USER INTERFACE
The user has a display and four keys for
controlling status and programming of the
instrument.
KEYS AND MENUS
UP key Scrolls through the menu
items
Increases the values
DOWN key Scrolls through the menu items
Decreases the values
fnc key ESC function (exit)
set key Accesses the setpoint
Accesses the menus
Confirms the commands
Displays the alarms (if active)
At start-up the instrument performs a
Lamp Test; for five (5) seconds the display
and the leds blink, in order to verify their
integrity and correct operation; afterwards
it will appear the label “Lod” (Loading) for
ten (10) seconds. The instrument has two
main menus: the “Machine Status” and
“Programming” menu.
ACCESSING AND USING MENUS
Resources are arranged in a menu, which
can be accessed by pressing and quickly
releasing the “set” key (“Machine Status”
menu) or by holding down the “set” key
for more than 5 seconds (“Programming”
menu).
To access the contents of each folder, indi-
cated by the relevant label, just press the
“set” key once.
You can now scroll through the contents
of each folder, modify it or use its func-
tions. If you do not use the keyboard for
over 15 seconds (time-out) or if you press
the “fnc” key once, the last value shown
on the display is confirmed and you return
to the previous screen mask.
MACHINE STATUS MENU
To access the “Machine Status” menu
Press and quickly release the “set” key.
The label “SP1” appears.
By using the “UP” and “DOWN” keys you
can scroll through the other folders in the
menu:
-AL: alarm folder (if alarms present);
-SP1: Setpoint 1 setting folder.
Setpoint Setting
Access the “Machine Status” menu by
pressing and quickly releasing the “set”
key. The label of the “SP1” folder appears.
To display the Setpoint value press the
“set” key again.
The value appears on the display.
To change the Setpoint value, use the “UP”
and “DOWN” keys within 15 seconds.
If the parameter is LOC = y the Setpoint
cannot be changed.
PROGRAMMING MENU
To enter the “Programming” menu, press
the “set” key for more than 5 seconds.
If specified, the access PASSWORD will be
requested, (parameter “PA1”), and the
label of the first folder will follow.
To scroll through the other folders, use
the “UP” and “DOWN” keys.
To enter the folder, press “set”. The label
of the first visible parameter appears. To
scroll through the other parameters, use
the “UP” and “DOWN” keys; to change the
parameter, press and release “set”, then
set the desired value using the “UP” and
“DOWN” keys, and confirm with the “set”
key to move to the next parameter.
PLEASE NOTE: It is strongly recommended
to switch off and switch on again the con-
troller anytime parameters have been
changed to prevent malfunctioning on
configuration and/or ongoing timings.
PASSWORD
The password “PA1” allows access to level
1 parameters. In the standard configura-
tion passwords are not present.
To enable them and assign them the
desired value, access the “Programming”
menu, within the folder with the “diS”
label. If passwords are enabled, you will
see it at the entrance of the “Program-
ming” menu.
COPY CARD
The Copy Card is an accessory connected
to the TTL serial port which allows pro-
gramming quickly the instrument parame-
ters (upload and download parameter’s
map). The operation is performed as fol-
lows:
Format
This command allows copy card formatting,
an operation necessary in case of first use
or to copy maps with different models.
Warning: if the copy card has been pro-
grammed, using the “Fr” the data entered
are erased. This operation cannot be can-
celled.
Upload
This operation loads the programming
parameters from the instrument.
Download
This operation downloads to the instru-
ment the programming parameters.
The operations are performed accessing
the folder identified by the “FPr” label and
selecting, according to the case, “UL”, “dL”
or “Fr” commands; the operation is con-
firmed by pressing the “set” key. If the
operation is successful an “y” is displayed,
on the contrary, if it fails a “n” will be dis-
played.
Download “from reset (instrumennt
OFF”
Connect the Copy Card with the instru-
ment OFF (not under voltage).
When the instrument is switched on the
programming parameters will be down-
loaded into the instrument (this operation
takes about 15 seconds); after the lamp-
test the diplay will show for about 5 sec-
onds:
• label dLY if copy operation successful
• label DLn if not
PLEASE NOTE:
• after the download operation the instru-
ment will immediately work with the new
parameters map setting
KEYBOARD LOCKING
The instrument includes a facility for dis-
abling the keyboard, by programming the
“LOC” parameter (see folder with “diS”
label). If the keyboard is locked, you can
still access the programming menu by
pressing the “set” key.
The Setpoint can also be viewed.
IC 912 Pt100-TC
single stage electronic controller
fnc
set
LED
Position Related Function Status
OUT1 relay 1 (OUT1) ON when the regulator is started up; blinking in case of delay,
protection or blocked enabling
Alarm ON when the alarm is enabled;
DIAGNOSTICS
The alarm condition is always signalled by
the led of the alarm icon
The alarm signal (referred to the analogue
input) is shown as E1 on the instrument
display for a faulty analogue input error or
for reading values outside the viewing
range.
When the analogue input detects an error
condition:
• the code E1 is displayed
• the regulator is activated as indicated by
the "On1" and "OF1" parameters if pro-
grammed for the duty cycle or:
PLEASE NOTE: In case of wrong connec-
tion of the 3rd wire (Pt100 sensor) in “AL”
folder it will appear the label “Pt3”.
For few seconds the display will shows
a uncorrect temperature.
INSTALLATION
The instrument is designed for panel
mounting. Make a hole of 29x71 mm,
insert the instrument and fix it using the
brackets provided. Do not mount the
instrument in humid and/or dirty places; it
is suitable for use in ordinary polluted
places. Ventilate the place in proximity to
the instrument colling slits.
ELECTRICAL
WIRING
Attention! Never work on electrical con-
nections when the machine is switched on.
The instrument is equipped with screw ter-
minal boards for connection of electrical
cables with a diameter of 2.5 mm2(one
conductor only per terminal for power
connections).
For the capacity of the terminals, see the
label on the instrument.
The relay contacts are voltage free. Do not
exceed the maximum current allowed; in
case of higher loads, use an appropriate
contactor. Make sure the power supply
voltage complies with the one required by
the instrument.
In 12V versions the power supply must be
provided by a security transformer with
the protection of a delayed 250 mA fuse.
Probe cable (Pt100 model), power supply
cables and the TTL serial cables should be
distant from power cables.
(Pt100 model)
Probe can be extended using a regular
bipolar cable (note that the extension of
the probes affects the EMC electromagnet-
ic compatibility of the instrument: pay
extreme attention to wiring).
CONDITIONS OF USE
PERMITTED USE
For safety reasons the instrument must be
installed and used according to the
instruction provided and in particular,
under normal conditions, parts bearing
dangerous voltage levels must not be
accessible.
The device must be adequately protected
from water and dust as per the application
and must also only be accessible via the
use of tools (with the exception of the
frontlet).
The device is ideally suited for use on
household appliances and/or similar refrig-
eration equipment and has been tested
with regard to the aspects concerning
European reference standards on safety. It
is classified as follows:
• according to its manufacture: as an auto-
matic electronic control device to be
incorporated by independent mounting;
• according to its automatic operating fea-
tures: as a 1 B-type operated control type;
• as a Class A device in relation to the cat-
egory and structure of the software
UNPERMITTED USE
Any other use other than that permitted is
de facto prohibited. It should be noted
that the relay contacts provided are of a
practical type and therefore subject to
fault. Any protection devices required by
product standards or dictated by common
sense due to obvious safety reasons should
be applied externally.
LIABILITY AND RESIDUAL
RISKS
Invensys Controls Italy S.r.L. shall not be
liable for any damages deriving from:
- installation/use other than that pre-
scribed and, in particular, that which does
not comply with safety standards anticipat-
ed by regulations and/or those given here-
in;
- use on boards which do not guarantee
adequate protection against electric shock,
water or dust under the conditions of
assembly applied;
- use on boards which allow access to dan-
gerous parts without the use of tools;
- tampering with and/or alteration of the
products;
TECHNICAL DATA
Frontal panel protection: IP65.
Casing: plastic body in resin type
PC+ABS UL94 V-0, inspection window in
polycarbonate, buttons in thermoplastic
resin.
Dimensions: frontal panel 74x32 mm,
depth 59 mm (without wirings).
Installation: on panel, with drilling tem-
plate 71x29 mm (+0.2/–0.1 mm).
Use temperature: –5…55 °C.
Storage temperature.: –30…85 °C.
Use environment humidity: 10…90 % RH
(not condensing).
Storage environment humidity: 10…90% RH
(not condensing).
Viewing range:
• Pt100 model : -150…650°C, with decimal
point, selectable through parameter ndt
• TcJ model -40…750°C*
• TcK model -40…1350°C*
*without decimal point
on 3 digit & 1/2+ mark display.
PLEASE NOTE: viewing is 1/10 °C for
model Pt100 and 1°C for models TcJ/TcK
Serial: TTL for connection to Copy Card.
Analogue input: one PT100 input or TcJ or
TcK depending on model.
Digital outputs: 2 SPST outputs on 8(3)A
1/2 hp 250Va, (for relay capabilities see
label on the instrument)
Measuring range: from -150 to 1350.
Accuracy:
• Pt100 model : 0,5% for all scale + 1 digit;
0,2% from -150 to 300°C.
• TcJ model: 0,4% for all scale + 1 digit;
• TcK model 0,5% for all scale + 1 digit;
0,3% from -40 to 800°C.
Resolution:
• Pt100 model: 0,1°C (0,1°F) within 199,9
°C, 1°C (1°F) over
• TcJ/TcK model 1°C (1°F).
Consumption
• model 230V: 3 VA max.
• model 12V: 1,5 VA max.
Power supply: 12 Va/c±10% or 230Va
±10% 50/60 Hz.
Warning: check the power supply specified
on the instrument label; for relay and
power supply capacities, contact the Sales
Office).
IC 912 Pt100/TcJ/TcK 2/4
On1
0
0
>0
>0
OF1
0
>0
0
>0
regulator output
OFF
OFF
ON
D.C.
PARAMETER
HC1
dF1
HS1
LS1
dn1
do1
di1
dE1
On1
OF1
LOC
PA1
ndt
CA1
dro
H00 (1) (!)
H10
rEL
tAb
UL
dL
Fr
(1)
PARAMETER VISIBLE ONLY INTcJ/TcK MODELS. Pt100 Model works only with Pt100 sensor (3 wires) while TcJ and TcK Models work also with Pt100 sensor
selectable by this parameter
* DEFAULT column: for parameters HC1, HS1, LS1, DF1, H00/10 the default depends don the model.
* VALUE column: to be filled manually, with customized settings (if different from the default value).
(!) WARNING!
• If one or more of these parameters highlighted with (!) are modified, teh controller must be switched off and switched on again to ensure correct operation.
• It is strongly recommended, anyway to switch off and switch on again the controller anytime parameters have been changed to prevent malfunctioning on configuration
and/or ongoing timings
3/4
DESCRIPTION
REGULATOR 1 (folder with “rE1” label)
Heat/Cool Mode. If set to H the generic regulator actuates for hot
operation. If set to C the generic regulator actuates for cold opera-
tion
diFferential. Relay 1 tripping differential. The regulator stops on
reaching the Setpoint value (as indicated by the adjustment
probe), and restarts at temperature value equal to the Setpoint 1
plus (o minus depending on HC1) the value of the differential.
see ON-OFF regulation diagram
Higher SEt. Maximum possible setpoint 1 value.
Lower SEt. Minimum possible setpoint 1 value.
REGULATOR 1 PROTECTIVE DEVICE (folder with “rE1” label)
Delay time in activating the regulator relay after switch-on of
instrument.
Delay after switch off. The indicated time must elapse between
switch-off of the regulator relay and the successive switch-on.
Delay between switch-ons. The indicated time must elapse
between two successive switch-ons of the regulator.
Delay before switch-off. The indicated time must elapse between
switch-off request and the switch-off of the regulator.
On time (regulator 1).
Regulator activation time in the event of faulty probe. If set to “1”
with OF1 at “0” the regulator is always on, while at OF1 >0 it
functions always in duty cycle mode. .see Duty Cycle Diagram
OFF time (regulator 1). Regulator in disabled state time in the
event of a faulty probe. If set to “1” with On1 at “0” the regulator
is always off, while at On1 >0 it functions always in duty cycle
mode. see Duty Cycle Diagram
DISPLAY (folder with “diS” label)
(keyboard) LOCk (set and keys). Keyboard locking. However, you
can enter parameter programming
modify them along with the status of this parameter in order to
allow keyboard locking. y = yes; n = no
PAssword 1. When enabled (value other than 0) it constitutes the
access key for level 1 parameters.
number display type. View with decimal point. y = yes; n = no
PLEASE NOTE: for modelsTcJ/TcK only n value.
CAlibration 1.Calibration 1. Positive or negative temperature value
added to the value read by probe 1,
display read-out. Select °C or °F for displaying the temperature
read by the probe. PLEASE NOTE: the switch between °C and °F
DO NOT modify setpoint, differential, etc. (for example
set=10°C become 10°F).
CONFIGURATION (folder with “CnF” label)
PLEASE NOTE: PARAMETER VISIBLE ONLY INTcJ/TcK MODELS
Probe type selection: Pt1 for Pt100; JtC: for TcJ; HtC for Tck
delay time in activating the outputs after switch-on WARNING! If
set = 0 it is not active; if set ≠0 output will not be activated before
this time
reLease firmware. Device version: read only parameter.
tAble of parameters. Reserved: read only parameter.
COPY CARD (folder with “Fpr”label)
Up load. Programming parameter transfer from instrument to
Copy Card.
Down load. Programming parameter transfer from Copy Card to
instrument
Format. Erasing all data in the Copy Card.
PLEASE NOTE using “Fr” parameter (copy card formatting)
the data within the copy card will be lost permenently. The
operation cannot be cancelled. After using the copy Card
device the controller must be switch off and switch on again
Tab. 1 Parameter Table
DEFAULT*
H/C*
0 (n.z. models)*
1*
*
*
1
0
0
0
0
1
n
0
n
0
°C
Pt1/JtC/HtC*
0
/
/
/
/
/
RANGE
H/C
0.0...30.0
LS1..HdL
LdL..HS1
0...250
0...250
0...250
0...250
0...250
0...250
n/y
0...250
n/y
-30.0...30.0
°C/°F
Pt1/JtC/HtC
0...250
/
/
/
/
/
VALUE* U.M.
flag
°C/°F
°C/°F
°C/°F
sec
min
min
sec
min
min
flag
num
flag
°C/°F
flag
num
min
/
/
/
/
/
IC 912 Pt100/TcJ/TcK
IC 912 Pt100/TcJ/TcK 4/4
Invensys Controls Italy s.r.l
via dell'Industria, 15 Zona Industriale Paludi
32010 Pieve d'Alpago (BL) ITALY
Telephone +39 0437 986111
Facsimile +39 0437 989066
Internet http:/www.climate-eu.invensys.com
12/2002 eng
cod. 9IS22093
IC 912 Pt100-TC - 12 V A
6 7 10 11 12
+-
1 2 3
IC 912 Pt100-TC - 230 V A
10 11
+-
12
6 7
1 2 3
WIRING
1 - 2 N.O. regulator 1 relay output (OUT1)
1 - 3 N.C. regulator 1 relay output (OUT1)
6 - 7 Power supply 1,5 VA max. (12V version)
Power supply 3 VA max. (230V version)
*10-11-12 Pt100 3 wires input
*11-12 TcJ/TcK input (11 = +; 12 = -)
A TTL input for Copy Card
PLEASE NOTE:
* depending on model
• User Default Settings
• for relay capacities check on the instrument label
In the diagram it is shown relays with 8(3) 1/2 hp 250V
capability
Wiring diagram
SP1
SP1-dF1
dF1
Off
On
HC1=H
ON-OFF Regulation Diagram
OF1
Off
On
OUT
On1 On1
parameters On1 ed OF1 programmed for
the duty cycle
When the analogue input
detects an error condition:
• the code E1 is displayed
• the regulator is activated as
indicated by the "On1)" and
"OF1" parameters if pro-
grammed for the duty cycle
Duty Cycle Diagram
On1
0
0
>0
>0
OF1
0
>0
0
>0
regulator output
OFF
OFF
ON
D.C.
DISCLAIMER
This manual and its contents remain the sole property of Invensys Controls Italy
s.r.l., and shall not be reproduced or distributed without authorization. Although
great care has been exercised in the preparation of this document, Invensys
Controls Italy s.r.l., its employees or its vendors, cannot accept any liability whatso-
ever connected with its use. Invensys Controls Italy s.r.l. reserves the right to make
any changes or improvements without prior notice.

Other Eliwell Controllers manuals

Eliwell EWDB 111 User manual

Eliwell

Eliwell EWDB 111 User manual

Eliwell ICPlus 915 User manual

Eliwell

Eliwell ICPlus 915 User manual

Eliwell IC 912 User manual

Eliwell

Eliwell IC 912 User manual

Eliwell IWP 760 LX User manual

Eliwell

Eliwell IWP 760 LX User manual

Eliwell ID 970 User manual

Eliwell

Eliwell ID 970 User manual

Eliwell EWRC 300 NT Series User manual

Eliwell

Eliwell EWRC 300 NT Series User manual

Eliwell EWPlus 902 User manual

Eliwell

Eliwell EWPlus 902 User manual

Eliwell EW 4800 User manual

Eliwell

Eliwell EW 4800 User manual

Eliwell IC 912 Series User manual

Eliwell

Eliwell IC 912 Series User manual

Eliwell Televis EWCM 809/NH3/S User manual

Eliwell

Eliwell Televis EWCM 809/NH3/S User manual

Eliwell IC 912 LX Pt100 R User manual

Eliwell

Eliwell IC 912 LX Pt100 R User manual

Eliwell IC 915 NTC/PTC User manual

Eliwell

Eliwell IC 915 NTC/PTC User manual

Eliwell IDplus 902 User manual

Eliwell

Eliwell IDplus 902 User manual

Eliwell EWCM 8900 User manual

Eliwell

Eliwell EWCM 8900 User manual

Eliwell EWHT 1800LX User manual

Eliwell

Eliwell EWHT 1800LX User manual

Eliwell EWCM 4120 User manual

Eliwell

Eliwell EWCM 4120 User manual

Eliwell EWRC 500 NT Series User manual

Eliwell

Eliwell EWRC 500 NT Series User manual

Eliwell EWPC 961/S User manual

Eliwell

Eliwell EWPC 961/S User manual

Eliwell IDplus 961 User manual

Eliwell

Eliwell IDplus 961 User manual

Eliwell ID 985 User manual

Eliwell

Eliwell ID 985 User manual

Eliwell ECH 200BD "Adaptive" User manual

Eliwell

Eliwell ECH 200BD "Adaptive" User manual

Eliwell EWDR 983/CS User manual

Eliwell

Eliwell EWDR 983/CS User manual

Eliwell ID 985 User manual

Eliwell

Eliwell ID 985 User manual

Eliwell IC 915 NTC/PTC User manual

Eliwell

Eliwell IC 915 NTC/PTC User manual

Popular Controllers manuals by other brands

Bosch AVENAR panel 8000 manual

Bosch

Bosch AVENAR panel 8000 manual

Omron R88M-1M Series user manual

Omron

Omron R88M-1M Series user manual

Tekmar D 650 Data brochure

Tekmar

Tekmar D 650 Data brochure

EVA Logik ZW37 manual

EVA Logik

EVA Logik ZW37 manual

Ltech LT-3600RF manual

Ltech

Ltech LT-3600RF manual

Blue Robotics Thruster Commander quick start guide

Blue Robotics

Blue Robotics Thruster Commander quick start guide

GIESSE ST450 instructions

GIESSE

GIESSE ST450 instructions

Unitronics Vision OPLC V130-33-T38 installation guide

Unitronics

Unitronics Vision OPLC V130-33-T38 installation guide

Numark MIXTRACK3 Service manual

Numark

Numark MIXTRACK3 Service manual

QED Micropurge MP10 instruction manual

QED

QED Micropurge MP10 instruction manual

LOVATO ELECTRIC FFL700EP instruction manual

LOVATO ELECTRIC

LOVATO ELECTRIC FFL700EP instruction manual

Chemtrol PC6000 instruction manual

Chemtrol

Chemtrol PC6000 instruction manual

Sunricher SR-ZV9003T3-RGBW-US Installation

Sunricher

Sunricher SR-ZV9003T3-RGBW-US Installation

SIGMA TEK SR 011 Technical manual

SIGMA TEK

SIGMA TEK SR 011 Technical manual

DeVilbiss HGB Service bulletin

DeVilbiss

DeVilbiss HGB Service bulletin

Fuelab 72001 Operating and installation instructions

Fuelab

Fuelab 72001 Operating and installation instructions

Doms PSS 5000 Technical manual

Doms

Doms PSS 5000 Technical manual

Carel Easy PJEZS Series Guide

Carel

Carel Easy PJEZS Series Guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.