Elka 135 16 140 User manual

KNX Metering gateway
Art. No. : 135 16 140
Operating instructions
1 Safety instructions
Electrical devices may only be mounted and connected by electrically skilled
persons.
Serious injuries, fire or property damage possible. Please read and follow manual fully.
Danger of electric shock. During installation and cable routing, comply with the
regulations and standards which apply for SELV circuits.
Fire hazard. Only use limited-capacity power sources according to EN 60950-1. Observe
the technical data.
These instructions are an integral part of the product, and must remain with the end
customer.
2 Device components
Figure 1
(1) Connection for M-bus devices
(2) Connection for wM-bus antenna
(3) Ethernet connection
(4) D0 connection for optical communication head
(5) Slot for micro SD card
(6) For future expansions; has no function
(7) Two S0 connections
(8) Power supply connection
(9) KNX connection
(10) Status LEDs
KNX Metering gateway
1/9
82594604 05.02.2016

3 Function
System information
This device is a product of the KNX system and complies with the KNX directives. Detailed
technical knowledge obtained in KNX training courses is a prerequisite to proper understanding.
The function of this device depends upon the software. Detailed information on loadable
software and attainable functionality as well as the software itself can be obtained from the
manufacturer´s product database.
Planning, installation and commissioning of the device are carried out with the aid of KNX-
certified software. Full functionality with KNX commissioning software version ETS4.2 and
higher.
An updated version of the product database and technical descriptions are available on our
Internet website.
System information M-bus / wireless M-bus
Detailed information about the function and commissioning of M-bus and wireless M-bus
devices is a prerequisite to complete understanding of these instructions.
Intended use
- Transmission of measurement values from metering systems with M-bus, wireless M-bus,
D0 or S0 interfaces in KNX systems
- Mounting on DIN rail according to EN 60715
Figure 2: Overview of connectable measurement points
Product characteristics
- Acquisition of consumption data from energy, water, gas or other meters
- Data acquisition via 2 S0 interfaces, 1 D0 interface, 1 M-bus interface, 1 wM-bus interface
- M-bus/wM-bus: Integration of up to 20 meters (depending on number of data sets)
- Slot for micro SD card for continuous data recording
- Ethernet interface
- Integrated web server function to visualize values on PC or mobile devices
- Decoding of AES-encoded wM-bus data
- Bus connection with standard bus connecting terminal
A selection of appropriate meter types is available in the compatibility list on our Internet
website.
2/9
KNX Metering gateway
82594604 05.02.2016

4 Operation
LED function
The LEDs indicate the device and communication statuses. Depending on the direction of
communication, the LED signals may overlap or only be displayed briefly.
Power/Error:
Red: Internal error
Red flashing: Error during KNX commissioning
Yellow: External commissioning (meter scan) active
Yellow flashing: Commissioning; KNX parameters loading
Green: Normal operation
Green/red flashing: Updated firmware loading from micro SD card
LAN:
Yellow flickering: Data traffic via Ethernet connection
M-Bus:
Red: No meter detected during commissioning.
Red flashing: Not enough memory for all M-bus and wM-bus meters
Yellow: Data reception
Green: Transmitting
wM-Bus:
Red: Internal error
Yellow: Receiving
Green: Transmitting (only during meter commissioning)
D0:
Red: No communication with meter
Yellow: Receiving
Green: Transmitting (depending on meter)
S01 and S02:
Flashing (about 1.2 seconds): Impulse recognized.
SD-Card:
Red: Writing on micro SD card is not possible.
Red flashing: Micro SD card full
Yellow flashing: Reading micro SD card
Green blinking: Writing on micro SD card
Insert micro SD card into gateway
An inserted micro SD memory card allows measurement data to be collected on site. The
memory card can be read out with a card reader.
oFormat micro SD card as FAT32.
oInsert micro SD card into slot (5).
The card is automatically recognized by the device.
Remove micro SD card from gateway
Make sure that no writing cycle is active. The SD-Card LED must not light.
oRemove micro SD card from slot (5).
iA suitable card reader can be used to read out the saved data. Details for reading out data
are contained in the technical documentation.
5 Information for electrically skilled persons
DANGER!
Electrical shock on contact with live parts in the installation environment.
Electrical shocks can be fatal.
Before working on the device, disconnect the power supply and cover up live
parts in the working environment.
3/9
KNX Metering gateway
82594604 05.02.2016

5.1 Fitting and electrical connection
Fitting the device
Observe the temperature range. Ensure adequate cooling.
oMount device on DIN rail.
Connecting the device
iWhen selecting the measurement points to be connected and when laying cable, make
sure all dangerous voltages have been disconnected. All connected circuits must be SELV
circuits.
iCaution! Possible device damage due to electromagnetic coupling. Avoid looping with
other circuits or components. Position measurement point gateways as centrally as
possible and guide cables along the supply cables. As needed, use surge protection with
coarse, medium and fine protection.
Figure 3: Avoid looping with other circuits or components
Use a separate power supply for each measurement point gateway (accessories).
oConnect the power supply to terminal (8).
oConnect KNX to terminal (9) via a connecting terminal.
oOptional: Connect PC, IP router, etc., to socket (3).
Observe maximum number of connectable measurement points.
oConnect measurement points to connections M-Bus (1), D0 (4), S01 or S02 (7). Connect
antenna for wireless-M-bus to socket wM-Bus (2). See following section.
4/9
KNX Metering gateway
82594604 05.02.2016

Figure 4
Connect PC or router
Saved data can be read out via the integrated Ethernet interface (3). A PC or a mobile device
can be connected either directly, via a network distributor or via a router.
Figure 5: Connection example for PC or router
Use network cables with RJ45 connectors.
oConnect Ethernet cable to socket (3).
Connect measurement points to M-bus interface
5/9
KNX Metering gateway
82594604 05.02.2016

Figure 6
Use, e.g., J-Y(St)Y 2x2x0.8 as bus cable.
oConnect measurement points to M-bus connection at terminal M-Bus (1).
Connect antenna for measurement points with wireless M-bus interface
Figure 7
oPlace the antenna outside of the distribution board and insert antenna cable into the
distribution board. Ensure safe isolation from other voltages.
Transmission quality depends on the distance from the measurement point as well as the
transmission field strength of the measuring point. To ensure good transmission quality, keep a
sufficient distance from possible interference sources, e.g., metallic surfaces, microwave ovens,
hi-fi and TV sets, ballasts or transformers.
oInsert the antenna connector into the wM-Bus socket (2).
oRelive strain on antenna cable.
Connect measurement points with S0 interface
iOnly connect measurement points which ensure safe isolation from other voltages!
6/9
KNX Metering gateway
82594604 05.02.2016

Figure 8
Use, e.g., J-Y(St)Y 2x2x0.8 as bus cable.
oConnect a measurement point to each connection, S0 1 or S0 2.
Connect measurement point with D0 interface
Figure 9
oUse RJ10 connector to connect D0 measurement head to socket (4).
oSet optical communication head on the measurement point optical interface.
oRelive strain on cable.
iTo prevent manipulation of communication head (e.g. pulling from measurement point) by
unauthorized persons, access to the measurement point should be locked.
5.2 Commissioning
Load the address and the application software
oSwitch on the bus voltage.
oAssign physical address.
oLoad the application software into the device.
7/9
KNX Metering gateway
82594604 05.02.2016

oNote the physical address on the device label.
Setting IP address
Necessary when connecting a PC or router to the integrated Ethernet interface. The IP address
can be allocated statically or dynamically via DHCP.
oFor static setting: Enter IP address in the ETS.
oWhen setting via DHCP: Take IP address from the router's address table.
Commissioning M-bus
If M-bus is activated, the connected measurement points are automatically scanned and
allocated according to their secondary addresses. Primary addressing is not supported.
Commissioning the wireless M-bus
Wireless M-bus measurement points cannot be scanned; they can only be received. The
measurement points are recognized and allocated by means of their secondary addresses.
6 Appendix
Simplified Declaration of Conformity
Hereby Elka Elektronik GmbH declares that the radio system type
KNX measurement point gateway, art. no. 13516140
corresponds to the directive 2014/53/EU. The complete text of the EU Declaration of Conformity
is available under the Internet address:
www.elka.de/compliance
Legal Notice
This product incorporates open source software components covered by the terms of third party
copyright notices and/or license agreements. Details for addressing are contained in the
technical data.
6.1 Technical data
External supply
Rated voltage DC 24 V ±10 % SELV
Power consumption 6.5VA
Power supply Max. 50 W / 2 A
Connection mode Screw terminal
Protection class III
Ambient conditions
Ambient temperature -5 ... +45°C
Storage/transport temperature -25 ... +70°C
Fitting width 72mm / 4modules
Weight approx. 175g
Network communication
IP communication Ethernet 10/100
IP transmission rate 10 / 100Mbit/s
IP connection mode RJ45 socket
Number of measurement points
M-bus and wireless M-bus max. 20
S0 2
D0 1
M-Bus
Rated voltage, M-bus DC 36VSELV
Transmission rate 2400 bit/s
Connection Screw terminals
wireless M-Bus
Reception frequency 868.0 ... 868.6MHz
Operating modes T1 / S1
Antenna connection SMB socket
8/9
KNX Metering gateway
82594604 05.02.2016

Antenna cable length max. 3 m
Receiver category 2
S0 connections
Number 2
Current approx. 14mA
Connectable measurement points 2× 1
Connection mode Screwless terminal
D0 connection
Standard IEC 62056-21 (IEC 61107)
Communication RS232
Connectable measurement points 1
Connection RJ10
D0 cable length max. 3 m
Micro SD slot
Memory card Micro SDHC, max. 32 GB
6.2 Accessories
Power supply 24 V DC/0,4 A Art. No. 140 01 913
Wireless M-Bus antenna Art. No. 110 01 312
D0 sensor Art. No. 110 01 212
6.3 Warranty
We reserve the right to make technical and formal changes to the product, as long as they are
the result of technical progress.
Our products are under warranty within the scope of the statutory provisions.
Please return the device, postage paid, to our central service department, giving a brief
description of the fault:
ELKA-Elektronik GmbH
ServiceCenter
Hohe Steinert 10
58509 Lüdenscheid
Germany
Tel.: +49 2351 176-4440
Fax: +49 2351 176-4900
www.elka.de
ELKA-Elektronik GmbH
Hohe Steinert 10
58509 Lüdenscheid
Deutschland
Tel.: +49 2351 176-0
Fax: +49 2351 176-1780
www.elka.de
9/9
KNX Metering gateway
82594604 05.02.2016