2 Description
IP KNX interface • Version: 13.03.2017 • Technical changes and errors excepted.
1. Description
The IP KNX interface serves to transmit data between the Mobotix IP cameras and
the KNX bus system. For this purpose, the KNX telegrams are converted into the Ether-
net protocols and sent to the LAN in which the cameras are installed (and vice versa).
Features:
• Communication with 8 IP cameras with 8 input and 8 output objects each
• Transfer of the camera events to the KNX bus
• Controlling the camera via the KNX bus
• KNX Bus Terminal and Ethernet / IP Connection (POE)
• Suitable for IP cameras that meet the communication requirements as
described in the camera settings in the manual
Configuration is made using the KNX software ETS. The product file can be downloa-
ded from the Elsner Elektronik website on www.elsner-elektronik.de in the “Ser-
vice” menu.
1.0.1. Scope of delivery
•IPKNXInterface
1.1. Technical specifications
The product is compliant with the provisions of EC guidelines.
Housing Plastic
Colour White
Assembly Series installation on a mounting rail
Protection category IP 20
Dimensions approx. 53 x 88 x 60 (W x H x D, mm), 3 modules
Weight approx. 110 g
Ambient temperature Operation at 0...+65°C, storage at -40...+70°C
Ambient humidity max. 90% RH, avoid condensation
Operating voltage • POE (Power Over Ethernet), IEEE 802.3af, Category 1
• KNX bus voltage
Power on bus: 10 mA
Ethernet/IP connection LAN jack RJ45
KNX bus connection KNX +/- bus connector terminal
BCU type integrated micro-controller
PEI type 0
Group addresses max. 1,024
Assignments max. 1024
Communication objects 897