Gemu SideStep Profibus DP User manual

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
1/42
GEMÜ SideStep®Motorized Actuator
Industrial OPEN/CLOSE Profibus DP
Status 06.04.09
from version 1.0.6.0
GB OPERATING INSTRUCTIONS

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
2/42
CONTENTS
1. TECHNICAL DATA - GEMÜ SIDESTEP PROFIBUS DP 3
2. ELECTRICAL CONNECTIONS 3
2.1. GEMÜ SideStep industrial OPEN/CLOSE Profibus DP 3
2.2. RS-485 4
2.3. Profibus DP status LED 4
2.4. Supply voltage 4
2.4.1. 24V DC supply voltage 4
2.4.2. 120V 50/60Hz or 230V 50/60Hz supply voltage 4
3. WIRING IN THE PROFIBUS SYSTEM 5
4. SERIAL WIRING IN THE BUS SYSTEM 5
5. BUS WIRING VIA STUB 6
6. DIFFERENT CONFIGURATION MENU 6
7. CYCLIC PROFIBUS DATA 7
7.1. Set value and digital input 7
7.2. Valve position 7
7.3. Digital output 7
7.4. Parameter data: Parameters / Actions / Errors 8
7.4.1. No action 8
7.4.2. Change parameters 8
7.4.3. Request parameters 9
7.4.4. Read error list 10
7.4.5. Amount of active errors and readout of the active error 11
7.4.6. Amount of active warnings and readout of the actice warnings 12
7.4.7. Trigger action in the SideStep 12
7.4.8. Quit TravelTimeError 13
7.4.9. Quit Field bus Event 13
7.4.10. NoInit 14
7.4.11. Clear Error List 15
7.4.12 Set Default 15
7.4.13. Init valve 16
7.4.14. GoClose 16
7.4.15. GoOpen 17
8. EXTERNAL DIAGNOSTIC ERRORS 18
9. PARAMETER NUMBERS 19
10. CONFIGURATION EXAMPLE USING SIEMENS S7 23

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
3/42
1. Technical Data - GEMÜ SideStep Profibus-DP
Protocol flow
GSD data file G9ASSind.GSD
PNO-ID 0x2079
Baud rate 9.6 baud
19.2 baud
93.75 baud
187.5 baud
500 baud
1.5 Mbaud
3 Mbaud
6 Mbaud
12 Mbaud
Profibus address 26
(Default setting)
2. Electrical connections
2.1. GEMÜ SideStep industrial OPEN/CLOSE Profibus DP
Connection Pin Signal name
X1 1 Uv, L1 / L+ supply voltage
Connector plug 2 Uv, N / L- supply voltage
3 n.c.
4 n.c.
5 n.c.
6 n.c.
PE conductor
Connection Pin Signal name
X3 1 n.c.
M12 plug 2 RxD/TxD-N
B coding 3 n.c.
PB in 4 RxD/TxD-P
5 Shield
Connection Pin Signal name
X4 1 BUS-VDC, +5V DC
M12 socket 2 RxD/TxD-N
B coding 3 DGNG
PB out 4 RxD/TxD-P
5 Shield

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
4/42
2.2. RS-485
2.3. Profibus DP status LED
Profibus DP status LED
Red light – no bus connection
No light – bus connection ok
No function at Profibus DP design
2.4. Supply voltage
2.4.1. 24V DC supply voltage
Plug Pin Signal name Wiring
internal external
X1 1 Uv, L+ supply voltage 24V DC power
supply
X1 2 Uv, L- supply voltage
2.4.2. 120V 50/60Hz or 230V 50/60Hz supply voltage
Plug Pin Signal name Wiring
internal external
X1 1 Uv, L1 supply voltage AC power
supply
X1 2 Uv, N supply voltage
RxD/TxD-N
VP +5
DGND
RxD/TxD-P
1234
5
6789
~

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
5/42
3. Wiring in the Profibus system
4. Serial wiring in the bus system
With a transmission rate ≥1.5 Mbaud.
390
Ω
390
Ω
220
Ω
390
Ω
390
Ω
220
Ω
VP +5
DGND
VP +5
DGND
Shield
Protection
ground
Protection
ground
Slave
With transmission rates
≥1.5 Mbaud no wiring with
drop cables
Profibus
terminating
resisto
r

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
6/42
5. Bus wiring via drop cable
With a transmission rate ≤1.5Mbaud.
6. Different configuration menu
The GEMÜ SideStep with Profibus DP has the following expanded configuration menu
compared to the standard SideStep:
DP Adr
Determines the Profibus address of the actuator.
PwrOnT.Out
Defines the time between error recognition and message when the actuator is switched
on.
Profibus
terminating
resisto
r
Service
1SetBasics
2 SetFunction
3SetCalibration
4Return
6
SETUP
Communication
5
Fieldbus
5.2
IR-Port
5.1
DP adrr 26 Return
PwrOnT.Out

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
7/42
7. Cyclic Profibus data
Input data: (Profibus ÅSideStep)
Addr. 0 Addr. 2 Addr. 3
2 bytes 1 byte 8 bytes
Valve position Dig. Out Parameters / Actions / Errors (see page 9)
Output data: (Profibus ÆSideStep)
Addr. 0 Addr. 1
1 byte 8 bytes
Set value and digital input Parameters / Actions / Errors (see page 9)
7.1. Set value and digital input
Profibus ÆSideStep
Set value Digital Input bit 7 6 5 4 3 2 1 0
1 byte Stop valve X X 0 0
Open valve X X 0 1
Close valve X X 1 0
Valve moves to X X 1 1
position Pref Dir
Digital input 1 0 1 X X
Digital input 2 1 0 X X
Digital input 1 + 2 1 1 X X
7.2. Valve position
Profibus ÅSideStep
0..1000
Valve position
2 bytes
7.3. Digital Output
Profibus ÅSideStep
Digital Output bit 7 6 5 4 3 2 1 0
1 byte Digital output 1 0 1
Digital output 2 1 0
Digital output 1 + 2 1 1

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
8/42
7.4. Parameter data: Parameters / Actions / Errors
SideStep ÅÆProfibus
Parameters / Actions / Errors:
Toggle Para
code
Para
ID
Para
value
1
byte
1
byte
2
bytes
4
bytes
8 bytes
If the same information is sent more than once, the data record needs to be changed via
the toggle byte.
7.4.1. No action
When using the “N” (NOP) instruction, no action is carried out. The response is another
NOP instruction.
Inquiry from the master:
0xYY 0x4E (“N“) 0x00, 0x00 0x00, 0x00, 0x00, 0x00
1 byte 1 byte 2 bytes 4 bytes
Response of the SideStep:
0xYY 0x4E (“N“) 0x00, 0x00 0x00, 0x00, 0x00, 0x00
1 byte 1 byte 2 bytes 4 bytes
7.4.2. Change parameters
The “S“ (SET) instruction enables the change of a parameter in the SideStep via the
Profibus. As a response, the SideStep returns the SET instruction with the changed
parameter value. If the value is higher than the valid range, an external diagnostic error
with code 0x21 is generated; if below, the error generated has code 0x20.
Where the parameter does not exist, the diagnostic error triggered has code 0x22, and the
value returned is 0.
In case of a parameter change, the new value of the parameter is returned to the master
together with a SET instruction.
Where the parameter does not exist, the value returned is 0.

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
9/42
Inquiry from the master:
0xYY 0x53 (“S“) ID Value of the parameter
1 byte 1 byte 2 bytes 4 bytes
Response of the SideStep:
0xYY 0x53 (“S“) ID Value of the parameter
1 byte 1 byte 2 bytes 4 bytes
The individual parameters of the GEMÜ SideStep are on page 19.
Ex: The Mode parameter needs to be changed to Manual.
0xYY 0x53 (“S“) ID Value of the parameter
Mode Manual
0xYY 0x53 0x64 0x00, 0x00, 0x00, 0x02
7.4.3. Request parameters
The “G“ (GET) instruction is used to request from the SideStep the value of a parameter
via the Profibus. The SideStep responds with a GET instruction containing the parameter
value.
Where the parameter does not exist, an external diagnostic error with code 0x22 is
triggered.
Inquiry from the master:
0xYY 0x47 (“G“) ID2 0x00 0x00 0x00 0x00
1 byte 1 byte 2 bytes 4 bytes
Response of the SideStep:
0xYY 0x47 (“G“) ID Value of the parameter
1 byte 1 byte 2 bytes 4 bytes
When the parameter value in the GEMÜ SideStep changes, it is
immediately sent to the Profibus master. There is no need to
continuously request the parameter.

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
10/42
7.4.4. Read error list
The error list is requested using the “E“ (Error List) instruction.
Inquiry from the master:
0xYY 0x45 (“E“) Serial num-
ber of error
in the list
0x00, 0x00, 0x00, 0x00
1 byte 1 byte 2 bytes 4 bytes
The first error is requested with 0x00 0x00
Response of the SideStep:
0xYY 0x45 (“E“) Serial num-
ber of error
in the list
Error information
1 byte 1 byte 2 bytes 4 bytes
Attention:
•When a new error occurs, the serial numbering of the listed errors changes.
Error 0 then becomes Error 1, Error 1 becomes Error 2, etc.
•Once the error list is full, the oldest error in the list is deleted.
•If no entry on the required number is found in the error list, an external
diagnostic error with code 0x34 is triggered. In this case the response value
is 0xFF 0xFF 0xFF 0xFF
•With number 0 the current error can be monitored
•If there is no error in the error list, error 0x00 0x00 0x00 0x00 is displayed

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
11/42
7.4.5. Amount of active errors and readout of the active error
The “D“ instruction is used to request the amount of active errors and the active error
selected using the ID.
Inquiry from the master:
0xYY 0x44 (“D“) Number of
active error
0x00, 0x00, 0x00, 0x00
1 byte 1 byte 2 bytes 4 bytes
The first error is requested with 0x00 0x01.
Response of the SideStep:
0xYY 0x44 (“D“) Number of
active error
Amount of
active errors
Value of active
error (selected
via ID)
1 byte 1 byte 2 bytes 4 bytes
Example:
The SideStep motor does not move during the time shown in the "TravelTime" parameter.
Error "022: TRAVEL T ERR" is triggered, the error is active.
Inquiry from the master:
0x00 0x44 0x00, 0x00 0x00, 0x00, 0x00, 0x00
Response of the SideStep:
0x00 0x44 0x00, 0x00 0x00, 0x01, 0x00, 0x15
Example:
An error with error number (ID) 0x15 or 21dec is active.
Error list
Error name Parameter
ID
Hex
Parameter
ID
Dec
Description
NO ERROR 0x00 0x00 0 There are no errors
POWER FAIL 0x00 0x14 20 Power supply failure (only with optional emergency power
supply module)
TRAVEL T ERR 0x00 0x15 21 Potentiometer error during normal operation
Bus Fault 0x00 0x28 40 Bus fault was recognized

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
12/42
7.4.6. Amount of active warnings and readout of the active warning
The "W" instruction advises the Profibus of the amount of active warnings. It functions
analogous to the "D" instruction (readout active error messages) but refers to warnings
rather than error messages.
Inquiry from the master:
0xYY 0x57 („W“) Number of
active
warning
0x00, 0x00, 0x00, 0x00
1 byte 1 byte 2 bytes 4 bytes
7.4.7. Trigger action in the SideStep
The ”A“ (Action) instruction is used to trigger an action in the SideStep. Depending on the
action to be triggered, additional parameters may be required.
As long as an action is active, no other action may be triggered. Where this is attempted,
the SideStep will ignore the new action and generate an external diagnostic error with
code 0x40.
Inquiry from the master:
0xYY 0x41 (“A“) ID Parameter
1 byte 1 byte 2 bytes 4 bytes
Only one action may be active at a time. If no action is active, the Side-
Step responds as described in the individual actions.
If an action is active, the field bus will create the following response:
Response of the SideStep:
0xYY 0x41 (“A“) ID 0xFF Source Number
1 byte 1 byte 2 bytes 1 byte 1 byte 2 bytes
Source:
Active action was started via the GEMÜ SideStep keypad.
ÎAcknowledge (quit) at the GEMÜ SideStep
0x01
Active action was started via the e.sy-com interface of the GEMÜ
SideStep.
ÎClose active browser window
0x02
Active action was started via the field bus.
ÎQuit with instruction "Q" or
ÎSelect action again and quit
0x03

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
13/42
7.4.8. Quit TravelTimeError
Quit TravelTimeError is used to acknowledge a "TravelTimeError" that has occurred.
Instruction from the master
0xYY 0x41 0x00, 0x07 Function
1 byte 1 byte 2 bytes 4 bytes
Function:
Acknowledge TravelTimeError 0x00,0x00,0x00,0x01
Response of the SideStep:
0xYY 0x41 0x00, 0x07 Status
1 byte 1 byte 2 bytes 4 bytes
Status:
TravelTimeError acknowledged 0x00,0x00,0x00,0x01
TravelTimeError not acknowledged 0x00, 0x00, 0x00, 0x02
7.4.9. Quit field bus event
The instruction "Q" (Quit) is used to stop an active event.
This event acknowledges all active events activated via the field bus.
Instruction from the master:
0xYY 0x51 („Q“) 0x00 0x00 0x00 0x00 0x00 0x00
1 byte 1 Byte 2 bytes 4 bytes
Response of the SideStep:
0xYY 0x51 („Q“) 0x00 0x00 0x00 0x00 0x00 0x00
1 byte 1 byte 2 byte 4 bytes

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
14/42
7.4.10. NoInit
With “NoInit“, the actuator can be opened and closed manually if not yet initialised.
Where this action is activated once the SideStep has been initialised, the SideStep will
generate an external diagnostic error with code 0x42.
Instruction from the master:
0xYY 0x41 (“A“) 0x00, 0x01 Function
1 byte 1 byte 2 bytes 4 bytes
Function:
Stop valve 0x00, 0x00, 0x00, 0x00
Open slowly 0x01, 0x00, 0x00, 0x00
Open quickly 0x02, 0x00, 0x00, 0x00
Close slowly 0x03, 0x00, 0x00, 0x00
Close quickly 0x04, 0x00, 0x00, 0x00
Open with PWM [0..1000] 0x05, 0x00, PWM High, PWM Low
Close with PWM [0..1000] 0x06, 0x00, PWM High, PWM Low
End event 0x07, 0x00, 0x00, 0x00
The status reported is the current valve function selected.
Response of the SideStep:
0xYY 0x41 (“A“) 0x00, 0x01 Status
1 byte 1 byte 2 bytes 4 bytes
Status:
Stop valve 0x00, 0x00, 0x00, 0x00
Open slowly 0x01, 0x00, 0x00, 0x00
Open quickly 0x02, 0x00, 0x00, 0x00
Close slowly 0x03, 0x00, 0x00, 0x00
Close quickly 0x04, 0x00, 0x00, 0x00
Open with PWM [0..1000] 0x05, 0x00, PWM High, PWM Low
Close with PWM [0..1000] 0x06, 0x00, PWM High, PWM Low
End event 0x07, 0x00, 0x00, 0x00

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
15/42
7.4.11. Clear Error List
This action clears the entries from the error list.
Instruction from the master:
0xYY 0x41 (“A“) 0x00, 0x02 0x00, 0x00, 0x00, 0x00
1 byte 1 byte 2 bytes 4 bytes
Response of the SideStep:
0xYY 0x41 (“A“) 0x00, 0x02 Status
1byte 1 byte 2 bytes 4 bytes
Status:
Error list cleared (action is ended) 0x00, 0x00, 0x00, 0x01
Error list not cleared (action remains active) 0x00, 0x00, 0x00, 0x02
7.4.12. Set Default
This action sets the SideStep to the default state.
Instruction from the master:
0xYY 0x41 (“A“) 0x00, 0x03 0x00, 0x00, 0x00, 0x00
1 byte 1 byte 2 bytes 4 bytes
Response of the SideStep:
0xYY 0x41 (“A“) 0x00, 0x03 Status
1 byte 1 byte 2 bytes 4 bytes
Status:
Default setting loaded (action is ended) 0x00, 0x00, 0x00, 0x01
Default setting not loaded (action remains active) 0x00, 0x00, 0x00, 0x02

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
16/42
7.4.13. Init valve
This action initialises the valve. The SideStep here determines the open and closed
position.
Instruction from the master:
0xYY 0x41 (“A“) 0x00, 0x04 Function
1 byte 1 byte 2 bytes 4 bytes
Function:
Start initialisation 0x00, 0x00, 0x00, 0x01
Cancel initialisation 0x00, 0x00, 0x00, 0x02
Response of the SideStep:
0xYY 0x41 (“A“) 0x00, 0x04 Status
1 byte 1 byte 2 bytes 4 bytes
In the status, the SideStep reports the action currently taken.
Status:
Initialisation inactive 0x00, 0x00, 0x00, 0x00
Closed position determined 0x00, 0x00, 0x00, 0x01
Open position determined 0x00, 0x00, 0x00, 0x02
7.4.14. GoClose
The motor moves the valve to the closed position. Once the valve is in the required
position, this needs to be communicated to the SideStep. This then takes the position as
"closed".
Instruction from the master:
0xYY 0x41 (“A“) 0x00, 0x05 Function
1 byte 1 byte 2 bytes 4 bytes
Function
Go to closed position 0x00,0x00,0x00,0x01
In closed position 0x00,0x00,0x00,0x02
Cancel Close function (ESC) 0x00,0x00,0x00,0x03
Response of the SideStep:
0xYY 0x41 (“A“) 0x00, 0x05 Status
1 byte 1 byte 2 bytes 4 bytes
Status:
Go to closed position 0x00,0x00,0x00,0x01
In closed position 0x00,0x00,0x00,0x02
Close function cancelled 0x00,0x00,0x00,0x03

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
17/42
7.4.15. GoOpen
The motor moves the valve to the open position. Once the valve is in the required
position, this needs to be communicated to the SideStep. This then takes the position as
"open".
.
Instruction from the master:
0xYY 0x41 (“A“) 0x00, 0x06 Function
1 byte 1 byte 2 bytes 4 bytes
Function:
Go to open position 0x00,0x00,0x00,0x01
In open position 0x00,0x00,0x00,0x02
Cancel Open function (ESC) 0x00,0x00,0x00,0x03
Response of the SideStep:
0xYY 0x41 (“A“) 0x00, 0x06 Status
1 byte 1 byte 2 bytes 4 bytes
Status:
Go to open position 0x00,0x00,0x00,0x01
In open position 0x00,0x00,0x00,0x02
Open function cancelled 0x00,0x00,0x00,0x03

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
18/42
8. External diagnostic errors
Defined error messages:
Error ID Error
0x01 Data length service data from master to slave incorrect
0x02 Data length service data from slave to master incorrect
0x20 Specified parameter value too low
0x21 Specified parameter value too high
0x22 Parameter does not exist
0x30 Error in SideStep
0x31 Error in SideStep acknowledged
0x32 Warning in SideStep
0x33 Warning in SideStep acknowledged
0x34 No error list entry on the requested number available
0x40 Event active in SideStep, therefore no new event possible.
0x41 Active action cannot be affected by Profibus
0x42 NoInit not available
0x43 Event doesn´t exist

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
19/42
9. Parameter numbers
Parameter Parameter
ID
Hex
Parameter
ID
Dec
Access Value range
Mode 0x64 100 Write 0: OFF
1: Auto
2: Manual
SETUP
Service
I/O Status
ActiveParaSet 03E8 1000 Read 0: P1
1: P2
2: P3
3: P4
Pot Min 03E9 1001 Read [0..1000] *0.1 %
Pot Max 03EA 1002 Read [0..1000] *0.1 %
Pos W 03ED 1005 Read [0..1000] *0.1 %
Pos X 03EE 1006 Read [0..1000] *0.1 %
Pot Abs 03EF 1007 Read [0..1000] *0.1 %
Pos Ctrl Out 03F0 1008 Read [-1000..1000] *0.1 %
Diagnosis
Operating hour 044C 1100 Read [0..99 999] h
Operating minute 044D 1101 Read [0..59] min
Operating second 044E 1102 Read [0..59] s
Warnings 044F 1103 Write 0: ON
1: OFF
Errors 0450 1104 Write 0: ON
1: OFF
SetBasics
D.Refresh 07D1 2001 Write [1..10] *0.1s
Dlight 07D2 2002 Write 0: ON
1: ON Key
AutoReturn 07D3 2003 Write [1..60] min
HelpLanguage 07D4 2004 Write 0: D
1: GB
Helptext 07D5 2005 Write 0: ON
1: OFF
PwrOnMode 07DF 2015 Write 0 : fast
1 : safe

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
20/42
Parameter Parameter
ID
Hex
Parameter
ID
Dec
Access Value range
SetBasics
Speed Adj
StartSpOpen 07D7 2007 Write [0..1000] *0.1 %
StartSpClose 07D8 2008 Write [0..1000] *0.1 %
StopSpOpen 07D9 2009 Write [0..1000,-1] *0.1 %
StopSpClose 07DA 2010 Write [0..1000,-1] *0.1 %
Force ADj
InitFOpen 07DB 2011 Write [0..550] *0.1 %
InitFClose 07DC 2012 Write [0..550] *0.1 %
ForceOpen 07DD 2013 Write [0..550] *0.1 %
ForceClose 07DE 2014 Write [0..550] *0.1 %
SetFunction
PrefDir 0BB8 3000 Write 0: Close
1: Open
2: Hold
DeadBand 0BB9 3001 Write [1..250] *0.1%
PwFailDir ** 0BBA 3002 Write 0: Close
1: Open
2: Hold
CpyParaSet 0BBB 3003 Write 0: OFF
1: P1<=W
2: P1=>P2
3: P1<=P2
4: P1=>P3
5: P1<=P3
6: P1=>P4
7: P1<=P4
PosCtrl
Pos P 0C80 3200 Write [0..1000] *0.1
Pos D 0C81 3201 Write [0..1000] *0.1
Pos T 0C82 3202 Write [1..5000] ms
MinPos 0C83 3203 Write [0..1000] *0.1 %
MaxPos 0C84 3204 Write [0..1000] *0.1 %
closeTight 0C85 3205 Write [0..200] *0.1 %
openTight 0C86 3206 Write [800..1000] *0.1 %
TightTime 0C87 3207 Write [0..1200] *0.1 s
** only available with emergency power supply module version
This manual suits for next models
2
Table of contents
Other Gemu Controllers manuals
Popular Controllers manuals by other brands

Contro l4
Contro l4 HC-250 quick start guide

Welbilt
Welbilt Frymaster YUM WINGSTREET K3000 Operation manual

Unibright
Unibright DMX1RGBW instructions

NovaStar
NovaStar CX40 Pro user manual

Smart system
Smart system DIGIDRIVE BASIC Quick reference guide

Oriental motor
Oriental motor DGII Series operating manual