.0...HA1 -5.0
PAO Alarm exclusion time after device is switched on following a power failure.
This parameter refers to high/low temperature alarms LAL and HAL only. hours 0 ... 10 3