Elk Products ELK-M1G Assembly instructions

INSTALLATION
MANUAL
Cross Platform Control
Specifications, Installation and Programming
M1 includes the SIA CP-01 Standards for False Alarm Reduction †
TM
L520 Rev. K 10/4/13 Current with Firmware 5.3.0

M1G Installation and Programming
Page 2
Introduction
LIMITATION
The ELK-M1G Control is designed to warn against unauthorized entry and other situations. However, it is not a guarantee of protection against
the occurrence of burglary, fire, or other emergency. Any alarm system is subject to compromise or failure to warn for various reasons. For
example:
- Unauthorized access can be gained through unprotected points or by disarming or bypassing protected points.
- Sensing devices are power driven and do not operate without electrical power. Battery-operated devices will not work without batteries, with
dead batteries, or if the batteries are not put in properly. Devices powered solely by AC will not work if their AC power supply is cut off for any
reason, however briefly.
- Telephone lines over which alarm signals are transmitted may be out of service or rendered inoperable by an intruder.
- Even if the system responds to the emergency as intended, occupants may have insufficient time to protect themselves from the emergency
situation. In the case of a monitored alarm system, authorities may not respond appropriately.
- Smoke detectors have limitations and cannot detect all types of fires. According to data published by the Federal Emergency Management
Agency, while smoke detectors have played a key role in reducing residential fire deaths in the United States, they may not activate or provide
early warning for a variety of reasons in as many as 35% of all fires, . Some of the reasons some detectors used in conjunction with this
System may not work are as follows. Smoke detectors may have been improperly installed and positioned. Smoke detectors may not sense
fires that start where smoke cannot reach the detectors, such as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level of a residence or building. A second floor detector, for example, may not sense a first floor
or basement fire. Finally, smoke detectors have sensing limitations. No smoke detector can sense every kind of fire every time. In general,
detectors may not always warn about fires caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas,
improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson. Depending an the nature of the
fire, and/or location of the smoke detectors, the detector, even if it operates as anticipated, may not provide sufficient warning to allow all
occupants to escape in time to prevent injury or death..
- Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarm receiver. Even if the signal path
has been recently checked during a weekly test, blockage can occur if a metal object is moved into the path.
- Wireless transmitters (used in some systems) are designed to provide long battery life under normal operating conditions. Longevity of
batteries may be as much as 4 to 7 years, depending on the environment, usage, and the specific wireless device being used. External
factors such as humidity, high or low temperatures, as well as large swings in temperature, may all reduce the actual battery life in a given
installation. This wireless system, however, can identify a true low battery situation, thus allowing time to arrange a change of battery to
maintain protection for that given point within the system.
- Installing an alarm system may make the owner eligible for a lower insurance rate, but an alarm system is not a substitute for insurance.
Homeowner, property owners and renters should continue to act prudently in protecting themselves and continue to insure their lives and
property.
- A user may not be able to reach a panic or emergency button quickly enough.
- Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their installation manual. Passive
Infrared Detectors do not provide volumetric area protection. They do create multiple beams of protection, and intrusion can only be detected
in unobstructed areas covered by those beams. They cannot detect motion or intrusion that takes place behind walls, ceilings, floors, closed
doors, glass partitions, glass doors, or windows. Mechanical tampering, masking, painting or spraying of any material on the mirrors, windows
or any part of the optical system can reduce their detection ability. Passive Infrared Detectors sense changes in temperature; however, as the
ambient temperature of the protected area approaches the temperature range of 90 to 105F (32 to 40C), the detection performance can
decrease.
- Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located on the other side of
closed or partly open doors. If warning devices are located on a different level of the residence from the bedrooms, they are less likely to
waken or alert people inside the bedrooms. Even persons who are awake may not hear the warning if the alarm is muffled by noise from a
stereo, radio, air conditioner or other appliance, or by passing traffic. Finally, alarm warning devices, however loud, may not warn hearing-
impaired people.
- This equipment, like other electrical devices, is subject to component failure. Even though this equipment is designed to last as long as 20
years, the electronic components could fail at any time.
- The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This alarm
system should be tested weekly to make sure all sensors and transmitters are working properly.
ALL RIGHTS RESERVED
No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by any means, electronic, mechanical,
photocopying, recording, or otherwise without the prior written permission of the manufacturer. The material in this publication is for information
purposes and subject to change without notice. The manufacturer assumes no responsibility for any errors which may appear in this publication.
Printed in U.S.A.
Use of this control for fire detection and/or annunciation may not be permitted by certain states, counties, municipalities or local jurisdiction. It is
the responsibility of the installing alarm company to check with the local A.H.J. (Authority Having Jurisdiction) or State Fire Marshal’s office prior
to using this control for fire detection.

M1G Installation and Programming Page 3
Table of Contents
Specifications, Features, and Benefits ..................................................................................................... 5
Wiring & Hookup Diagram ........................................................................................................................... 6
Section 1 - Installation and Wiring ............................................................................................................. 8
1.1 Planning the Installation ...................................................................................................................... 8
1.2 Parts Diagram & Descriptions ........................................................................................................... 8
1.3 Mounting and Wiring Preparation ....................................................................................................... 8
1.4 Control Wiring .................................................................................................................................... 9
Data Bus E.O.L. Termination - VERY IMPORTANT! .............................................................................. 12
Section 2 - Operating the System ............................................................................................................ 14
2.1 Introduction ....................................................................................................................................... 14
2.2 Powering Up (One Keypad) ............................................................................................................. 14
2.3 User Codes and Authorities .............................................................................................................. 14
2.4 Installer Program Code and Authorities ............................................................................................ 14
2.5 Keypad Overview ............................................................................................................................. 15
Keypad Menus ........................................................................................................................................ 16
Menu 0 - Select Keypad Alternate Area - Multi-area (Partition) Operation .............................................. 20
Section 3 - Programming The Control ..................................................................................................... 21
3.1 Introduction ....................................................................................................................................... 21
3.2 Local Keypad Programming ............................................................................................................. 21
3.3 Local or Remote Computer Programming (ELK-RP) and Anti-Takeover ......................................... 21
3.4 Area Partitioning ................................................................................................................................ 21
3.5 Communicator Setup Checklist ....................................................................................................... 22
3.6 Entering Installer Level Programming ............................................................................................... 22
Menu 01 - Bus Module Enrollment .......................................................................................................... 24
Menu 02 - User Code Options ................................................................................................................ 25
Menu 03 - Area Definitions ...................................................................................................................... 26
Menu 04 - Keypad Definitions ................................................................................................................. 28
Menu 05 - Zone Definitions ..................................................................................................................... 30
Menu 06 - Alarm Duration Timers ........................................................................................................... 33
Menu 07 - Global System Definitions ..................................................................................................... 34
Menu 08 - Telephone Account Setup ...................................................................................................... 38
Menu 09 - Area Reporting Codes ........................................................................................................... 40
Menu 10 - Zone Reporting Codes ........................................................................................................... 42
Menu 11 - Keypad F-Key Reporting Codes ............................................................................................ 43
Menu 12 - Sys Report Code Options & Codes ...................................................................................... 44
Menu 13 - User Report Codes................................................................................................................ 46
Menu 14 - Wireless Setup ...................................................................................................................... 47
Section 4 - PC Programming and Automation Capabilities .................................................................... 49
4.1 ELK-RP Software ............................................................................................................................ 49
4.2 Update/Verify Firmware in the Control and Peripherals ................................................................... 50
4.3 Automation Rules and Attributes ...................................................................................................... 51
Appendix A - Event Codes ........................................................................................................................ 58
Appendix B - Telephone Remote Control ............................................................................................... 60
Appendix C - Voice Message Vocabulary *RP only * ............................................................................. 62
Appendix D - Two Way “Listen-in/Talk” Interface................................................................................... 64
Appendix E - SIA CP-01 Compliance ........................................................................................................ 65
Appendix F - Regulatory Agency Statements .......................................................................................... 66
Appendix G - Additional ELK-M1KP Keypad Information ...................................................................... 69
Index ............................................................................................................................. 71

M1G Installation and Programming
Page 4
OUT3 On LED
J-16 Programmable Outputs
See Note 1
& Note 2
PLC ††
Lighting
Interface Conn.
J4
1 WAY (PL513/PSC04)
Select PLC Mode
2 WAY (TW523/PSC05)
JP2
RS232 CONN.
J5
Bell (Supervised)
Voice/Siren † †
Dry Contact Relay
rated 4A @
12 - 24VDC
See Note 2
OUT 1 OUT 3
N/C
COM
N/O
OUT 2
RED
BLACK
WHITE
GREEN
+VAUX
+12VDC Auxiliary Power
(3)
1.25 Amp PTC protected
Grey
Brown
Red
Green TELCO
LINE
HOUSE
PHONES
Z1
NEG
Z2
Z3
NEG
Z5
NEG
Z7
Z6
Z4
NEG
Z8
Z9
NEG
Z10
Z11
NEG
Z13
NEG
Z15
Z14
Z12
NEG
Z16
+SAUX
NEG
+VAUX
NEG
+VAUX
NEG
+VAUX
NEG
AC
16.5 V
AC
+VKP
DATA B
DATA A
NEG
OUT 16
OUT 15
OUT 14
OUT 13
OUT 12
OUT 11
OUT 10
OUT 9
OUT 8
OUT 7
+12V
NEG
T1
R1
RING
TIP
Serial Port ††
for Computer/ELKRP
See Manual
J3
B
A
-
C
+
Audio Network Interface ††
1
Keypad &
Data Bus
J2 J1
16 Zones expandable to 208
Do Not
Connect to
a Phone
Line!
Not Used -See Note 3
BATTERY
ON
SW1
+-
12V Battery
7 to 18 Ah
Keypad
Control specifications subject to change without
notice. All circuits are power limited except for
Battery leads.
Complies with FCC Part 68:
Reg. # US: 5K6AL03BELK-M1 REN: 0.3B
Use Standard Jack: USOC RJ-31X.
Serial Number located below on base.
Complies with part 15 of FCC rules.
This Class B digital apparatus complies with
Canadian ICES-003.
See Note 2
+SAUX
+12VDC Switched
Smoke Power
1.1 Amp PTC protected
NEG
DATA B
+12V
JP3
Jumper to start with
no AC - See Note 4.
Power
Status
Reverse
Bat Leads
UL Listed Transformer,
Class 2, 16.5VAC, 45VA
Do not connect to a
switched outlet.
ELK-TRG1640
NORMAL
ZONE 16
JP1 SMOKE
2WIRE
TELCO SEIZED
DIALER ACTIVE
1
N.C. N.O.
ZONE
2200
Ohm
EOL
2
N.C. N.O.
ZONE
2200
Ohm
EOL
3
N.C. N.O.
ZONE
2200
Ohm
EOL
4
N.C. N.O.
ZONE
2200
Ohm
EOL
5
N.C. N.O.
ZONE
2200
Ohm
EOL
6
N.C. N.O.
ZONE
2200
Ohm
EOL
7
N.C. N.O.
ZONE
2200
Ohm
EOL
8
N.C. N.O.
ZONE
2200
Ohm
EOL
9
N.C. N.O.
ZONE
2200
Ohm
EOL
10
N.C. N.O.
ZONE
2200
Ohm
EOL
11
N.C. N.O.
ZONE
2200
Ohm
EOL
12
N.C. N.O.
ZONE
2200
Ohm
EOL
13
N.C. N.O.
ZONE
2200
Ohm
EOL
14
N.C. N.O.
ZONE
2200
Ohm
EOL
15
N.C. N.O.
ZONE
2200
Ohm
EOL
16
N.C. N.O.
ZONE
2200
Ohm
EOL
2-Wire Smoke Detector - Zone 16 ONLY
4-Wire Smoke Detector - Any Zone
U.L. Listed EOL Supervision Relay, ESL #204A or equiv.
Use 2,200 Ohm EOL resistor, part # ELK-ER2200. Set
JP1 to 'Normal'.
DATA A
+
-
+
-See Note 2
Data Bus Terminating Resistor
See Note 1.
Data Bus
See Note 1
J7
1.25 Amp PTC
protected
08/13
ELK
PRODUCTS, INC.
HILDEBRAN, N.C., 28637, USA
1
1
Cross Platform Control
PSC05
††or
Equivalent
ELK-M1
StripStrip Wires to 1/4" Length
+
820
Ohm
EOL
-
NEG
Z16
2. OUT 1 †† for speaker(s) ONLY (4 to 8 Ohms).
If connecting more than 2, use series/parallel
wiring to avoid going below a 4 ohm total load.
OUT 2 Connect ONLY 1 UL Listed Bell or
Siren (self-contained). Current limited to 1 Amp.
Program Global Option 26 to Voltage. This
output supervised. Speaker(s) only permitted
for non-UL installations. Series/parallel wire to
avoid dropping below a 4 ohm total load.
OUT 3 NO/NC dry contact relay rated 4A.
OUT 7 through 16 are +12V switched positive
voltage outputs rated at 50mA max.
3. This terminal (formerly earth gnd) not used.
Do not connect any neg terminals to ground.
4. If AC fails, control will shut down if battery
drops below 10.2 Volts. To start the control with a
good battery and no AC, short the silver pads
momentarily. Replace Battery every 3-5 years.
Test regularly with ELK-BLT Battery Life Tester.
O - I - B A +
TM
† Not Evaluated by UL
†† Not for use in UL Listed Systems
HA008F
2200
Ohm
EOL
To Zone Input
N.O. Alarm Contacts
+
-
+
-
+SAUX
To Zone NEG
NEG
Aux Data Bus ††
Notes
1. Refer to Appendix F located in the Installation
Manual #L520 Rev. K for the UL limitations on
total continuous 'standby' current drain from
terminals +SAUX, +VAUX, +VKP, and J16.
To configure Zone 16 as a 2-wire smoke zone,
set Jumper JP1 to '2WIRE SMOKE' and use 820
Ohm EOL resistor, part # ELK-ER820
Use Only Compatible Detectors
Control Compatibility Identifier: M10001
Refer to the Wiring & Hookup Diagram in the
Installation Manual # L520 Rev. K for the 2-Wire
Smoke Detector Compatibility chart.
TEST SYSTEM WEEKLY

M1G Installation and Programming Page 5
General:
• Large zone capacity: 16 on-board zones expandable to 208
• Up to 144 of the expandable zones may be wireless using
the ELK-M1XRFTW Wireless Receiver
• Two Way Listen-in interface †
• Flash Memory - Allows field updates to firmware electronically
• RS-232 serial port to interface PCs and peripheral devices
• Time/Date stamped 512 event history log
• Menu driven, text keypad programming - no manual required!
• Voice announcement of alarms, zone descs, status, etc.
- 500+ Word/Phrase Vocabulary
- Link up to 6 words/phrases per announcement
- 10 custom recordable words/phrases
• 13 On-Board Outputs: 1 voice driver/siren, 1 siren driver/
voltage, 1 form “C” Relay, and 10 low current (50 mA) voltage
outputs
• Supports 4 wire (any zone) and 2 wire (zone 16) smoke
detectors
• Includes Fire alarm verification routine
• Can be partitioned into 8 areas and account numbers
• User Codes:199 (4 or 6 digit) with assignable authority levels
• Arm levels: Away, Stay, Stay Instant, Nite, Nite Instant, Vacation
• Plug-in terminal blocks make service and pre-wires a snap!
• Hardware "watchdog" and nonvolatile EEPROM memory
• Supervised phone line, alarm output, and aux. overcurrent
Communications
• True V.22 bis Modem for fast reliable upload/download
• Optional M1XEP Ethernet Interface †for user operation,
alarm reporting, programming, and more
• Built-in Phone Remote Control makes any phone a keypad
• Integrated Voice Dialer uses vocabulary or custom words
• Communicator formats: SIA, Contact ID, 4 + 2, and Pager
• Installer telephone (buttset) test feature
• Elk-RP PC programming software with conflict resolution to
easily highlight differences between control and PC
- Dial-up, ethernet, RS-232 port, or local house phone jack
- Automatic answering machine bypass
Keypad
• Backlit, Large Character LCD Display, 16 x 2 lines
• Built-in Temperature Sensor
• Optional Plug-in Prox Access reader (26 bit Weigand format)
• Menu navigation keys and 6 programmable function keys
• Plug-in connector, only 4 wires to the control
• 1 Zone input and 1 Output Programmable per Keypad
• Programmable display of time, date, & temperature
• Displays system diagnostics and settings.
• Maximum Keypads allowed: 16
Automation & Integration
• Create lifestyle enhancing comfort, convenience, and security
• Powerful “Whenever/And/Then” RULES Programming allows
almost any imaginable operation. No need to chain rules
together. Any single “Whenever” event can have one or more
ANDs and THENs (conditions and commands).
• Rules utilize easy to understand text based references
• Control lighting using RS-232 serial or 2-way Power Line
Control (PLC) Commands include On, Off, Dim, All On, All Off †
• Transmit and receive custom serial ASCII strings
• Read Temperature Sensors - Communicate with Thermostats
• Turn on Tasks, Lights, Outputs via Keypad or Telephone
•Sunset/Sunrise calculation and activation built-in
Power Supply
• Heavy duty - 2.5 Amp power supply
• Dynamic battery test
• Master power switch and Low battery disconnect
• PTC (fuseless) resettable overload protection
• Multiple auxiliary power terminals
Part Numbers and Accessories:
ELK-M1GCB M1G Gold Board Only (No Teminals Blocks)
ELK-M1GOLD M1G Gold - Control in 14” metal can
ELK-M1GK M1G Gold Kit - No Metal Can, for use with
structured wiring systems
ELK-M1SYS4 M1G Gold Kit - 14” metal can, Ctrl, Encl, Xfmr,
KP, 12V-8Ah, Spkr, RJset
ELK-M1KP Keypad, LCD,16 character x 2 line
ELK-M1KP2 Small LCD Keypad, 16 character x 2 line †
(no internal temp sensor and 2 less “F” keys)
ELK-M1KPAS Keypad Arming Station †
ELK-M1XIN 16 Zone (input) expander
ELK-M1XOVR 16 Output expander, 8 Voltage/8 Relays
ELK-M1RB Relay board, 8 form ”C” relays
ELK-M1DBH Data bus wiring hub “Passive” †
ELK-M1DBHR Data bus wiring hub “Active” for Retrofit †
ELK-M1XEP Ethernet Port Exp/Interface †
ELK-M1XRFTW Two-Way Wireless Receiver for ELK 6000 Xmtrs
ELK-M1XRFEG Wireless Receiver for GE Xmtrs †
ELK-M1XRF2H Wireless Receiver for Honeywell 5800 Xmtrs †
ELK-M1XSP Lighting, Thermostat Interface & Serial exp. †
ELK-M1PR Mini prox reader for keypad †
ELK-M1TWI Two Way Listen-in Int. w/3 mic inputs †
ELK-M1TWS Speaker & Mic for Two Way Listen-in †
ELK-M1ZTS Zone Temperature Sensor -50 to 140 F †
ELK-RP PC software - Free upon request with
Control Panel purchase
ELK-RM Remote “User” Management software
Highlighted Features of the M1G (Gold)
• Automation (“Whenever/And/Then”) Rules Capacity 528
• Serial (RS232) Port Supported 8 w/expanders
• Phone Number Capacity 8
• Number of HVAC Thermostats †Supported 16
• Total Number of Outputs Supported 205
• Advanced Lighting †Options (Pre-set Dim, Extended, Levels, Scenes) Yes
• Analog Zone Definitions Supported Yes
Specifications, Features, and Benefits
† Not evaluated by UL †† Not for use in UL Listed Systems
NOTE: Use of Two Way Listen-in may be regulated by local or state laws and/or ordinance. It is the responsibility of the
Installer to check before using this feature.

M1G Installation and Programming
Page 6
+SAUX
NEG
+VAUX
NEG
+VAUX
NEG
+VAUX
NEG
AC
NORMAL
ZONE 16
JP1
SW1
16.5 V
JUMPER TO START
WITH NO AC
POWER
TELCO SEIZED
AC
Z9
NEG
Z10
Z11
NEG
Z13
NEG
Z15
Z14
Z12
NEG
Z16
Z2
Z3
NEG
Z5
NEG
Z7
Z6
Z4
NEG
Z8
Auxiliary +12VDC Power Outputs protected by 1.25A PTC NOTE:
Refer to Appendix F for the UL limitations on total continuous 'standby'
current drain from terminals +SAUX, +VAUX, +VKP, and J16.
Replace Battery every 3-5 years. Use ELK model # ELK1280 (12V - 8 Ah) or ELK12180 (12V - 18 Ah) or equivalent.
DIALER ACTIVE
SMOKE
2WIRE
STATUS
REVERSE
BAT LEADS
+-
7
N.C. N.O.
ZONE
2200
Ohm
EOL 8
N.C. N.O.
ZONE
2200
Ohm
EOL
5
N.C. N.O.
ZONE
2200
Ohm
EOL 6
N.C. N.O.
ZONE
2200
Ohm
EOL
3
N.C. N.O.
ZONE
2200
Ohm
EOL 4
N.C. N.O.
ZONE
2200
Ohm
EOL
1
N.C. N.O.
ZONE
2200
Ohm
EOL 2
N.C. N.O.
ZONE
2200
Ohm
EOL
12 Volt
Sealed
Lead Acid
Control needs AC power to start. Momentarily shorting these two pads allows control to startup on battery only.
16.5VAC, 45VA UL Listed Class 2 Transformer - ELK-TRG1640
DO NOT CONNECT TO A SWITCHED OUTLET
For Canada use cUL Listed Transformer - ATC Frost # FPS-4016 18AWG Min.
NEG
Z1
15
N.C. N.O.
ZONE
2200
Ohm
EOL 16
N.C. N.O.
ZONE
2200
Ohm
EOL
13
N.C. N.O.
ZONE
2200
Ohm
EOL 14
N.C. N.O.
ZONE
2200
Ohm
EOL
11
N.C. N.O.
ZONE
2200
Ohm
EOL 12
N.C. N.O.
ZONE
2200
Ohm
EOL
9
N.C. N.O.
ZONE
2200
Ohm
EOL 10
N.C. N.O.
ZONE
2200
Ohm
EOL
Master Power Switch (SW1), disconnects AC and Battery power from control.
This unit provides Residential fire alarm service when installed according to ANSI/NFPA 72. Transmission
of the fire alarm signal to a fire alarm headquarters or central station shall be permitted only with the
approval of the authority having jurisdiction. The burglar alarm signal shall not be transmitted to a police
emergency number, equipment is to be installed in accordance with NFPA (985,55.1.P).
Recommended locations and wiring methods shall be in accordance with CSA C22.1, Canadian Electrical
Code, Part I, Safety Standard for Electrical Installations; CAN/ULC-S302, Installation and Classification of
Burglar Alarm Systems for Financial and Commercial Premises, Safes and Vaults; and CAN/ULC-S301,
Standard for Central and Monitoring Station Burglar Alarm Systems.
Reference NFPA70 (NEC) & Canadian Electrical Code.
All circuits are current limited except for Battery leads. Refer to Appendix F.
For Installation of Residential Fire Warning Systems reference CAN/ULC-S540 Standard.
Testing of this system should be performed regularly with the primary AC power de-energized. Control
panel specifications are subject to change without notice.
Lithium 3V "Clock" battery, Varta #CR2032 located in upper left corner behind cover. Battery has a life
expectancy of approx. 10 years. Replace ONLY with exact model available at most electronics and camera
retailers. "CAUTION: Lithium Battery May Explode If Mistreated. Do Not Recharge, Disassemble, or
Dispose Of In Fire."
Dialer/Modem is idle. If ON, Dialer/Modem is in use (communicating).
1 blink with equal On and Off times is Normal. 2 fast blinks = Control running on
bootloader only. 4 fast blinks = Control is re-initializing it's EEPROM memory after
a firmware flash. 5 fast blinks = Memory/Operation overflow
Battery is connected correctly. If ON, check battery lead connections.
AC Voltage is present and power switch is turned ON. If OFF, check AC power.
Phone line is good and house phones are connected. If ON constantly, the phone
line may be bad. During remote mode this LED will be ON since the house phones
are then disconnected from the outside line & are being powered from control.
TELCO
SEIZED
DIALER
ACTIVE OFF
OFF
LEDS
Indicators
Power
Regular 1
sec. Blink
ON
Battery
Reversed OFF
Status
4-Wire Smoke Detector
2200
Ohm
EOL
To Zone Input
U.L. Listed EOL Supervision Relay
(ESL #204 or Equivalent).
N.O. Alarm
Contacts
+
-
+
-
Switched +12 VDC Output
protected by 1.1A PTC.
BATTERY
To Zone NEG
(Left Side Terminals)
Normal
State Descriptions
Color Code for 2200
Ohm EOL Resistor
Part # ELK-ER2200
Color Code for 820
Ohm EOL Resistor
Part # ELK-ER820
NOTE: M1ZTS Temperature Sensors may only be connected to the first 16 zones.
Smoke Detector covers should be kept free
from dust and dirt by use of a dry or damp
(water) cloth as needed. When necessary,
clean the detector interior and/or replace the
optical chamber according to instructions
provided by the Smoke Detector Manufacturer.
+
2-Wire Smoke Detector
820
Ohm
EOL
+
-
NEG
Z16
Compatibility Identifier: M10001
Maximum Operating Voltage: 13.8 VDC
Max. wire resistance should not exceed 13 Ohms.
Use 18AWG Fire approved wire. Max. wire length = 1000 feet.
Do not mix different models on same circuit as proper operation
may be impaired.
Name
System Sensor
Sentrol (GE)
Model
2W-B, 2WT-B, 1151, 2100, 2100T, 2151
429AT, 521BXT, 521B
Compatibility ID
A
S09A
Max #
20
20
Base
None
None
To configure Zone 16 as a 2-wire smoke zone, set Jumper JP1 to "2 WIRE SMOKE" and use 820
Ohm EOL resistor, part # ELK-ER820.
2-Wire Smoke Detector Compatibility
† †
M1G "Board only" non-alarm
current draw = 140mA ( .14 Amp )
Gray (8)
Red (2)
Brown (1 x 0)
Gold (quality)
Red (2)
Red (2)
Red (2 x 0)
Gold (quality)
Wiring & Hookup Diagram

M1G Installation and Programming Page 7
(Right Side Terminals)
OUT1
+12V (+VAUX)
NEG
16
15
14
13
12
11
10
9
8
7
NEG -
DATA B
+12V
DATA BUS
-
A
B
C
J3 J4
1 WAY
PLC
Mode
2 WAY
JP2
RS232
+
J16
J5
OUT3 LED
OUT3OUT2
+-+-
+VKP
DATA B
DATA A
NEG
Not Used
R1
TIP
RING
T1
* See Auxiliary Current ratings
1 WAY (PL513/PSC04) Select PLC Mode (JP2)
Selects single or bi-directional
PLC Transmissions
2 WAY (TW523/PSC05)
JP2
Voice/Siren †
OUTPUTS
AUDIO NETWORK INTERFACE
J7
Aux Data Bus (J3) ††
For wireless receiver. Presently
works with ITI / Caddx NX408E,
NX416E, or NX448E. See
Programming Menu 14.
Audio Network Connection (J7) ††
For Two-Way Listen-in and Future Use!
J1J2
NEG
+12V
N/CCOMN/O
Compiles with FCC Part 68
Reg. Number: US:5K6AL03BELK-M1
Ringer Equivalence REN: 0.3B
Use USOC RJ-31X connector.
Complies with the limits for class B computer
devices in accordance with the specifications of
subpart J of part 15 of FCC rules.
Out 3 - Programmable General Purpose Relay
Rated at 4Amps @ 12 - 24VDC
(Dry Contacts)
Terminating Jumper (JP3): See
important information about Data
Bus Termination.
This terminal (formerly earth ground) is no longer used. Do not connect this or any neg. terminals to earth ground.
Out 1 - Voice/Siren ††
Speaker output only (Interior)
Out 2 - Connect ONLY 1 UL Listed Bell or Siren (self-contained). For residential Fire the indicating
device shall be Wheelock 34T-12 or equiv. Current limited to 1 Amp. Program Global Option 26 to Voltage.
Speaker(s) are only permitted for non-UL installations and they must be series/parallel wired to avoid
dropping below a 4 ohm total load.
Programmable Outputs (J16)
OUT 7 - 16 are +12V switched
positive general purpose
outputs rated at 50mA.
Lighting ††
Interface Conn.
RJ31X JACK (ELK-RJSET)
PC Personal Computer
(Windows Based)
Serial Port (J4) ††
for Computer/ELKRP
(This connection not
evaluated by UL)
Lighting Interface Conn. (J5) ††
Use Std. 4 conductor modular telephone
cable to connect to a powerline Interface
(PSC05, X-10 PLC or equiv.).
Do not connect to a live phone line!
(This connection not evaluated by UL)
N/C
COM
N/O
DATA BUS TERMINATION IS VERY IMPORTANT!!
Diagram shows 2 basic (4-wire) home run cables with daisy chained devices on each. Last device on each cable
MUST have a Terminating Jumper installed. Jumpers are marked JP2 on keypads, JP1 on Expanders. Control
Hardware pack has two black jumpers for this purpose. Jumpers engage a 120 Ohm resistor across data A & B lines.
NOTE: If there is only 1 data bus cable, install JP3 Jumper on the Control.
Temporary Connection "Plug-in" jacks for RS-485 Data Bus (J1 & J2)
Local connection for Data Bus Devices ie: Keypads, etc. for testing purposes only.
ELK-SP35 or equiv.
PSC05 or
equiv.
Relay Expansion Module (ELK-M1RB)
Optional module adds 8 general purpose
relays. Plugs into J16 connector.
Red
Black
White
Green
Brown
Blue
Yellow
Violet
Pink
Tan
Orange
Grey
+VAUX
NEG
OUT 16
OUT 15
OUT 14
OUT 13
OUT 12
OUT 11
OUT 10
OUT 9
OUT 8
OUT 7
+12V
NEG
Green
Grey
Red
Brown
BLACK
WHITE
GREEN
JP3
RS-485 Data Bus Max. length is 4000 ft. Total
length of 2 homeruns must not exceed that distance.
NOTE: If you want to home run more than 2 cables, run 6 or 8 conductor cable so that the data lines A & B can have a
return path to series connect back out to the next device. This is best done with a ELK-M1DBH Data Bus Hub which
accepts Cat5 or Cat6 cable with RJ45 plugs. For more information see diagram in keypad instructions.
WARNING! The RS485 Data Bus must NEVER have more that two (2) terminating jumpers installed.
RS-485 DATA BUS
DATA A
RED
Data Bus Devices e.g. Keypads, Expanders
Jumper
Terminate
these two
devices.
DO NOT Jumper
Terminate these devices.
Yellow
Green
Red
Black
Yellow
Green
Red
Black
Close up view of std. 4 conductor modular phone cord. When
viewed as shown (back to back), the pin to pin color coding
does not reverse. Cord for PLC must be similar to above.
End
view
11
Pin 2 < to > 2
Pin 3 < to > 3
Pin 5 < to > 5
Pinout for Serial Port Cable (9 pin male to 9 pin female)
Maximum recommended length = 50 ft.
Out 2 is supervised. If not used, install a 2.2K Ohm
resistor to avoid Output 2 trouble condition.
NOTE: Do Not place a Direct Short Across OUTPUT 2.
Bell (Supervised)
+
+
-
-
TELCO
LINE
HOUSE
PHONES
T
R
T1
R1
5
4
8
1
Tip
Ring
Green
Red
Yellow
Black
Demark splices
† Not evaluated by UL †† Not for use in UL Listed Systems
Use 26AWG telco wire
A UL Listed Supplementary Power Supply may be required to meet the minimum standby
power supply requirements. Refer to the Chapter containing Regulatory Agency Statements.
Min. wire gauge: 24 AWG
18 to 22 AWG is best for
long distances.

M1G Installation and Programming
Page 8
1.1 Planning the Installation
The first step in any multi-zone security system installation is planning the job.
1. Read this entire manual to familiarize yourself with all system features and procedures before actually beginning the
installation. Read all the information regarding Underwriters Laboratories (UL) and NFPA requirements.
2. Perform a physical survey of the installation site. Use the diagrams below as a guide in planning the installation.
3. Discuss the installation requirements and applications with the customer.
4. Compare the installation requirements and applications with the factory default settings to determine what customized
programming is needed to meet the specific installation requirements.
5. Bench test the system prior to installation.
1.2 Parts Diagram & Descriptions
See Wiring & Hookup Diagram on pages 6 & 7.
1.3 Mounting and Wiring Preparation
Control Mounting
DO NOT MOUNT THE CONTROL OUTDOORS OR IN A DAMP LOCATION OR WHERE THE ENVIRONMENTAL CONDITIONS
ARE UNSUITABLE FOR ELECTRONIC BASED EQUIPMENT. DO NOT MOUNT IN AN UNCONDITIONED ATTIC. USE
COMMON SENSE AND GOOD INSTALLATION PRACTICES. A suitable location would be inside a secure dry location where
the ambient temperature inside the control box can remain at 32‘ to 120°Fahrenheit (0’ to +49' Celsius). Choose a location
that allows easy wiring to an unswitched power outlet and to a grounding conductor for the control. A central location makes
running system wiring easier. Remove control box knockouts that best suit your wiring needs.
After removing all packing materials, compare the system components with those in the figure above to familiarize yourself
with the part names. Mount the control using the upper center slotted hole to level. Install and connect all necessary wiring for
the power transformer, detection loops, keypads and siren outputs.
Keypad Mounting and Wiring
Ideal height is 50-58 inches. Pick a location with an ambient temperature range between 32°and 120°F (0° to +49°C). Avoid
direct sunlight if possible. Fasten backplate to electrical box or wall with flat head screws to prevent shorts to the back of the
circuit board. Keypads have an unpluggable harness for connecting to the M1data bus. Splice the Black, Red, White, and
Green wires from the unpluggable harness to the M1 Data Bus field cabling. Plug the connector into the back of the keypad.
Tuck wires neatly into back plate and install Keypad on mounting plate. The LCD keypads have connections for an optional
programmable output and a programmable zone input. NOTE: Min. field wire gauge is 24 AWG, but 18 to 22 AWG is better for
long distances. CAT5 (8 conductor) cable can be purchased in various wire gauge sizes. Where possible always use the
larger gauge CAT5 cable. The extra conductors in CAT5 wires can be used to provide return path for the data A & B lines.
Section 1 - Installation and Wiring
Legend
- Main Control
- Audible Alarm
- Smoke Detector
- Contact
- Keypad
M
A
S
C
K
Bedroom 1Bedroom 2
Bedroom 3 Living Room
Kitchen / Dining
TYPICAL BURGLARY INSTALLATION LAYOUT
M
A
K
Bedroom 1Bedroom 2
Bedroom 3 Living Room
Kitchen / Dining
TYPICAL FIRE INSTALLATION LAYOUT
M
A
K
C
CCCCC
S
SS
S
Basement
First Floor
All perimeter openings below 18" should be provided with protection.
A Smoke Detector shall be located in each sleeping area and between
the sleeping areas and the main living area.
Early warning fire detection is best achieved by the installation of fire
detection equipment in the location shown above.
In homes basements or multiple levels at least one smoke detector
shall be on each level.

M1G Installation and Programming Page 9
1.4 Control Wiring
Zone Inputs (1 thru 16 on main board, 17 thru 208 via expanders)
Zones are arranged in groups of 16, starting with Z1 thru Z16 on the main board. Each 2 zones share a common negative
terminal. A zone may be programming for EOL resistor supervision (Default), or normally closed/normally open without a
resistor. In addition, Burglar and Keyswitch zones may be programmed for EOL with Security Alert on Short, or EOL with
Security Alert on Open/Short, also referred to as a Four (4) State Zone (firmware 4.3.5 or later). If EOL resistors are used, they
should be placed at the furthest most remote end of the detection device wiring. EOL zones permit a combination of N.C.
(normally closed) or N.O. (normally open) devices. Using voltage meter probes across the zone and com terminals, a non-
violated EOL zone will measures approx. 7.0 VDC. An open circuit will be approx. 13.8 VDC. A shorted circuit will be 0
VDC. The Keypad also provides the ability “Menu 8 “System Diagnostics” to view zone voltage.
ELK-M1KP
1
See Note about
Data Bus
Termination
6
BLACK
WHITE
GREEN
RED
Keypad
Wiring
Assembly
Optional programmable Zone Input from Keypad
Hookup Diagram for Keypad
Splice 6 Pin Keypad Wiring Assembly to the Data Bus cable using ELK-900-2 "B" Connectors.
BROWN
Optional programmable Output from Keypad
Keypad 1
The optional Zone Input # or Output # is
determined by the Keypad Address.
Load (50mA max)
I.E. LED, Relay
-
+
To BLACK (Neg) Wire
To BROWN Wire
N.C. N.O.
2200
Ohm
EOL
To BLACK (Neg) Wire
BLUE
To BLUE Wire
NOTE: Early production M1KP Keypads provided a switched
negative (pull to ground) output. These units have the letter "E"
at the end of the ID number on the lower back side of the board.
Connect per diagram above. Boards marked PC096 with a letter
"F" or later provide the output as a switched positive.
Load (50mA max)
i.e. Relay, LED
-
+
To Red (Pos) Wire
To Brown Wire
KP Zone Output
Address # #
1 193 193
2 194 194
3 195 195
4 196 196
5 197 197
6 198 198
7 199 199
8 200 200
KP Zone Output
Address # #
9 201 201
10 202 202
11 203 203
12 204 204
13 205 205
14 206 206
15 207 207
16 208 208
Min. wire gauge: 24 AWG
18 to 22 AWG is best for long
distances.
Optional Four (4) State Zone Wiring (2 series resistors w/ N.C. contacts)
Zone
Input
Neg.
N.C. Alarm
Contacts
2200 Ohm
Resistor
2200 Ohm
EOL Resistor
N.C. Tamper
Contacts
Pos.
Neg.
Fig 2: Powered PIR, Glassbreak, etc. with Tamper
N.C. N.O.
Contact
2200
Ohm
EOL
Zone Input
Neg.
Tamper Contact
N.C.
Alarm
Contact
Diagnostic Table
Short ~
2.2k Ohms
4.4k Ohms
Open ~
0 - 3.9 Volts
4.0 - 7.3 Volts
7.4 - 11 Volts
11.1 - 13.8 Volts
Zone
Resistance
Approx. Zone
Voltage Reading
Alarm
-
Alarm
Alarm
Armed
Sec. Alert/Tamper
Ready
Not Ready
Sec. Alert/Tamper
Disarmed
Condition When:
0 - 72
73 - 159
160 - 220
221 - 255
A to D
Value
Fig 1: N.C. Alarm Contact
(Unpowered) with N.C. Tamper
Program Zone for EOL Wiring
Type 4 - Supervisory on Open
This feature
requires Firmware
2.3.5 or later.
2200 Ohm
Resistor
Traditional Three (3) State Zone Wiring (1 series resistor)
Wire in Series with zone
input or use another zone.
Neg.
N.C. Alarm
Contacts
2200 Ohm
EOL Resistor
N.C. Tamper
Contacts
Pos.
Neg.
Powered Motion, PIR, Glassbreak, etc.
N.O.
Contact
2200
Ohm
EOL
Zone Input
Neg.
N.C.
Alarm
Contact
Diagostic Table
Short ~
2.2k Ohms
Open ~
0 - 3.9 Volts
4.0 - 8.8 Volts
8.9 - 13.8 Volts
Zone
Resistance
Approx. Range
of Zone Voltage
Alarm
-
Alarm
Armed
Not Ready
Ready
Not Ready
Disarmed
Condition When:
0 - 72
73 - 170
171 - 255
A to D
Value
Zone
Input
Alarm Contact
NOTE: Refer to the section ‘Data Bus E.O.L. Termination’ for information on multiple homerun cables. NEVER SPLICE OR
CONNECT WIRE WITH CONTROL POWER ON. Minimum cabling should be four conductor 22 or 24 gauge. Maximum resistance per wire
is 25 Ohms. Device placement beyond 1000' is not recommended.

M1G Installation and Programming
Page 10
Two-Wire Smoke Zones (Zone 16)
To enable use of two-wire smoke detectors on Zone 16, position Jumper JP1 (located below Zone 16 terminals) so that the
two right hand pins are covered. Go to Installer programming mode, Menu 05 - Zone Definitions, and program Zone 16 as a
Fire zone (Def=10). Step to next location and program Wire Type=6. NOTE Use only compatible two-wire detectors listed on
the front label of the control. Do not mix brands. The maximum number of detectors is also listed on the front label. For
two-wire operation, a 820 Ohm EOL resistor part # ER820 must be used instead of the 2,200 Ohm resistor part # ER2200.
Use 18AWG Fire approved wire. Max. wire length = 1000 feet. Max. wire resistance should not exceed 13 Ohms.
Switched Power Connection (+SAUX)
Four-wire smoke detector and other devices that require a temporary power disruption in order to reset or unlatch from the
alarm state (i.e. smoke detectors, etc.) should be connected to the +SAUX 12 Volt DC switched power terminal. When a
smoke reset is performed, the operating voltage to these devices is momentarily interrupted.
Auxiliary Power Connections (+VAUX)
Motion detectors, glass breaks, etc. and other devices requiring unswitched 24-hour power should be connected to one of the
auxiliary terminals, +VAUX. All negative terminals on the terminal strip are at the same reference and may be used whenever
a common (circuit ground) negative is required. Use caution when wiring the control to distribute the load devices among the
supply and the negative terminals evenly. NOTE: Circuit ground refers to any negative terminal connection on this control.
This does not refer to the earth ground terminal or to the common terminals of Relay Output 3. These terminals are not at
the same voltage potential and should not be wired so that they are electrically connected to a negative.
PTC (Positive Temperature Coefficient) Circuit Breakers
The +VAUX Auxiliary power and J16 power output terminals are protected against shorts and overloads by a 1.25A PTC. A PTC
is a solid state, auto-restoring type of circuit breaker. The +SAUX Switched (Smoke) power output is protected by a 1.1A PTC.
The +VKP Keypad power output is protected by a 1.25A PTC. Output 2 is protected by a 1.25A PTC. NOTE: Sometimes it may
be necessary to remove power (unplug the outputs) for approx. 20 seconds after a short, to allow the PTC to reset. Even
if the short is no longer present, the remaining residual current draw may be so high that the PTC cannot determine that
the short is gone. If the PTC re-trips, check the field wiring and repair.
Transformer Primary Power Input (AC)
The control is powered by a 16.5 VAC, 40 min. VA, UL Listed Class 2 transformer (ELK-TRG1640). The specified sized and
rated transformer must be used to operate this control. The transformer must be connected to a 120 VAC, 24-hour outlet not
controlled by a switch other than an approved overcurrent protection device.
Connect the transformer to the AC Terminals using 16 to 18 gauge minimun wire. Do not exceed 50 feet between the
transformer and the control or run the AC power in a multiconductor with other system circuits. Leave the transformer
unplugged as well as the standby battery until all other connections have been made.
Standby Battery Connection
Connect the BLACK wire to the Neg (-) terminal on the battery, the connect the RED wire to the Pos (+) terminal on the battery.
The control is designed to operate with and recharge a 12 volt, sealed lead acid battery from 7Ah up to 18 Ah for backup of the
primary power supply. The control maintains a float charge for the battery of 13.8 VDC at 100 mA. This is in addition to the
continuous output of 1.5 Amps that the power supply maintains (see maximum current drains for UL Listed Systems).
CAUTION: Do not reverse the battery leads! The control has special circuitry which helps protect it from battery reversal
damage for short durations. However, prolonged reversal of the battery leads may cause permanent damage. A reverse
battery warning LED is located to the left of the power On/Off switch. If this light is ON, turn the power off immediately
and correct the battery lead connections.
+VAUX
NEG
AC
SW1
16.5 V
JUMPER TO START
WITH NO AC
POWER
AC
BATTERY
+-
12V Battery
5 to 18Ah
Sealed Lead Acid
STATUS
REVERSE
BAT LEADS
UL Listed Transformer,
Class 2, 16.5VAC, 45VA
RED BLK
+-
ELK-TRG1640

M1G Installation and Programming Page 11
AC Failure, Low Battery, and Automatic Low Voltage Shutdown
During an AC power failure the battery automatically takes over and AC Fail trouble annunciates at the keypad. The
communicator can be programmed to report AC Fail to the Central Station after a time delay (see Menu 12, System Option 01).
If the battery voltage falls below 11.2 VDC a Low Battery Trouble condition will occur. The communicator can be programmed
to report Low Battery to the Central Station. The battery will continue to run the control until its voltage drops below 10.2 VDC,
at which time the control will disconnect and shut down to prevent a false alarm and damage to the battery. The AC Fail
trouble display will clear if the AC restores. However, the Low Battery Trouble requires a manual or automatic battery load test
before it will clear. An automatic battery load test is performed every 24 hours. See Section 2.2 for powering up the control.
Telephone Line Connection (R1,T1,T,R)
The telephone interface is connected by the use of an approved RJ-31X interconnect jack. This device allows the subscriber
to disconnect the control/communicator from the public switched telephone network in the event of a malfunction. The control
is equipped with line seizure so that the premises telephone service is interrupted during communication to the central
station. Connection to the approved jack is done with a RJSET cord which connects the control terminals to the RJ31X jack.
NOTE: The Telco cord can be supervised to the RJ31X or demarc block by installing an EOL resistor across the Orange and
Blue wires (RJ31X terminals 2 and 7). In the control, connect the Orange and Blue leads to any 24hr Burglar zone input.
Outputs
There are 13 outputs on the main board. Outputs may be expanded utilizing output expander boards connected to the RS-485
4-wire Keypad data bus. Outputs 1 & 2 trip when any alarm is activated. All others must be enabled through the RP Rules
Programming and can be triggered by multiple conditions “events”. Do not exceed the current limits on voltage only outputs.
Output 1 †† is for speakers(s) ONLY (4 to 8 Ohms). If connecting more than 2, use series/parallel wiring to avoid going
below a 4 ohm total load. This output is the source for voice announcements such as: Zone 1 not ready, System Armed, Alarm
Activated, etc., as well as alarm siren sounds. The initial start volume and the final volume can be adjusted in programming
to suit the application.
Output 2 - Connect a UL Listed Bell or Siren (self-contained). Current limited to 1 Amp. Program Global Option 26 to Voltage.
This output is supervised. Speaker(s) are only permitted for non-UL installations. Series/parallel wire to avoid dropping
below a 4 ohm total load.
Output 3 is a Single Pole Double Throw Relay with form “C” contacts (Com, N/O, and N/C).
Outputs 7, 8, 9, 10, 11, 12, 13, 14, 15, and 16 are low current, positive (+) voltage only, for driving LEDs, relays, etc. Outputs 4,
5, and 6 ARE NOT available from the main board. They can only be accessed with a data bus Output expander set to
address 1. This expander will replicate main board outputs 7 thru 16, while also including outputs 4, 5, and 6.
Earth Grounding
Tests have determined that the best results against lightning and transients are obtained by isolating the control from ground.
Do NOT connect any of the terminals, especially the Neg. terminals to earth ground. Early production boards had an earth
ground terminal. This terminal is no longer used on circuit board revision I or later. However, ancilliary devices such as the
ELK-950 Surge Protector on the incoming Telephone circuit are still recommended.
Keypad & Expanders on the RS-485 Data Bus (+VKP, Data A, Data B, Neg)
Keypads and data bus expander devices connect to the four terminals marked +VKP, Data A, Data B, and Neg. The keypad
plug-in wire harness color code is: Red +VKP, Green Data A, White Data B, and Black (-) Neg. The +VKP power terminal is
protected by an auto reset PTC device. In the event of a short circuit or malfunction, power will be removed from all devices
until the problem is resolved. Two (2) quick connect header pin plugs (J1 and J2) along the bottom of the board may be used
for temporary purposes I.E. bench testing using a four conductor ribbon cable. Do not use for permanent connections.
Using Output 7 (low current) with a sensitive relay to switch 24V AC to a Door Strike †
24V AC
Transformer
+-
Door
Strike †
ELK-924 †
POS
NEG
-T+T
N/OCOMN/C
D3
24V OPEN
N/OCOMN/C
+12V
NEG
16
15
14
13
12
11
10
9
8
7
J16
OUTPUTS
Programmable Outputs (J16) OUT 7 - 16 are +12V switched
positive general purpose outputs rated at 50mA.
+12V Red
Black
White
Green
Brown
Blue
Yellow
Violet
Pink
Tan
Orange
Grey
+VAUX
NEG
OUT 16
OUT 15
OUT 14
OUT 13
OUT 12
OUT 11
OUT 10
OUT 9
OUT 8
OUT 7
† Not evaluated by UL †† Not for use in UL Listed Systems

M1G Installation and Programming
Page 12
Data Bus E.O.L. Termination - VERY IMPORTANT!
The M1 data bus comforms to EIA RS-485 standards and operates at 38,400 bits per second. The RS-485 standard stipulates there be no
more than 2 home run data bus cables attached to the M1 Main Data terminals, with the end of each cable terminated by a 120 Ohm resistor
connected across the data wires. The M1 board and bus devices come with built-in terminating resistors that may be activated via 2 pin
jumpers (2 Gold Pins). Placing a shorting cap (included in hardware pack) on the two gold pins activates the 120 Ohm terminating resistor
across Data Lines A & B. These jumpers are marked JP2 on the keypads and JP1 on the expanders. From the factory, no terminating
resistors are installed. Without proper termination, noise and interference can cause data corruption and missed communications.
BLACK
WHITE
GREEN
NOTE: RS-485 Data Bus Max. wire length is 4000 ft. Total
length of 2 homeruns must not exceed that distance.
RED
Jumper
Terminate
these two
devices.
DO NOT Jumper
Terminate these devices.
Keypad 1
Data Bus Devices
e.g. Keypads, Expanders
Keypad 3
Diagram of Two (2) Home Run Cables with Devices Daisy Chained along the Data Bus
+VKP
DATA B
DATA A
NEG
RS-485 DATA BUS
The last device on each home run cable SHOULD be terminated via the gold 2 pin terminating header/jumper. Placing a shorting cap on the pins will engage a 120 Ohm
resistor across data lines A & B. If there is only 1 data bus home run cable then place shorting cap on JP3 of Main Board. See other hookups below.
Min. wire gauge: 24 AWG
18 to 22 AWG is best for
long distances.
Install Teminating
Jumper on this last
device AND on the
control JP3.
6 conductor cable
DATA
A1 A
B1 B
DATA
A1 A
B1 B
Optional Output and Zone Input - See Keypad Instructions
Connect each device to the 6 conductor cable as shown above
OPTION B - Using 6 Conductor Cables and Series Splices to Daisy Chain Connection of Data Bus Devices
Keypad
RS-485 DATA BUS
+VKP
DATA B
DATA A
NEG
Keypad
RED
GREEN
BLACK
WHITE
To 12VDC
To 12VDC
BLUE
BROWN
6 Wire
Cable
Keypad
RED +12
+
BLACK (-)
-
GREEN
WHITE
A
A1
B
B1
TO CONTROL
NOTE: RS-485 Data Bus Max. wire distance is 4000' total. Each homerun 6 conductor
cable must be calculated as double the running distance since the Data A & B lines
travel out and then back (A1 & B1) where they are used to feed the next homerun.
Another option for wiring multiple home runs is to use 6 conductor cabling. This allows devices to be daisy chained using an out and back configuration. This involves a 3
way splice of the data A (Green)wire to 2 wires of the 6 conductor cable (designated A and A1). Same is done for data B (White) wire. At the control wires A1 and B1 get
spliced to the A and B wires feeding the next device. Terminate the last wired device and the control JP3 ONLY! The POS (+) and Neg (-) power wires should be parallel
wired to the +VKP and Neg terminals or to an auxiliary Power Supply if the combined current draw exceeds the rated current available from the Control.
Min. wire gauge: 24 AWG
18 to 22 AWG is best for
long distances.
ELK-M1DBH Data Bus Hub †
Mount M1DBH inside control.
Use 4 conductor cable to connect
to the M1 Data Bus terminals.
J2 J4 J6 J8
J1 J3 J5 J7 J9
RJ45 Terminating Plug Insert in first unused jack and terminate the
control at JP3. DO NOT TERMINATE AT ANY OF THE DEVICES!
CAT5 Cables
OPTION A - Using an optional ELK-M1DBH and CAT5 Cables to Daisy Chain Devices
RS-485 DATA BUS
Keypad
Refer to Keypad Instructions
for more info about Output and Zone Input
+
-
A
A1
B
B1
TO CONTROL
8 - Brown
7 - Wht/Brn
6 - Orange
5 - Wht/Blue
4 - Blue
3 - Wht/Org
2 - Green
1 - Wht/Grn Pin1 RJ45 Plug
Blue pair
is unused
COLOR CODE EIA 568A for CAT5/6 Data Bus Cable to RJ45 Plugs.
Pin1
Front
view
Optional programmable Zone Input
Optional programmable Output
-
+
N.C. N.O.
2200
Ohm
EOL
To BLACK (Neg)
To BLACK (Neg)
Wht/Blue
Brown
Wht/Brn
Orange
Wht/Org
Green
Blue Wht/Grn
RED +12V
BLACK (-)
GREEN
WHITE
BROWN
BLUE
Keypad
CAT5
or
CAT6
Cable
To
+ 12V
Load (50mA max)
I.E. LED, Relay
+ VKP
DATA A
DATA B
NEG
NOTE: RS-485 Data Bus Max. wire length is 4000 ft. Total. Each CAT5 homerun from
the M1DBH must be calculated as double the running distance since the Data A & B
lines travel out and then back (A1 & B1) where they are used to feed the next homerun.
Keypad
The ELK-M1DBH † Data Bus Hub is great for new installations where it is possible run multiple CAT5 homerun cables. The RJ45
jacks allow neat and organized connections and a third wire pair is used to return the DATA lines back from each device where they
are used to feed the next adjacent jack. The M1DBH circuitry daisy chains the devices by series connecting the DATA lines A & B.
Termination is accomplished with a plug-in RJ45 terminator (supplied).
Min. wire gauge: 24 AWG
18 to 22 AWG is best for
long distances.
† Not evaluated by UL †† Not for use in UL Listed Systems
A
+B-
DATA BUS TERMINALS AUXILIARY POWER
SUPPLY
+
-
RED
GREEN
WHITE
BLACK
RED
BLACK
GREEN
WHITE
††† An Auxiliary Power Supply will be required if the control's Aux. power load for all
combined loads exceeds 1A. (450 mA for UL Commercial). Connect as shown below.
Be sure to connect the negative (-) terminal of the power supply to the negative (-)
terminal (Data Bus NEG) on the control.
ULUse a UL Listed, battery backed-up Power Supply for UL installations. The battery
will be supplying power to the Keypads/Expanders during a power outage. The Power
Supply and backup Battery should be sized to supply the Keypads/Expanders with the UL
required minimum standby time.
To Keypads or Expanders To Keypads or Expanders
WARNING! Do not splice or interconnect the M1 Data Bus using Telephone type 66 or 110 punch down blocks.
The RS-485 Data Bus must NEVER have more than 2 terminating resistors header/jumpers installed.

M1G Installation and Programming Page 13
Setting the Data Bus Address and Enrolling Device(s) into the System
Keypads and Expanders communicate over the RS-485 data bus. Each device must have a unique address setting (1 to 16)
within it's device type. Keypads are TYPE 1, input (zone) expanders TYPE 2, output expanders TYPE 3, etc. Device types permit
address numbers to be re-used on different device type. For example: a Keypad, Zone Expander, and Output Expander can
each be set to address 2 on the same data bus because each device is a different device type. But duplicate addresses
CANNOT exist within the same device type. I.E. Multiple keypads on the same bus cannot be set to 'like' addresses.
ADDRESS: From the factory all keypads are set to address 1. Valid addresses are 1 to 16. The first keypad on the system
(Keypad 1) is automatically enrolled upon power up. Each additional keypad must be assigned a unique address and then
manually enrolled from “Menu 1 - Bus Module Enrollment”. (See Menu 01, for complete instructions on Bus Module Enrollment)
1. Enter Keypad setup by one of the following three (3) methods:
a. Press and hold the " * " key for approx. 10-12 seconds (KP1 Keypads with firmware 2.1.48 or later)
b. Press the “ * ” and F5 keys at the same time for approx. 10 seconds. (older KP1 Keypads)
c. Hold ANY key pressed while applying power.
Keypad is in setup mode when the display indicates: Exit when done. F1 Set Addr.
2. Press the F1 key to display the current address setting.
3. Set the desired address by entering a number from 1 to X.
4. Press the Exit key when done.
1234567890123456789012345
1
23456789012345678901234
5
1
23456789012345678901234
5
1
23456789012345678901234
5
1
23456789012345678901234
5
1
23456789012345678901234
5
1
23456789012345678901234
5
1
23456789012345678901234
5
1234567890123456789012345
Auth. Required
Enter Valid Pin
1234567890123456789012345
1
23456789012345678901234
5
1
23456789012345678901234
5
1
23456789012345678901234
5
1
23456789012345678901234
5
1
23456789012345678901234
5
1
23456789012345678901234
5
1
23456789012345678901234
5
1234567890123456789012345
01-Bus Module
Enrollment
ENROLLING:
1. Press the ELK key, then 9 (or scroll up) to display 9 - Installation Programming. Press the RIGHT
arrow key to select this menu. The Installer Program Code must be entered to access this menu.
2. Enter the Installer Program Code. (The default code is 172839)
3. The first Installer Programming menu display will be “Bus Module Enrollment”
4. Press the RIGHT arrow key to select this menu. “Enrolling Bus Modules” will display.
5. After a few seconds the display will show the total Bus Modules that are enrolled. To view the
enrolled devices and /or remove a device press the RIGHT arrow key next to the word Edit.
6. Press the * or Exit keys to exit Installer Programming.
1234567890123456789012345
1
23456789012345678901234
5
1
23456789012345678901234
5
1
23456789012345678901234
5
1
23456789012345678901234
5
1
23456789012345678901234
5
1
23456789012345678901234
5
1
23456789012345678901234
5
1
23456789012345678901234
5
1234567890123456789012345
XX Bus Modules
Enrolled, Edit rr
rr
r
JP1
Terminating Jumpers (JP1 - JP5)
JP1 = Terminates Input from Control
JP2 = Terminates Branch 1
JP3 = Terminates Branch 2
JP4 = Terminates Branch 3
JP5 = Terminates Branch 4
See details about Data Bus Termination.
ELK-M1DBHR †
DATA BUS HUB FOR RETROFIT
ELK PRODUCTS, INC. HILDEBRAN, N.C., 28637, USA
JP2 JP3 JP4 JP5
+VKP
DATA B
DATA A
NEG
RS-485 DATA BUS
BLACK
RED
GREEN
WHITE
AB-
+
INPUT
FROM CONTROL
Mount M1DBHR(s) in same enclosure with the
M1 Main Board. Connect to the M1 Data Bus
terminals using a short 4 conductor cable.
DO NOT attempt to remotely mount an
M1DBHR or use as a remote bus extender!
RED
GREEN
WHITE
BLACK
A
+B-
DATA BUS
BRANCH 1
RED
GREEN
WHITE
BLACK
Keypad
A
+B-
DATA BUS
BRANCH 2
Keypad
Keypad
Example #1
A single Keypad on Branch 1
Place terminating jumper on the
Keypad/Bus Device AND on JP2 of
the M1DBHR.
Example #2
Two (2) Keypads on Branch 2
Place terminating jumper on BOTH Keypads
and remove jumper JP3 on M1DBHR.
Example #3
Three (3) Keypads & 2 Expanders on Branch 3
(Devices must be Daisy chain wired on each
homerun so they appear to be in series.)
Jumper
Terminate
these two
devices.
DO NOT Jumper Terminate
these devices.
Keypad
Keypad
Keypad
RED
GREEN
WHITE
BLACK
A
+B-
DATA BUS
BRANCH 3
A
+B-
DATA BUS
BRANCH 4
Jumper
Terminate
these two
devices.
Example #4
Branch 4 empty (not used)
Place terminating jumper JP5 of M1DBHR.
Jumper Terminate
this device AND
JP2 on the
M1DBHR.
DO NOT Jumper JP3.
DO NOT Jumper JP4.
Bus Termination:
If using 1 M1DBHR place jumper on JP1 of
the M1DBHR and JP3 of the M1 Control.
With 2 M1DBHR boards place jumper on
JP1 of both M1DBHR boards and remove
jumper JP3 on the M1 Control.
OPTION C - Using an optional M1DBHR Retrofit Data Bus Hub
A
+B-
DATA BUS TERMINALS AUXILIARY POWER SUPPLY
+
-
RED
GREEN
WHITE
BLACK
RED
BLACK
GREEN
WHITE
Place terminating jumper on the LAST
device connected to each homerun and
remove jumper JP4 on M1DBHR.
††† An Auxiliary Power Supply will be required if the control's Aux.
power load for all combined loads exceeds 1A. (450 mA for UL
Commercial). Connect as shown below. Be sure to connect the
negative (-) terminal of the power supply to the negative (-) terminal
(Data Bus NEG) on the control.
ULUse a UL Listed, battery backed-up Power Supply for UL
installations. The battery will be supplying power to the Keypads/
Expanders during a power outage. The Power Supply and backup
Battery should be sized to supply the Keypads/Expanders with the
UL required minimum standby time.
To Keypads or Expanders To Keypads or Expanders
DO NOT attach more than two (2)
M1DBHR Hubs to a single M1 Control.
DO NOT EXCEED two (2) terminating jumpers on
any of the 4 branches of the M1DBHR or the
main M1 bus.
Like the Main M1 Bus, the Maximum wire
length of any of the 4 branches on the
M1DBHR is 4000 ft.
+VKP is protected with 1.25A PTC
The max. number of bus devices
varies based on the types and
models being used or combined.
The ELK-M1DBHR † Data Bus Hub Retrofit is NOT INTENDED for use on newly wired installations. It is expressly designed for retrofit jobs where existing 4 conductor
cables are the only wires available. The M1DBHR creates 4 managed RS-485 BRANCHES from the single M1 main RS-485 Bus. Each of these branch can have only 2
home run cables (4 branches x 2 ea. = 8 home runs). WARNING! DO NOT CONNECT more than 2 M1DBHRs to an M1. DO NOT CONNECT an M1DBHR on a branch
of a DBH or another M1DBHR! DO NOT ATTEMPT to use an M1DBHR as a data bus extender or repeater. DO NOT REMOTE a M1DBHR(s) away from the M1.
Always mount it inside or very close to the M1 Control enclosure. Terminate the last (end of line) device on each home run.
Min. wire gauge: 24 AWG
18 to 22 AWG is best for long distances.
† Not evaluated by UL †† Not for use in UL Listed Systems

M1G Installation and Programming
Page 14
2.1 Introduction
The control has factory default programming which make it easy to bench test prior to installation. Terminate all zones with
EOL resistors, then connect a keypad, transformer, and battery. The factory (Master) user code is 3456. This code can
operate all user related features of the system. This section gives an overview of powering up and basic keypad functioning.
2.2 Powering Up (One Keypad)
After all other connections have been made and checked thoroughly, the controls AC transformer and battery may be
connected. The Master Power Switch located on the lower left corner can then be turned. Upon power up the control will
perform self-diagnostics and auto-enroll the first keypad (Keypad Address #1). Any additional keypads or expanders must be
manually enrolled using Installer Level Programming. See “Menu 01 - Bus Module Enrollment”.
NOTE: It is very important to make certain that every keypad, input expander, output expander, or any other data bus
device be assigned a unique data bus address within its type. See “MENU 01 - Bus Module Enrollment” for instructions
on setting keypad and expander addresses.
System Startup on Battery Only (Ordinarily the control will not startup without AC power)
If AC power is not available (new construction site, etc.) the control may be started on battery ONLY by shorting the two silver
pads (located in the lower left corner of the circuit board) with a small blade screwdriver. This will temporarily bypass the AC
sensing circuit and allow the control to startup. NOTE: The On/Off power switch must be in the On position.
2.3 User Codes and Authorities
The control has 199 user codes plus one installer code. Each user code may be assigned specific authorities as to what it is
allowed to do. The authorities are assigned from the Installer level programming, however the code digits and user names
are assigned from the keypad user menu 6 - Change User Codes. Only a Master authority level code or the Installer code is
allowed to access keypad user menu 6. The User’s Guide contains a description of operations accessible to the user codes.
Control operations accessed by the installer passcode are slightly different.
Factory Default for User Code 1 is: 3 4 5 6 (Master Code) (1 2 3 4 5 6 if the six digit code option is enabled)
User code may be used for functions in a specific area or system-wide. Some options may be performed at any time, even
while the control is fully or partially armed. The menu system is designed to be next-step-oriented. After a brief explanation of
the options, the user should be able to begin operating the system immediately. For purposes of discussion, the installer and
the end consumer are both considered users, but have different capabilities.
2.4 Installer Program Code and Authorities
The installer code can access all the keypad user menus and has limited arm/disarm privileges. It may be used to arm any
area and disarm any area as long as the area WAS NOT armed by a user code. The Installer code can silence 24hr alarms
or a Burglary alarms in an area that was armed by the installer or in an area that is not armed. The installer code can silence
a trouble condition in a disarmed area. See User’s Guide for a full description of arming and disarming procedures.
Factory Default for the Installer Program Code is: 1 7 2 8 3 9
WARNING! Do Not use 0 0 0 0 0 0 for the Installer Program Code.
This will cause complete lockout of Keypad Installer Level Programming.
Section 2 - Operating the System

M1G Installation and Programming Page 15
Ready Light - ON when all burglar zones are secure and the system is OK to arm. If OFF, one or more zones are violated (not secure). For
maximum security, secure all zones before arming the system. If FLASHING, one or more force-armable zones are violated. Force arming
temporarily excludes violated zone(s) from the system. If a force armed zone becomes secure while system is armed, it will automatically
restore to service. This is handy for a garage door as system may be armed with the door up, but will secure when door closes.
Armed Light- ON when the system is armed. The mode of arm will be indicated by the LCD display and the Exit or Stay lighted pushbuttons.
This light will be OFF when the system is disarmed.
Exit Key - May be programmed for single or double press arming to the AWAY (not occupied) mode. If ON the system is armed and all
perimeter sensors and interior motions are active. The Away key may be pressed during the exit delay time t to convert from Away to Away
Vacation mode. Vacation mode is primarily for use with the Whenever/And/Then Rules programming of Elk-RP for long term energy savings.
Stay Key - May be programmed for single or double press arming to the STAY (occupied) mode. If ON the system is armed and all interior
zones are excluded (bypassed). Only perimeter doors and windows are active in the Stay mode. This key may also be programmed to
change to other Stay modes such as: Stay Instant, Stay Night, and Stay Night Instant. Since interior zones are automatically excluded once
the Stay mode is activated, the M1 allows this key to Stay arm even while one or more interior zones are violated, provided they are pro-
grammed for “force arming”. The Stay Night mode re-activates any interior night zones. To prevent a false alarm the control will not allow
change to the Stay Night mode when a interior night zone is violated unless it is programmed for “Force arm”.
2.5 Keypad Overview
Keypad Models and Feature Comparison
PART
NUMBER
ELKM1KP
ELKM1KP2
ELKM1KPAS
PHYSICAL
DIMENSIONS
6.87" W x 5.25" H x 1.32" D
4.65" W x 5.5" H x .95" D
1.3" W x 2.62" H x .3" D
(keypad area not incl. elect. plate)
FUNCTION
KEYS
(6) F1 thru F6
(4) F1 thru F4
(6) F then 1- 6
DOOR
COVER
Yes
No
No
BACKLIGHTING
LCD KEYS
Green Amber
Blue Blue
N/A Blue
TEMP
SENSOR
Yes
No
No
ZONE
INPUT
Yes (1)
Yes (1)
No
PROG.
OUTPUT
Yes (1)
Yes (1)
No
OPT. 26 BIT
PROX READER
Yes - Int. or Ext.
Yes - Ext. Only
No
MOUNTING
OPTIONS
Surface Only
Surface Std.
(Flush w/opt. BBK2)
Flush Std.
ELK-M1KP LCD Keypad
ELK-M1KP2 LCD Keypad
Smaller than M1KP.
Available Keypads Styles
ELK-M1KPAS Arming Station
Fits a single gang electrical box.
Features and/or operational characteristics will vary by keypad style.
Chime Key - Will be lighted when the Chime mose is On. A tone or announcement will be heard when certain zone(s) are opened. If OFF
the chime mode is off. There are four different selections: Tone only, Voice, Tone/Voice, and Off. In the programming mode this key also
functions as an insert character key for text programming. The key will be lighted when Chime is On.
Bypass Key - Pressing this key followed by a zone number and the bypass key again will exclude or bypass the selected zone. This
key may also be used to delete a character during text programming. When the Bypass key is lit, one or more zones are bypassed.
* Key - Serves as a clear or reset key. If an error is made while entering digits, press this key to clear the error. Master clear is 3 presses.
# Key - This key is currently a duplicate of the Bypass key.
Numerical Keys - Used for entry of passcodes, programming, etc. Keys 2 - 9 also have an assigned alpha character for entering text.
ELK and Arrow Keys - The ELK and arrow keys have powerful functionality for both normal operation and programming. Pressing the
ELK key displays relative information according to each application. The arrow keys allow scrolling through all available options. The user
can activate or select the displayed option by pressing the right arrow key. Once an option has been selected, the user may be prompted
for a passcode. Additional sub-menu options may appear to assist. The user may return to the status screen by pressing the * key.

M1G Installation and Programming
Page 16
Access to menus 1 to 5 can be restricted via programming to only Users that have “User Code Option 8” set. Menus 6 & 8
required a Master or Installer Code. Menu 9 requires the Installer Code. Press ELK to begin, then press the UP or DOWN
arrow key to select a menu. Enter a code if prompted. To select a menu press the RIGHT arrow key.
Keypad Menus
Allows viewing or controlling of the automation functions such as Tasks, Lighting, Outputs,
Temperature Sensor, Keypad Temperature, and Thermostats. Press the RIGHT arrow key to
select, then choose the desired function using the UP or DOWN arrow keys.
NOTE: The automation functions must be assigned and named using the ELK-RP software.
In most cases they cannot do anything unless they have been written into one of the
“Whenever/And/Then” automation rules.
† Tasks are like 1 button macros, performing multiple jobs with one push. To activate a task
press the RIGHT arrow key and press UP or DOWN to scroll through the list of available tasks.
To jump directly to a particular task, enter it’s two digit number. Once the task is displayed, all
it takes to activate it is to press the # key. A rule to use the “Water the Lawn” task might be:
WHENEVER “Water the Lawn” IS ACTIVATED THEN TURN ON Valve 19 FOR 5 MINUTES, etc.
† Lighting allows the individual control of lights and/or appliances which have been assigned
through the ELK-RP software. Press the RIGHT arrow key to select Lighting, then press the
UP or DOWN arrow keys to scroll through the list. If you know the three digit number, you may
enter it to jump directly to that Lighting/Appliance. The current state of the unit will be
displayed. Press the # key to toggle (change) the unit from on > off or from off > on.
Outputs might be relays or voltages used to actuate something like a motor, fan, pump, etc.
Outputs can be turned on or turned off from this menu. Press the RIGHT arrow key to select
Outputs, then press the UP or DOWN arrow keys to scroll through the list. If you know the
three digit number, you may enter it to jump directly to that Output. The current state of the
output will display. Press the # key to toggle (change) the output from on > off or from off > on.
Remote “Zone” Temperature Sensors can be read from this menu. Press the RIGHT arrow
key to select this menu, then press the UP or DOWN arrow keys to scroll through the list of
available sensors. To jump directly to a particular sensor enter it’s two digit number. The
current temperature will be displayed. Press the * key to exit.
Keypad Temperature Sensors can be read from this menu. Press the RIGHT arrow key to
select this menu, then press the UP or DOWN arrow keys to scroll through the list of available
keypads. To jump directly to a particular keypad enter it’s two digit number. The current
temperature at the keypad will be displayed. Press the * key to exit.
† Thermostats can be read from this menu. Press the RIGHT arrow key to select this menu,
then press the UP or DOWN arrow keys to scroll through the list of available thermostats. To
jump directly to a particular thermostat enter it’s two digit number. The current temperature at
the thermostat will be displayed. Press the * key to exit.
Used for resetting latched smoke detectors after a fire alarm activation..
Press the RIGHT arrow key to actuate the Reset Smoke Detector feature. This causes the
power to smoke detectors to be removed for 5 seconds. During this time all fire zones will be
ignored to keep an accidental alarm from occurring.
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
1-View/Control r
Automation Fncts
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
2-Reset r
Smoke Detectors
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
READY TO ARM
9:00AM 08/01/03
Continued on next page..
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
3-Outputs r
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
Pump Motor Cntrl
001:=Off, # to Chg
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
2-Lighting r
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
1-Tasks r
123456789012345678901234567890
12345678901234567890123456789
0
12345678901234567890123456789
0
12345678901234567890123456789
0
12345678901234567890123456789
0
12345678901234567890123456789
0
12345678901234567890123456789
0
12345678901234567890123456789
0
123456789012345678901234567890
Water The Lawn
01: # Activates
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
Kitchen Lights
001:=Off, # to Chg
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
5 Seconds Smoke
Output Reset r
The control offers extended Menu Options via the center navigation “ELK” key. Some menus
may require a valid code to authorize. The Factory Default Code for USER Code 1 is: 3 4 5 6
(1 2 3 4 5 6 if the six digit code option is enabled)
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
4-Temperature r
Sensor
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
Outside
S01:=032 Degrees
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
5-Keypad r
Temperature
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
Keypad 01
K01:=073 Degrees
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
6-Thermostat r
Temperature
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
Hallway
T01:=072 Degrees
† Not evaluated by UL

M1G Installation and Programming Page 17
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
3-Walk Test Area r
< Area? Name >
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
4-View History r
Log
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
6-Change r
User Codes
Requires Master or
Installer Code
Menu 3 permits a local walk test of all zones assigned to this keypad’s area. The siren(s) and
communicator are disabled during a walk test. Press the RIGHT arrow key to begin a Walk
Test. The keypad displays the total tested zones adjacent to the total number of zones involved.
When a zone is activated, it’s name is displayed across the bottom and can be audible if the
Chime mode is on.
Allows viewing of the past 512 activities stored in the history log. Press the RIGHT arrow key to
view. History activities include: Arm, Disarm, Alarm, Trouble, etc. The top line displays the Log
number, Mth/Day, Time, and event description. The log can ONLY be cleared from ElkRP.
L001 is always the most recent event. Press the UP or DOWN arrow keys to move forward and
back. Event 512 will be the oldest event. The bottom line displays the event description, the
extended data (zone, user, etc.) and the area number (A1-A8).
Allows viewing of the current status of all zones. Press the RIGHT arrow key to select. Press
UP or DOWN to scroll through the zones or enter a three digit number to jump directly to a
particular zone. I.E. for zone 16 enter 016. Press the * key to exit.
For changing a user code and/or name for codes which have been previously enabled by the
Installer. Only a Master code OR the installer code can access this menu. Press the RIGHT
arrow key to begin. Press UP or DOWN keys to locate a user, or enter 3 digits to jump. Press
RIGHT arrow key to view the existing code. To change, enter the new code digits and listen for 3
beeps to confirm. To edit the name, press the RIGHT arrow key once, then press the DOWN
arrow key. Enter the text using the letters on the keys. I.E. For “K” press the 5 key twice. Move
RIGHT or LEFT with the arrow keys. Press Chime to insert a space. Press Bypass to erases a
letter. The UP and DOWN arrow keys shift from upper to lower case letters. Press the ELK key
to save and exit.
.
Allows an end user to change up to 20 settings incorporated into an automation rule. These
settings can be: time of day, time duration (seconds), or a numeric value. Each custom setting
has a reference number (CS) and a text description: I.E. CS01: Sprkl On 00:00 [Time] implying
a time of day setting. Press the RIGHT arrow key to begin.
Press the UP or DOWN arrow keys to locate a setting, then press the RIGHT arrow key to
select. Enter the new value and press the ELK key to save and exit.
Menu 8 consists of 8 sub-menus used for advanced system settings. Press the right arrow key
and enter a valid user code. Press the UP or DOWN arrow keys to select a sub-menu or enter
the one digit number to jump directly to any sub-menu. I.E. enter 6 to jump to 86.
To set the system clock press the RIGHT arrow key, then press the UP or DOWN arrow key to
select the day. Next, press the RIGHT arrow key to move to Date/Time setting. Enter two digits
for month, date, year, hour, and min. To exit press the * key.
To set the volume for output 1 voice messages (non-alarm) press the RIGHT arrow key and set
desired volume with the UP or DOWN keys. There are 8 settings (0-7). WARNING: PROTECT
EARS! Each adjustment broadcasts a test message through Output 1. To exit press the * key.
To set keypad adjustments press the RIGHT arrow key. Then press the UP or DOWN keys to select
one of the three options.
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
8-System r
Settings
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
83-Keypad r
Adjustments
1234567890123456789012345678901
1
23456789012345678901234567890
1
1
23456789012345678901234567890
1
1
23456789012345678901234567890
1
1
23456789012345678901234567890
1
1
23456789012345678901234567890
1
1
23456789012345678901234567890
1
1
23456789012345678901234567890
1
1234567890123456789012345678901
1:Set Keypad r
Beep Tone
1234567890123456789012345678901
1
23456789012345678901234567890
1
1
23456789012345678901234567890
1
1
23456789012345678901234567890
1
1
23456789012345678901234567890
1
1
23456789012345678901234567890
1
1
23456789012345678901234567890
1
1
23456789012345678901234567890
1
1234567890123456789012345678901
2:Set Keypress r
Beep Volume
1234567890123456789012345678901
1
23456789012345678901234567890
1
1
23456789012345678901234567890
1
1
23456789012345678901234567890
1
1
23456789012345678901234567890
1
1
23456789012345678901234567890
1
1
23456789012345678901234567890
1
1
23456789012345678901234567890
1
1234567890123456789012345678901
3:Set Backlight r
Dim Level
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
82-Out1 Voice
Adjust Volume r
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
81-Set Sys Clock r
24hr format
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
000of016 Tested r
A?-Violate Zones
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
L001:01/01bb
bb
b08:00
AreaArmed 103A1
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
001:Selbb
bb
b Prgr
< User Name >
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
7--Automation r
Custom Settings
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
CS01:bb
bb
b00:00Timer
Sprklr On
Requires Master or
Installer Code
Requires Master or
Installer Code
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
5-View Status r
of all zones
To set keypad beep tones press the RIGHT arrow key, then select the desired tone using the UP or
DOWN keys. There are 9 settings (0-8). When done, exit by pressing the * key.
To set key-press beep volume press the RIGHT arrow key, then select the desired volume using
the UP or DOWN keys. There are 7 volume levels (1-7) plus Off (0). To exit press the * key.
To set backlight dim level press the RIGHT arrow key, then select the desired level using the UP or
DOWN keys. There are 9 backlight levels (1-9) plus Off (0). The keypad automatically dims to this
setting after 30 seconds of no activity in order to save energy. To exit press the * key.

M1G Installation and Programming
Page 18
To perform system tests press the right arrow key. Then press the up or down arrow keys to
select one of the three tests.
The control’s standby battery is load tested automatically every 24hrs. However, it can also be
manually load tested anytime using this option. Press the right arrow key to start the test. The
battery is placed under load for 30 seconds and the battery voltage and system current is
displayed. If the battery falls below a set level, a Low Battery trouble will occur. If it’s necessary
to replace the battery, this test should be used to test and clear a Low Battery Trouble condition.
To test the keypad’s LCD screen press the RIGHT arrow key. The entire screen should appear
black indicating all pixels are working. To exit press the * key.
To manually test the communicator (dialer) press the RIGHT arrow key. Testing is done using
the first phone number that is programmed to send a test code. If there is no phone number
programmed to send a test code, the test will end. To exit this menu press the * key.
There are two types of test, silent and monitored. To silently send a test press the right
arrow key from this display. To hear the test using the inside speakers (OUT1) press the up
or down arrow key to bring up the following display.
This unique feature permits you to hear or “monitor” a single communicator test using the
inside speakers (OUT1) eliminating the need for a telephone “Butt” set. Simply press the
right arrow key from this display to begin.
Similar to above, this works for multiple communicator tests. Press the right arrow key to
enable. Each communicator transmission will be monitored until mode is cancelled. Press
the star (*) key three times to cancel. Cancelled automatically after 24hr daily battery test.
This special option allows any pending (not reported) dialer communications to be cleared
or cancelled. Typically this will be used only for initial installation and testing.
NOTE: ALWAYS NOTIFY THE MONITORING STATION BEFORE TESTING THE DIALER! If the test
should fail, a Comm Fail trouble will occur. To clear a Comm Fail the dialer must be able to
complete a good communication.
To connect ELK’s Remote Program PC software (RP) via the user assisted method, press the
RIGHT arrow key and then select the connection mode with the UP or DOWN arrow keys.
1:Seize Line Attended Mode - 1) Allows RP connection to begin on an already established voice
connection between the control phone line and the RP Computer. 2) Also useful for manually
answering an incoming call from the RP Computer with programming Rings to Auto Answer.
2:Seize Line Unattended Mode - Pressing the RIGHT arrow key causes the control to dial the
programmed RP telephone number. The RP Computer must be in the “wait for call” mode.
NOTE: UL requires that a Technician be On-Site when doing Remote Programming.
This is a collection of tools for diagnosing system problems. Press the RIGHT arrow key and
enter a valid user code to begin. Press the UP or DOWN keys to select one of the four tools:
This tool is for use in conjunction with Tech Support to diagnose data bus retries and errors. It
displays the device type and number of retries accumulated since the last power-up. T=Device
type, A=The Address within the device type
This tool displays the control’s voltage and average current being drawn from the power supply.
This tool allows the voltage on each zone to be displayed in real time. It changes as contacts
or devices are violated. Press the RIGHT arrow key to begin.
Use the UP or DOWN keys to scroll through each zone. The displayed information consists of:
the present zone voltage, the L low and H high alarm thresholds, and the analog (A to D)
equivalent of the zone voltage..
This is a read only screen displaying the telephone line voltage during the last on-hook
condition. It is an approximate measurement accurate to only +-20%.
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
85-Connect ‘RP’ r
Remote Program
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
2:LCD Test r
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
3:Communicator r
Manual Test
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
1:Seize Line r
Attended Mode
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
2:Seize Line r
UnAttended Mode
1234567890123456789012345678901
1
23456789012345678901234567890
1
1
23456789012345678901234567890
1
1
23456789012345678901234567890
1
1
23456789012345678901234567890
1
1
23456789012345678901234567890
1
1
23456789012345678901234567890
1
1
23456789012345678901234567890
1
1234567890123456789012345678901
86-System r
Diagnostics
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
1:DataBusErrors b
T2A1 Retry 00000
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
2:Sys Volt/Curr b
13.8V 0.440Amps
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
3:Zone=001 Volts
Display Level r
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
4:LastOnHookTele
Line V=57,+-20%
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
Zn=001 Volt=07.2
L04.6 H09.0 A132
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
1:Battery Test r
for 30 Seconds
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
84-System r
Tests
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
Send Test r
Silently
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
Send Test w/ r
speaker monitor
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
Turn Butt Set r
Monitor Mode On
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
Clear Pending r
Dialer Reports

M1G Installation and Programming Page 19
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
9-Installation r
Programming (0)
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
87-Custom
Message Record r
†This option is used in conjuction with a house telephone (microphone) to record up to 10
custom voice messages. Each message occupies a 6 second block. Two or more
consecutive blocks may be linked together for longer times. Total record time cannot exceed
60 seconds. These messages require the Elk-RP software, which utilize these messages
together with the built-in 500+ word vocabulary to construct voice phrases for many uses,
including the voice dialer. Press the RIGHT arrow key to begin custom message record.
Selects any one of the custom messages (VM01-VM10) for playback or recording. Press the
UP or DOWN arrow keys to select. To Play the selected message press the RIGHT arrow key.
The message will play through Output 1 speakers. To record a new message press the LEFT
arrow key. To exit press the * key.
This sets the number of consecutive 6 sec. record blocks. The default is 01 blocks which is
normally long enough for most applications. However, to create a longer message press the
RIGHT arrow key and enter the number 01 to 02, etc. NOTE: Creating longer messages
reduces the total number of custom messages. This screen also allows all messages to be
played “PlayAll” by pressing the RIGHT arrow key. When ready to record press the LEFT arrow
key.
This is the prerecord screen. To begin recording: 1) lift the house phone (off hook), 2) press
the LEFT arrow key, 3) start speaking. To stop recording press the “0” key. If stop is not
pressed, recording will automatically end after 6 sec. (or the total number of blocks times 6
seconds).
NOTE: A local house phone is used as the microphone. Installer programming menu 07,
option 1, must be set to a 1 in order for the local phone to be recognized by the control.
This will display as soon as recording has stopped. To play the new message press the
RIGHT arrow key. To record the message again press the LEFT arrow key and follow the
same procedures again. To exit press the * key.
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
VM01b 1 Block(s)
Record< Play>
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
6 Sec Blocks=01b
Record< PlayAll>
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
6 Sec Blocks=01b
Rec< LiftPhone!
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
VM01b 1 Block(s)
Record< Play>
Step by step summary of procedures for recording a custom message:
1) Verify that a house telephone is connected to the control’s T1 and R1 terminals and that Installer menu 07, option 1
is set to a 1. This allows the control to recognize the telephone and allow it to be used as a microphone.
2) Go to the user menu 8-System Settings by pressing the ELK key and entering 8. Press the rkey and enter a valid
user code. Press 87 to reach the custom message record screen.
3) Using the Up/Down arrow keys, select the voice message to record VM01 to VM10. There are 10 custom
messages.
4) Press the lkey and select the number of 6 second blocks for your message. Hint-rehearse and time the message,
if it is greater than 6 seconds then increase the number of consecutive blocks as required.
5) Lift the telephone handset and press the lkey to begin the recording. The recording will not start until the handset
is off-hook and the lkey is pressed.
6) Record your message by speaking into the handset. If the message is shorter than the amount of time selected
then press 0 to stop recording. Otherwise, recording will stop when the number of blocks is reached.
7) Press the Right arrow key to play the message. The message will be heard through the telephone handset if it is
still off-hook. Otherwise the message will be directed to the amplifier connected to output 1.
Requires
Installer
Code
From this menu you may press the RIGHT arrow to enter Installation Level Programming. If
the Installer Programming Code has not already been entered it will be required at this time.
REFER TO PAGE 22 FOR PROGRAMMING INSTRUCTIONS
† Not evaluated by UL
NOTE: The Remote Programming RP software can be used to lockout certain local program capabilities for “anti-takeover”
purposes. The number in the lower right corner of this menu will indicate the level of lockout as follows:
(0) = No lockout,
(1) = Lockout Telephone number programming - view everything - cannot restore program defaults.
(2) = Lockout ALL programming - view everything - cannot restore program defaults
(3) = Lockout ALL Programming and Viewing - cannot restore program defaults. This level can only be set or removed
from the ELK-RP Software.

M1G Installation and Programming
Page 20
Menu 0 - Select Keypad Alternate Area - Multi-area (Partition) Operation
Press the RIGHT arrow key to select this menu and display the following:
Enter a valid user code. The control does not allow (restricts) mapping or viewing of
areas that are not authorized for the user code.
MAPPING TO AN INDIVIDUAL AREA
Enter an area number from 1 to 8 OR scroll UP and DOWN with the arrow keys.
Press the Right Arrow key to map the Keypad to the area shown. The LCD display
and the Ready / Armed LEDs will show the status for the mapped area for 1 minute.
During this minute, it is possible to arm, disarm, bypass, etc. the mapped area from
this keypad. Each time a key is pressed the 1 minute is restarted. However, after 1
minute of no keypress activity, the keypad will return to its original primary assigned
area.
ACCESSING ACONSOLIDATED DISPLAYOF ALL VALID AREAS
Entering “0” for the area number immediately maps the Keypad to a consolidated
‘snapshot’ of all authorized areas. This permits quick arming and disarming only. If an
area is not ready to arm it will be necessary to map individually to that area to view the
violated zone(s) and either secure or bypass them prior to arming.
This example shows all 8 areas, meaning that the User Code was valid for all 8.
The display only shows the areas for which the user code is authorized.
This menu allows the keypad to be mapped temporarily to any other area, allowing multi-area (partitioned) operation.
An individually mapped area can be armed, disarmed, and controlled just as if the keypad were permanently assigned
to that area. It may also be used to access a consolidated display of all areas at once, showing the status of each
area.
To reach the keypad menus press the center navigation key labeled “ELK”. A user code may be required depending on
how the control is programmed. The four arrow keys around the Elk key are used to scroll, backup, etc. Pressing the
RIGHT arrow key will select the displayed menu.
1. Press the ELK key. Enter a user code if prompted.
2. Use the UP or DOWN arrow keys to find menu “0-Select Keypad Alternate Area”.
1234567890123456789012345678
1
23456789012345678901234567
8
1
23456789012345678901234567
8
1
23456789012345678901234567
8
1
23456789012345678901234567
8
1
23456789012345678901234567
8
1
23456789012345678901234567
8
1
23456789012345678901234567
8
1
23456789012345678901234567
8
1234567890123456789012345678
0-Select Keypad
Alternate Area r
1234567890123456789012345678
1
23456789012345678901234567
8
1
23456789012345678901234567
8
1
23456789012345678901234567
8
1
23456789012345678901234567
8
1
23456789012345678901234567
8
1
23456789012345678901234567
8
1
23456789012345678901234567
8
1
23456789012345678901234567
8
1234567890123456789012345678
Auth. Required
Enter Valid PIN
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
ChangeKPArea-1
r
[Area Name] A1
Note the letter beneath each area number.
The single upper case “X” indicates the primary area. This area is controlled exclusively from
the regular operation screens.
A lower case “r” below an area indicates the area is Ready to Arm.
A lower case “n” below an area indicates the area is Not Ready.
A upper case “A” below an area indicates the area is Armed.
This example shows the user code was only authorized for areas 1, 2, and 3. The
unauthorized area(s) have a “-” below them.
To change or ‘toggle’ the arm status of an area, press the number key representing
the area number. IMPORTANT: The area status is not “real time”. It is a snapshot
taken when the RIGHT arrow key was pressed. If a zone has since become violated
the area will still be displaying “r”, however the letter will immediately change to “n”
and the keypad will emit an error tone when an attempt is made to arm by pressing
the area number.
When finished, press the “*” key to exit.
123456789012345678901234567890
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
1
2345678901234567890123456789
0
123456789012345678901234567890
ChangeKPArea-0 r
0=All Areas
12345678901234567890123456789
1
234567890123456789012345678
9
1
234567890123456789012345678
9
1
234567890123456789012345678
9
1
234567890123456789012345678
9
1
234567890123456789012345678
9
1
234567890123456789012345678
9
1
234567890123456789012345678
9
1
234567890123456789012345678
9
12345678901234567890123456789
Area# 12345678
Status X r r r r r r r
12345678901234567890123456789012
1
234567890123456789012345678901
2
1
234567890123456789012345678901
2
1
234567890123456789012345678901
2
1
234567890123456789012345678901
2
1
234567890123456789012345678901
2
1
234567890123456789012345678901
2
1
234567890123456789012345678901
2
1
234567890123456789012345678901
2
12345678901234567890123456789012
Area# 12345678
Status X r r - - - - - r
This manual suits for next models
3
Table of contents
Other Elk Products Control Panel manuals
Popular Control Panel manuals by other brands

CAME
CAME ZE5 V.7 installation manual

Hoftronic
Hoftronic 5422300 user manual

Protect America
Protect America Simon XT installation manual

Chamberlain
Chamberlain LiftMaster Professional CB124 instructions

Groupe Atlantic
Groupe Atlantic NAVISTEM B1000 Instructions for installation, use and maintenance

Well SEC
Well SEC WL1014 user manual