Elmdene G240 BMU Series User manual

1
Technical Support: +44(0)23 9269 6638 (option 3) PAK20056 _01B ©2016 ELMDENE INTERNATIONAL LTD
27.6V
DC
S
WITCH
M
ODE
P
OWER
S
UPPLY
M
ODULES
W
ITH
B
ATTERY
M
ONITORING
Models:
G240x MU
Where ‘x’ is max load current: 1A, 2A, 3A or 5A
F
EATURES
High efficiency cost effective power supply ideal for use in Fire, Access Control and General Security
applications. Featuring a regulated 2 .6Vdc output supplying continuous full rated current to load and up to
an additional 0.5A for charging 2 x 12V standby batteries. Maximum battery life is assured using Deep
Discharge Protection to prevent premature battery failure when operating in standby mode for extended
periods. Two sets of volt-free contacts are provided to signal (i) loss of mains and (ii) battery and loss of
output faults. The universal mains input voltage enables the power supply to be used across a wide
geographical area. The highly efficient switch mode design ensures low operating costs while generating less
heat. The modular construction simplifies maintenance.
•Universal mains input voltage 90-264Vac
•Additional 0.5A to charge 2 x 12V standby batteries
•High efficiency electronics for reduced running costs and lower
operating temperatures
•Continuous full rated current to load
•Volt free contact signalling mains failure
•Volt free contact signalling battery and output faults
•Deep Discharge Protection
•Installer safe design with all high voltage electronics fully shrouded
•Reverse battery connection protection
•Full electronic short circuit and overload protection on load output
•Mains transient protection circuit
•Modular construction for ease of maintenance & installation
•Green Mains present LED
•Orange Battery Charging LED
•Yellow Fault LED
Elmdene International Ltd
Tel: +44 (0)23 9269 6638
3 Keel Close, Interchange Park, Fax: +44 (0)23 9266 0483
Portsmouth, Hampshire, PO3 5QD, UK
Web: www.elmdene.co.uk

2
Technical Support: +44(0)23 9269 6638 (option 3) PAK20056 _01B ©2016 ELMDENE INTERNATIONAL LTD
S
PECIFICATION
Input Specification
Voltage (rated)
100
-
240Vac
Voltage (operating)
90
-
264Vac
Frequency
50
-
60Hz
Ma
x Current
See Model Specification T
able
Mains Input Fuse
See Model Specification Table
Max standby Power
0.8W (n
o load
and no battery
connected)
Output Specification
Voltage
2 .0 – 28.0Vdc (2 .6vdc nominal) on mains power
21.0 – 24. Vdc on battery standby
Max load current
See Model Spe
cification Table
Ripple
10
0 mV pk
-
pk max
Load output Fuse
See Model Specification Table below
Overload
Electronic shutdown until overload or short circuit removed
(under mains power only)
Local Indicators
MAINS LED
(Green)
FAULT LED
(Yellow)
Charge L
ED
(Orange)
Status
ON
OFF
OFF
NORMAL
-
Battery fully charged
ON
OFF
ON
NORMAL
-
Battery charging
ON
1s ON, 1s OFF
ON or OFF
FAULT
-
See signalling outputs
OFF 0.1s ON, 3s OFF OFF
FAULT
-
Mains Loss; PSU operating under standby
battery
OFF
OFF
OFF
FAU
LT
-
No Output, Mains and Battery Loss
Standby atteries
Battery Type
2 x 12V Valve Regulated Lead Acid
Battery Charging Fuse
protection
See Model Specification Table
Battery Re
-
Charge Time
< 24hr (to 80% of 8Ah capacity)
Signalling Outputs
GEN Fault
(general)
0.1 A @ 60 VDC N/O volt
-
free contact.
Open when battery disconnected, output fuse fail, battery fuse fail,
output short circuit or low output voltage.
EPS Fault (mains)
0.1 A @ 60 VDC N/O volt
-
free contact.
Open when loss of mains for more than 8s

3
Technical Support: +44(0)23 9269 6638 (option 3) PAK20056 _01B ©2016 ELMDENE INTERNATIONAL LTD
Mechanical
Model G2401 MU / G2402 MU G2403 MU / G2405 MU
Module
Dimensions
w x h x d (mm / external) 152 x 106 x 52 15 x 143 x 55
Recommended Batteries 2 x 12V NP or NP1
Weight (excluding batteries)
G2401 MU / G2402 MU G2403NU / G2405NU
280g 650g
Environmental
Temperature -10 to +40°C (operating) 95% RH non-condensing
-20 to +80°C (storage)
Connections
+O/P +ve voltage O/P to load equipment
-O/P -ve voltage O/P to load equipment
+BATT Red lead to standby battery 1
-BATT Black lead to standby battery 2
GEN FAULT Volt-free contacts for general faults
EPS FAULT Volt-free contacts for loss of mains indication
O
PERATION
This unit is intended for use by Service Personnel only - There are NO USER SERVICEABLE parts inside.
The Green Mains LED will be illuminated whilst the mains supply is present. In the event of a fault condition,
the Yellow Fault LED will be illuminated. The Orange Battery Charging LED will be illuminated when the
battery is not fully charged and is charging normally. When the battery is fully charged it will be
extinguished.
I
NSTALLATION AND
S
ET
-U
P
This unit is only suitable for installation as permanently connected equipment. The PSU is NOT SUITABLE for
external installation. EQUIPMENT MUST BE EARTHED. Before installation, ensure that external disconnect
device is OFF. The PSU should be installed according to all relevant safety regulations applicable to the
application.
Module Enclosure & Mounting
This power supply module has high voltage present and is for use by Service Personnel only. This power
supply module MUST be securely mounted within a robust enclosure having suitable means to prevent
unintentional access to the module. Suitable notices must be affixed to the outside of the enclosure to warn
of high voltages present internally.
Mounting
1) Mount securely in correct orientation allowing minimum clearance of 20mm all round – see diagrams
below.

4
Technical Support: +44(0)23 9269 6638 (option 3) PAK20056 _01B ©2016 ELMDENE INTERNATIONAL LTD
E
N
L
2
0m m
20mm
2) The G2401BMU and G2402BMU modules have the option of either being DIN rail mounted (using the
integrated DIN rail mount) or by using appropriate fixings using the four available mounting lugs. The
G2403BMU and G2405BMU modules are fixed using the three available mounting points.
I
NSTALLATION AND
S
ET
-U
P
CONTINUED
Mains Power Up
3) Attach correctly rated mains cable (minimum 0.5mm
2
[3A], 300/500Vac) and secure in enclosure using
cable ties.
4) Apply mains power. Check for 2 .6Vdc on load outputs. Check Green Mains LED is on.
5) Disconnect mains power.
Load Output
6) Attach correctly rated load cable and secure in enclosure using cable ties. Note polarity.
) Apply mains power. Check green Mains LED is on.
8) NOTE: Yellow Fault LED may flash to indicate no battery has been connected; this is normal.
9) Verify load is operating correctly.
10) Disconnect mains power.
Signalling Outputs
11) Connect EPS and GEN fault outputs to appropriate inputs of control equipment.
Standby attery
12) Connect battery to terminal block using minimum 32/0.2 (1.0mm
2
CSA) stranded wire.
NOTE: ensure correct polarity of battery connections. Maximum recommended total battery lead
length = 500mm
13) Apply mains power. Check Green Mains LED is ON. Check Orange Charging LED is ON.
14) Check there is no fault indication on Yellow LED.
15) Disconnect mains power. Check that the batteries continue to supply voltage and current to the load.
Check Green Mains LED is OFF and the control panel displays a Loss of Mains (EPS) fault
NOTE: Batteries must have sufficient charge to supply the load
16) Reconnect mains power. Green LED should be on.
1 ) Remove Load fuse. Check Yellow Fault LED is ON and control panel shows General PSU fault.
18) Replace Load fuse. Check Yellow Fault LED is OFF and General PSU fault has cleared at control panel.
E
N
L
2
0m m
20mm
N E L
G240
1BMU &G2402BMU
G2403BMU & G2405BMU
N E L
L E N
L E N

5
Technical Support: +44(0)23 9269 6638 (option 3) PAK20056 _01B ©2016 ELMDENE INTERNATIONAL LTD
Module Dimensions
128
98
42,4
60
51
19
84
152
12
4
106
13
G2401BM & G2402BM
157
1
2
8
7
,
5
128
42,4
1
9
6
0
5
6
,
5
4
1
3
51
4
3
12
G2403BM & G2405BM
Fixing Holes Ø3.3mm
Recommended fixing screw M3

6
Technical Support: +44(0)23 9269 6638 (option 3) PAK20056 _01B ©2016 ELMDENE INTERNATIONAL LTD
M
AINTENANCE
There is no regular maintenance required of the PSU other than periodic testing and replacement of the
standby batteries. Reference should be made to the battery manufacturer’s documentation to determine
typical/expected battery life with a view to periodic replacement of the battery.
If the output of the PSU fails the cause of the failure should be investigated e.g. short circuit load. The fault
should be rectified before restoring power to the PSU. The fuses may need to be replaced. Ensure the
correct fuse rating and type is used.
Model Specification Table G2401BMU G2402BMU G2403BMU G2405BMU
Output Current 1A 2A 3A 5A
Max Mains Input Current (at 90Vac) 1.0A 1.3A 1.4A 2.0A
F1 - Mains Input Fuse (20mm HRC) T2.0A T2.0A T3.15A T3.15A
F2 - Output Fuse (20mm) F1.0A F2.0A F3.15A F5.0A
F3 - Battery Fuse (20mm) F1.0A F2.0A F3.15A F5.0A

Technical Support: +44(0)23 9269 6638 (option 3) PAK20056 _01B ©2016 ELMDENE INTERNATIONAL LTD
This p ge h s been intention lly left bl nk

8
Technical Support: +44(0)23 9269 6638 (option 3) PAK20056 _01B ©2016 ELMDENE INTERNATIONAL LTD
C
OMPLIANCE
This product meets the essential requirements of the following EU Directives:
Low Voltage: 2014/35/EU
EMC: 2014/30/EU
RoHS2: 2011/65/EU
WEEE: 2012/19/EU
D
ISPOSAL OF
P
RODUCT AT
E
ND OF
L
IFE
This product falls within the scope of EU Directives 2012/19/EU Waste Electrical and Electronic Equipment
(WEEE) and 2013/56/EU (Battery). At the end of life, the product must be separated from the domestic
waste stream and disposed via an appropriate approved WEEE disposal route in accordance with all national
and local regulations.
Before disposal of the product, the standby battery must be removed and disposed separately via an
appropriate approved battery disposal route in accordance with all national and local regulations. Package
used batteries safely for onward transport to your supplier, collection point or disposal facility.
See Specification for battery type information. The battery is marked with the crossed out wheelie bin
symbol, which may include lettering to indicate cadmium (Cd), lead (Pb), or mercury (Hg).
For more information see: www.recyclethis.info
Caution: Risk of explosion if b ttery is repl ced by n incorrect type.
Dispose of used b tteries ccording to the b ttery m nuf cturer’s
instructions nd ll loc l nd n tion l regul tions.
The p ck ging supplied with this product m y be recycled.
Ple se dispose of p ck ging ccordingly.
This manual suits for next models
7
Table of contents
Other Elmdene Control Unit manuals