EMKO TRANS-SYNCRO User manual

TRANS-SYNCRO
AUTO START LOAD SHARE UNIT
Introduction Brochure. ENG TRANS-SYNCRO 01 V31 09/20
1. Introduction
1.1 General Specifications
TRANS-SYNCRO is an synchronising & load sharing unit for diesel, gas or gasoline generators.
The unit is an easy to use multi-generator loadshare system, designed to synchronise up to 32
generators including electronic and non-electronic engines.
- Multi genset load sharing (up to 32 gensets)
- kW and kVAr load sharing
- Busbar voltages and frequency measurements
- Dead bus sensing
- Bus failure detection
- Sequential set start
- Load dependent automatic start/stop
- Equal aging of gensets
- Manual voltage/frequency adjustment
- Direct/Reverse Governor andAVR control
-Auto adjust feature for Governor andAVR
- Volts, frequency and phase matching
- Synchroscope display
- Logic Controller functionality for PLC
- Black or gray theme selection for 4.3 TFT LCD screen
General Specifications:
"
1.2 Warranty
EMKO Elektronik warrants that the equipment delivered is free from defects in material and workmanship.
This warranty is provided for a period of two years. The warranty period starts from the delivery date. This
warranty is in force if duty and responsibilities which are determined in warranty document and instruction
manual performs by the customer completely.
1.3 Maintenance
Repairs should only be performed by trained and specialized personnel. Cut power to the device before
accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of these
solvents can reduce the mechanical reliability of the device. Use a cloth dampened in ethyl alcohol or
water to clean the external plastic case.

Ýçindekiler
A visual inspection of this product for possible damage occured during shipment is
recommended before installation. It is your responsibility to ensure that qualified mechanical
and electrical technicians install this product.
If there is danger of serious accident resulting from a failure or defect in this unit , power off
the system and seperate the electrical connection of the device from the system.
Keep the power off until all of the wiring is completed so that electric shock and trouble with
the unit can be prevented.
Before beginning installation of this product, please read the instruction
manual and warnings below carefully.
2. Installation
Ýçindekiler
2.1 Unit Configuration
Ýçindekiler
2.2 Panel Mounting
The unit is designed for panel mounting. Fixing is by two screw fixings.
Insert the unit in the panel cut-out from the front.
Insert the fixings in the slotted at the corners of the unit and tighten the fixing screws to secure
the unit against the panel.
1-
2-
During the equipment is putted in hole on the metal panel while mechanical
installation some metal burrs can cause injury on hands, you must be careful.
The unit can be programmed using the buttons and LCD display on the front panel or PC
Software.
2
!
!
Figure 2.1 Front View Figure 2.2 Panel Cut-Out
223mm
162mm
188.61mm
276.42mm
LOAD
ON
ü
LOG
PROG
ESC
MAN
AUTO TEST
ENGINE
RUNNING
RESET

2.3 Electrical Connection
3
TRANS-SYNCRO three phase connections schematic
c1-
The first and last units must be fitted with a 120 ohm resisýtor across H and L.
,
5- Current transformers secondary should be grounded. The CT of 5VA s recommended.
2-
3-
4-
i
Connect the unit as shown in the appropriate diagram. Be sure to connect the battery supply the right
way round
Screened cable must be used for connecting the communication The screen is grounded at one end
ONLY.
The CAN interface requires that a 120 Ohms terminator is fitted to each end of the communications
link. This termination resistor is fitted internally into the unit. So it is not required externally.
Screened cable must be used for connecting the CAN, ensuring that the screen is grounded at one end
ONLY.
Screened cable must be used for connecting the Magnetic Pickup, ensuring that the screen is
grounded at one end ONLY.
FUSE-1, FUSE-2, FUSE-3 : 2 A. T
FUSE-4, FUSE-5, FUSE-6 : 2 A. T
FUSE-7 : 10 A. T
FUSE-8 : 32 A. T
USB
PROGRAMMING
61
BATTERY -
BATTERY+ FUSE-7
1
62 63
EARTH
I
57565554535251
TRANSISTOR OUTPUT
MAX. 1 A
BATTERY+
Conf.Output-9
Conf.Output-8
Conf.Output-7
Conf.Output-6
Conf.Output-5
Conf.Output-4
Conf.Output-3
22
D+(W.L.)
Charge Alt.
23
Cabin Temp.
(Conf.Input-13)
24
Conf.Input-12
25
Conf.Input-11
26
Conf.Input-10
27
Conf.Input-9
28
Conf.Input-8
29
Conf.Input-7
30
Conf.Input-6
31
High Temperature
(Conf.Input-5)
32
Low Oil Pressure
(Conf.Input-4)
33
GCB feedback
(Conf.Input-3)
34
Remote Start
(Conf.Input-2)
35
BATTERY -
USB
HOST ETHERNET
RJ45
4
605958
Conf.Output-2 “Crank”
Conf.Output-1 “Fuel”
FUSE-8
TRANSISTOR OUTPUT
MAX. 15 A
46 47 48 49 50
Temperature Sender
Oil Pressure Sender
Sender Common
Configurable Analog Input-2
Level Sender or
Configurable Analog Input-1
3
5
14
L1
GENERATOR
BUS VOLTS
L2
L3
N
G
Generator
Contactor
Output
FUSE-1
FUSE-4
21 20 19 18
I
13 12 11
FUSE-2
FUSE-3
8A
4 3 8765
FUSE-5
FUSE-6
17
L1
L2
L3
N
LOAD
36
H(+) L(-)
J1939 ECU
SCR
37 38 39
(+) (-)
MPU
SCR
40 41 64
H(+) L(-)
SCR
65 66 696867
A(+) B(-)
SCR
42 43 45
G+ G- A+ A-
GOVERNOR AVR
MULTI LINK
COMMUNICATION
(CAN OPEN)
RS485
COMMUNICATION
c
c c
c
2
c
44
Connect screen at generator only
Connect screen at generator only
Emergency Stop
(Conf.Input-1)
To Engine
Earth
MAX. 300V~
GEN. VOLTS
MAX. 300V~
GEN. CURRENT
Conf.
Output-10
8A
2 1
TO OTHER UNITS
ON THE BUS

3. Changing And Saving Parameters Values
4
01.System
03.Generator
04.Engine
05.Inputs
06.Outputs
07.Timers
08.Expansion modules
09.Synchronization
10.Logic controller
TECHNICIAN SETTING
Press Enter button to
access to all parameters in
currently parameter page.
Press Enter button to access to
all parameters page in currently
main parameter group.
Press the Up or
Down buttons to
select the main
parameter group you
wish to view/change.
Note1: If Enter button is pressed
and the technician password is
zero, Password screen is ignored.
Enter password
with cursor (Right,
Left,
) .
Up and
Down buttons
Press the
Enter
button.
Press the Up or Down buttons to select
the section you wish to view/change.
When the Prog button is pressed, the
parameters section is asked for accessing to
parameters.
Operation Screen
ü
ü
ü
ü
ü
ü
ü
ü
Press the Enter button to confirm
password. If the password is
incorrect, the unit will drop out of
program mode.
Operator setting
PROGRAM
Technician setting
Factory adjustment
Operator setting
PROGRAM
Technician setting
Factory adjustment
V1: V
230
V2: V
230
V3: V
230
GENERATOR
I1: A
170.0
I2: A
170.0
I3: A
170.0
V12: V
400
V23: V
400
V31: V
400
A
0.0
Ie:
Hz:
50.0
Phase seq.:
L1-2-3
PF1:
PF2:
PF3:
1.00
1.00
1.00
On load
Password
TECHNICIAN SETTING
0000
Password
TECHNICIAN SETTING
0162
01.System
03.Generator
04.Engine
05.Inputs
06.Outputs
07.Timers
08.Expansion modules
09.Synchronization
10.Logic controller
TECHNICIAN SETTING
01.Volt level
02.Frequency level
03.Current level & actions
04.Power level
06.General
03.GENERATOR

5
001.Nominal voltage
014.Under volt set
015.Under volt actions
016.Under volt actions delay
003.Under volt prealarm
004.Under volt prealarm reset
017.Under volt prealarm delay
018.Over volt set
019.Over volt actions
03.01.GENERATOR VOLT LEVEL
Operation
Screen
3. Parametrelerin Ayarlanmasý
ü
ü
ü
ü
To exit from
programming mode any
time, press Prog button.
When the Escape button is
pressed any time, previous
page can be accessed.
Press Enter button to
confirm the changed
value.
Parameter can be
changed with Up
and Down buttons.
Press the Enter
button to view
parameter value.
V1: V
230
V2: V
230
V3: V
230
GENERATOR
I1: A
170.0
I2: A
170.0
I3: A
170.0
V12: V
400
V23: V
400
V31: V
400
A
0.0
Ie:
Hz:
50.0
Phase seq.:
L1-2-3
PF1:
PF2:
PF3:
1.00
1.00
1.00
On load
01.Volt level
02.Frequency level
03.Current level & actions
04.Power level
06.General
03.GENERATOR
001.Nominal voltage
400
03.01.GENERATOR VOLT LEVEL
Vac
001.Nominal voltage
405
03.01.GENERATOR VOLT LEVEL
Vac
001.Nominal voltage
014.Under volt set
015.Under volt actions
016.Under volt actions delay
003.Under volt prealarm
004.Under volt prealarm reset
017.Under volt prealarm delay
018.Over volt set
019.Over volt actions
03.01.GENERATOR VOLT LEVEL

4.1 Operator Parameters
4. Parameters
4.1.1 Generator
6
Note: dis = disable
600
600
60(dis)
60
600
600
VV
VV
VV
VV
60
60
Min Default
Max
Under Voltage Set
Nominal Voltage
Under Voltage Pre-Alarm
Under Voltage Pre-Alarm Reset
Over Voltage Pre-Alarm
320
400
340
350
60(dis) 600
60 600
450
430
Over Voltage Pre-Alarm Reset
VV
VV
014.Under volt set
001.Nominal voltage
003.Under volt prealarm
004.Under volt prealarm reset
006.Over volt prealarm
007.Over volt prealarm reset
Unit
00 .9 Unbalanve volt set
Unbalance Volt Set
03.01.GENERATOR VOLT LEVEL ( )Generator-> levelVolt
0 230 20 VV
600 VV
60
Over Voltage Set 470
01 .8 Over volt set
75.0
75.0
Hz
30.0(dis)
Min Default
Max
Under Frequency Pre-Alarm
Under Frequency Pre-Alarm Reset
Over Frequency Pre-Alarm
Over Frequency Pre-Alarm Reset
45.0
46.0
55.0
54.0
Hz
Hz
Hz
30.0
30.0(dis)
30.0
75.0
75.0
003.Under freq prealarm
004.Under freq prealarm reset
006.Over freq prealarm
007.Over freq prealarm reset
Unit
03.02. FREQGENERATOR LEVEL ( )Generator-> levelFrequency
75.0
75.0
Hz
30.0
Nominal Alternator Frequency 50.0
43.0 Hz
001.Nominal frequency
011.Under freq set Under Frequency Set 30.0
75.0 58.0 Hz
01 .5 Over freq set Over Frequency Set 30.0
Min Default
Max
003.Under current prealarm reset
006.Over current set
007.Over current prealarm
008.Over current prealarm reset
012.Earth fault current set
Unit
03.03. CUR LEVELGENERATOR ( )Generator->Current level
001.Under current set
002.Under current prealarm
0
0
9999
9999
0
100
AV
AV
0
0(dis)
0
0
0(dis)
9999
9999
9999
9999
9999
1
dis
5
9999
AV
AV
AV
AV
AV
015.Unbalance load set 0 9999 0 AV
Under Current Pre-Alarm Reset
Under Current Set
Under Current Pre-Alarm
Over Current Set
Over Current Pre-Alarm
Over Current Pre-Alarm Reset
Earth Fault Current Set
Unbalance Load Set
dis
9999
9999
9999
9999
9999
9999
kVA
kVA
kVA
kVA
0
0(dis)
0
0
0(dis)
0
Min Default
Max
Under SetPower
Under Pre-AlarmPower
Under Pre-Alarm ResetPower
Over SetPower
Over Pre-AlarmPower
0
5
Over Pre-Alarm ResetPower
kVA
kVA
Unit
Reverse Power Pre-Alarm
-9999(dis) 0 dis kW
dis
0
0
dis
001. powerUnder set
002. powerUnder prealarm
003. powerUnder prealarm reset
006. powerOver set
007. powerOver prealarm
008. powerOver prealarm reset
019.Reverse power prealarm
03.04. POWERGEN LEVEL ( )Generator->Power level
Excitation Loss Set
-9999 0 -100 KVAr
014.Excitation loss set
Reverse Power Set
-9999 0 -30 kW
011.Reverse power set
0-9999
Reverse Power Pre-Alarm Reset
kW
-9990
020. powerReverse prealarm reset

7
4.2 Technician Parameters
4.2.1 System
Min Default Unit
01.03.LCD DISPLAY ( )System->LCD display Max
Language Selection ENGLISH/TURKISH
0
0(dis)
1
250
23
002.Auto scroll time
003.Auto scroll number
001.Language
Auto Scroll Time
Auto Scroll Number
Scroll Time For Error Messages 2
0
1
0
250
1
Sec
004.Error message scroll time
005.Theme selection
ENGLISH
5
Sec
Notes: NO / NC : Normally Open / Normally Close
NOR / PULS : Normal / Pulse
dis = disable
Min Default Unit
01.04.SERIAL COMMUNICATION ( )System->Serial Comm.
Max
Slave Address 1
1 247
05 3
Baud Rate: 0 - 1200 baud
1 - 2400 baud
2 - 4800 baud
3 - 9600 baud
4 - 19200 baud
5 - 38400 baud
001.Slave address
002.Baud rate
Timeout 0(dis) 999 3
005.Timeout Min
Min Default
Max
Current Transformer Ratio
Earth Fault CT Ratio
001.CT ratio
002.Earth fault CT ratio
012.PT primary
01 .3 PT secondary
004.Type of AC system
005.Phase sequence
006.Generator kVA rating
007.Power unit
Unit
01.01.SYSTEM NETWORK ( )System->Network
9999
3
9999
65000
480
kVA
1
0
0
50
50
100
1
150
kW
400
400
L123
DISBL, L123, L321
99991 100
kVA/kW
Voltage Transformer Primary
Voltage Transformer Secondary
0- 1 Phase 2 Wire
1- 3 Phase 4 Wire
2- 2 Phase 3 Wire L1-L2
3- 2 Phase 3 Wire L1-L3
Phase Sequence
Generator kVA Rating Set
Power Unit
Min Default Unit
01.02.BREAKERS ( )System->Breakers
Max
Gen. Close Breaker Contact Type
Gen. Close Breaker Relay Type
Gen. Close Timer
0
Gen. Open Breaker Relay Type
0 3
Gen. Open Timer
NO / NC NO
NOR / PULS
5
1 250
0
Sec
0
NOR / PULS
0.5
0.5
1
0.0
0.0
250
10.0
10.0
5
3
0
0
250
250
2
5
5.0
Breaker Close Pulse Time
Breaker Open Pulse Time
Transfer Time
Spring Loading Time
Retry Number
Neutral Contactor Fail Delay
002.Gen.close breaker cont.type
003.Gen.close breaker relay type
004.Generator close timer
005.Gen.open breaker relay type
006.Generator open timer
001.Type of Breaker
013.Breaker open pulse time
014.Transfer time
015.Spring loading time
016.Retry number
017.Neutral contactor control
018.Neutral contactor fail delay
012.Breaker close pulse time
Sec
Sec
Sec
Sec
Sec
1
0.0
250
25.0 Sec
Neutral Contactor Control:
0-DISABLE, 1-EACH or 2-COMMON 0
0 2
Hardware Breaker Selection:
0-Breakers
1-User Configured
2-Motorised Breakers (Compact Type)
3-Motorised Breakers (Open Type)
Theme Selection:
0-Black theme, 1-Gray theme
VV
VV

8
Min Default01.06.DATA LOGGING ( )System->Data logging Max
001.Data log memory
Unit
1
Data Logging Memory
Data log Period 0.0(dis) 999.9 1.0
002.Data log period Min
0-Disable
1-Internal memory
2-External USB Host
Min Default01.07.DATE & TIME SET ( )System->Date & time set Max
Year
Month
0 99
112
Date 131
Day of week 17
Hour 023
Minute 059
Second 059
001.Year
002.Month
003.Day
004.Week
005.Hour
006.Minute
007.Second
Unit
Min Default Unit
01.09.PASSWORD SETTINGS ( )System->Password settings Max
Operator Password
Technician Password
0
0 9999
09999 0
001.Operator password
002.Technician password
Min Default Unit
01.08.DEFAULT SETTINGS ( )System->Default settings Max
Save setting to default
Reset default sets
001.Save setting to def.
002.Reset default sets
YES / NO NO
003.Reset factory sets
Reset factory sets
YES / NO NO
YES / NO NO
Min Default Unit
01.05.RS485 COMMUNICATION ( )System->RS 485 Comm. Max
Slave Address 1
1 247
05 3
Baud Rate: 0 - 1200 baud
1 - 2400 baud
2 - 4800 baud
3 - 9600 baud
4 - 19200 baud
5 - 38400 baud
001.Slave address
002.Baud rate
ModBus ASCII/RTU Selection ASCII
ASCII / RTU
005.ASCII/RTU selection
Note: dis = disable

9
Note: dis = disable
4.2.2 Generator
600
25.0
600
60(dis)
60
600
600
VV
VV
VV
VV
60
0.0
60
Min Default
Max
Under Voltage Set
Under Voltage Actions Delay
Nominal Voltage
Under Voltage Pre-Alarm
Under Voltage Pre-Alarm Reset
Over Voltage Pre-Alarm
320
2.0
400
340
350
60(dis) 600
60 600
450
430
Over Voltage Pre-Alarm Reset
VV
VV
014.Under volt set
016. actions delayUnder volt
001.Nominal voltage
003.Under volt prealarm
004.Under volt prealarm reset
006.Over volt prealarm
007.Over volt prealarm reset
Unit
00 .9 Unbalanve volt set
Unbalance Volt Set
03.01.GENERATOR VOLT LEVEL ( )Generator-> levelVolt
0 230 20 VV
010.Unbalance volt actions
011.Unbalance volt actions delay
0(dis)
0
3
99
dis
2Sec
Unbalance Volt Actions Delay Time
Unbalance Volt :
0- , 1- ,
2- , 3-
Actions
Disable Warning
Electrical Trip Shutdown.
Sec
Min Default Unit
01.10.ETHERNET SETTINGS ( )System->Ethernet settings Max
Tcp Client Mode
001.Tcp client mode
002.ModBus protocol
003.IP address byte1
004.IP address byte2
005.IP address byte3
006.IP address byte4
007.Subnet mask byte1
008.Subnet mask byte2
009.Subnet mask byte3
010.Subnet mask byte4
011.Gateway address byte1
012.Gateway address byte2
013.Gateway address byte3
014.Gateway address byte4
015.DNS address byte1
016.DNS address byte2
017.DNS address byte3
018.DNS address byte4
019.Device TCP port
ENABL/DISBL DISBL
ModBus Protocol Selection
IP Address Byte1
IP Address Byte2
IP Address Byte3
IP Address Byte4
Subnet Mask Byte1
Subnet Mask Byte2
Subnet Mask Byte3
Subnet Mask Byte4
Gateway Address Byte1
Gateway Address Byte2
Gateway Address Byte3
Gateway Address Byte4
DNS Address Byte1
DNS Address Byte2
DNS Address Byte3
DNS Address Byte4
Device TCP Port
ASCII
192
168
12
8
255
255
255
0
192
168
0
1
8
8
8
8
3500
ASCII, RTU, TCP
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
255
255
255
255
255
255
255
255
255
255
255
255
255
255
255
255
65535
015. volt actionsUnder 0(dis) 3 3
Under Volt :
0- , 1- ,
2- , 3-
age Actions
Disable Warning
Electrical Trip Shutdown.
25.00.0Under Voltage Pre-Alarm Delay 2.0
01 . delay7 Under volt prealarm Sec
600
25.0
VV
60
0.0
Over Voltage Set
Over Voltage Actions Delay
470
2.0
01 .8 Over volt set
020. actions delayOver volt Sec
019. volt actionsOver 0(dis) 3 3
Ov age Actions
Disable Warning
Electrical Trip Shutdown.
er Volt :
0- , 1- ,
2- , 3-
25.00.0Over Voltage Pre-Alarm Delay 2.0
0 . delay21 Over volt prealarm Sec

10
Note: dis = disable
75.0
75.0
Hz
30.0(dis)
Min Default
Max
Under Frequency Pre-Alarm
Under Frequency Pre-Alarm Reset
Over Frequency Pre-Alarm
Over Frequency Pre-Alarm Reset
45.0
46.0
55.0
54.0
Hz
Hz
Hz
30.0
30.0(dis)
30.0
75.0
75.0
003.Under freq prealarm
004.Under freq prealarm reset
006.Over freq prealarm
007.Over freq prealarm reset
Unit
03.02. FREQGENERATOR LEVEL ( )Generator-> levelFrequency
75.0
75.0
Hz
30.0
Nominal Alternator Frequency 50.0
43.0 Hz
001.Nominal frequency
011.Under freq set Under Frequency Set 30.0
25.00.0
Under Frequency Actions Delay 2.0
013. freq actions delayUnder Sec
01 . actions2 Under freq 0(dis) 3 3
Under Frequency :
0- , 1- ,
2- , 3-
Actions
Disable Warning
Electrical Trip Shutdown.
25.00.0Under Frequency Pre-Alarm Delay 2.0
014. delayUnder freq prealarm Sec
75.0 58.0 Hz
01 .5 Over freq set Over Frequency Set 30.0
25.00.0
Over Frequency Actions Delay 2.0
01 . freq actions delay7 Over Sec
01 . actions6 Over freq 0(dis) 3 3
Ov Actions
Disable Warning
Electrical Trip Shutdown.
er Frequency :
0- , 1- ,
2- , 3-
25.00.0Over Frequency Pre-Alarm Delay 2.0
01 . delay8 Over freq prealarm Sec

Min Default
Max
003.Under current prealarm reset
004.Under current actions
005.Under current actions delay
006.Over current set
007.Over current prealarm
008.Over current prealarm reset
009.Over current actions
010.Over current actions delay
011.Short circuit current
012.Earth fault current set
013.Earth fault current actions
014.E.F. current actions delay
Unit
03.03. CUR LEVEL & ACTGEN ( )Generator->Current level & act.
001.Under current set
002.Under current prealarm
0
0(dis)
0
0
0
0(dis)
0
9999
3
99
9999
9999
3
99
0
2
5
9999
100
dis
2
AV
AV
AV
0
0(dis)
0
0(dis)
0
0
0(dis)
9999
9999
9999
3
99
9999
9999
1
dis
5
dis
2
9999
AV
AV
AV
AV
AV
Sec
Sec
Sec
015.Unbalance load set
016.Unbalance load actions
017.Unbalance load actions delay
0
0(dis)
0
9999
3
99
0
dis
2
AV
Sec
Under Current Pre-Alarm Reset
Under Current Actions Delay Time
Under Current Set
Under Current Pre-Alarm
Under Current Actions
Disable
Warning
Electrical Trip
Shutdown
0 -
1 -
2 -
3 -
Over Current Set
Over Current Pre-Alarm
Over Current Pre-Alarm Reset
Over Current Actions Delay Time
Short Circuit Current Set
Earth Fault Current Set
Earth Fault Current Actions Delay Time
Over Current Actions
Disable
Warning
Electrical Trip
Shutdown
0 -
1 -
2 -
3 -
Earth Fault Current Actions
Disable
Warning
Electrical Trip
Shutdown
0 -
1 -
2 -
3 -
Unbalance Load Set
Unbalance Load Actions Delay Time
Unbalance Load
0 -
1 -
2 -
3 -
Actions
Disable
Warning
Electrical Trip
Shutdown
11
Note: dis = disable
dis
0 .Under current prealarm delay18
0 . current19 Over IDMT alarm
0 99 2 Sec
Under Current Pre-Alarm Delay Time
Over Current IDMT Alarm
ENABL/DISBL DISBL
0 . current20 Over 51VR alarm
0 1. current2 Over 51VR volt start
0 2. current2 Over 51VR volt stop
0 3. current factor2 Over 51VR min.
Over Current 51VR Alarm
Over Current 51VR Volt Start
Over Current 51VR Volt Stop
Over Current 51VR Minimum Factor
ENABL/DISBL DISBL
5.0
5.0
5.0
100.0
100.0
100.0
95.0
25.0
25.0
%
%
%
024.Over current prealarm delay 0 99 5 Sec
Over Current Pre-Alarm Delay Time
025.Earth fault current IDMT alarm Earth Fault Current IDMT Alarm
ENABL/DISBL DISBL

12
Note: dis = disable
9999
9999
9999
9999
9999
9999
kVA
kVA
kVA
kVA
0
0(dis)
0
0
0(dis)
0
Min Default
Max
Under SetPower
Under Pre-AlarmPower
Under Pre-Alarm ResetPower
Over SetPower
Over Pre-AlarmPower
0
5
Over Pre-Alarm ResetPower
kVA
kVA
Unit
Over Delay TimePower Actions
Reverse Power Pre-Alarm
0
-9999(dis)
99
0
2
dis
Sec
kW
dis
0
0
dis
001. powerUnder set
002. powerUnder prealarm
003. powerUnder prealarm reset
006. powerOver set
007. powerOver prealarm
008. powerOver prealarm reset
010.Over power actions delay
019.Reverse power prealarm
03.04. POWERGEN LEVEL ( )Generator->Power level
Under Delay TimePower Actions
0(dis)
0
3
99
0(dis)
2Sec
Under Actions
Disable
Warning
Electrical Trip
Shutdown
Power
0 -
1 -
2 -
3 -
004.Under power actions
005.Under power actions delay
0(dis) 3 0(dis)
Over Actions
Disable
Warning
Electrical Trip
Shutdown
Power
0 -
1 -
2 -
3 -
009.Over power actions
Excitation Loss Set
Excitation Loss Actions Delay Time
-9999
0(dis)
0
0
3
99
-100
0(dis)
2
KVAr
Sec
Excitation Loss
0 -
1 -
2 -
3 -
Actions
Disable
Warning
Electrical Trip
Shutdown
014.Excitation loss set
01 .Excitation loss5 actions
016.Excitation loss actions delay
Under Pre-Alarm Delay TimePower
0 99 2 Sec
017. powerUnder prealarm delay
Over Pre-Alarm Delay TimePower
0 99 2 Sec
01 . power8 Over prealarm delay
Reverse Power Set
Reverse Power Actions Delay Time
-9999
0(dis)
0
0
3
99
-30
2
6
kW
Sec
Reverse Power Actions
Disable
Warning
Electrical Trip
Shutdown
0 -
1 -
2 -
3 -
011.Reverse power set
012.Reverse power actions
013.Reverse power actions delay
0-9999
Reverse Power Pre-Alarm Reset
kW
-9990
020. powerReverse prealarm reset
Reverse Power Pre-Alarm Delay
0 99 6 Sec
021. powerReverse prealarm delay
Min Default Unit
03.06.GENERATOR GENERAL ( )Generator->General Max
001.Sensing option gen.frequency ENABL
ENABL/DISBL
0( )dis DISBL1000
002.Sensing option pickup&flywheel
003.All warning are latch ENABL/DISBL DISBL
Sensing Opt Generator Frq En/Dis
Sensing Opt Pickup En/Dis&Flywheel
All Warnings Are Latched En/Dis

13
Note: dis = disable
4.2.3 Engine
04.02.ENG.CRANK DISCONNECT( )Engine->Crank disconnect
001.Generator frequency
002.Engine speed
003.Generator volt
004.Alternator charge volt
Min Default UnitMax
Gen Frequencyerator
Generator Voltage
Charge Alternator Voltage
30.0
10.0 75.0 Hz
500
100 6000 RPM
300
60 (dis) 600 VV
dis
6.0 (dis) 30.0 VZ
Engine RPM
005.Oil pressure enable/disable
006. valueOil pressure
007.Check oil press. before start
Oil Pressure Enable/Disable
Oil Pressure Value
Check Oil Pressure Before Start
1.0 30.0 BAR
1.0
ENABL/DISBL DISBL
ENABL/DISBL ENABL
ENABL/DISBL
Sec
Min Default Unit
04.01.ENGINE START OPTIONS ( )Engine->Starting options Max
DISBL
3
5
1
1
10
99
10
5 99
3.0
0.1 10.0
001.Horn prior start
002. startNumber of attempts
003.Cranking time
004.Crank rest time
005. aPickup fail del y
Sec
Sec
Audible Alarm Prior To Starting
Number Of Start Attempts
Cranking Time
Crank Rest Time
Pickup Sensor Fail Delay
Min Default Unit
04.03.ENGINE SPEED SETS ( )Engine->Speed settings Max
Under Speed Shutdown
Under Speed Prealarm
Under Speed Prealarm Reset
dis
Over Speed Shutdown
500(dis) 5000
500(dis) RPM
500
500 5000
Over Speed Prealarm Reset 500
RPM
RPM
RPM
RPM
RPM
5000
500(dis) 5000
5000
5000
Over Speed Prealarm
002.Under speed shutdown
003.Under speed prealarm
004.Under speed prealarm reset
005.Over speed shutdown
006.Over speed prealarm
007.Over speed prealarm reset 500
Nominal Speed 1500
500 5000 RPM
001.Nominal speed
dis
dis
dis
500(dis)
25.00.0
Under Shutdown DelaySpeed 2.0
0 . delay09 Under speed shutdown Sec
25.00.0
Over Shutdown DelaySpeed 2.0
010.Ov delayer speed shutdown Sec
25.00.0
Under Prealarm DelaySpeed 2.0
0 . delay11 Under speed prealarm Sec
25.00.0
Over Prealarm DelaySpeed 2.0
0 . delay12 Over speed prealarm Sec
Min Default
04.04.ENGINE PLANT BATTERY ( )Engine->Plant battery Max
10.5
6.0(dis)
6.0
30.0
30.0
1.0
0.0
30.0
6.0(dis) 30.0
1.0
dis
9.9
30.0
9.9
6.0(dis) 30.0
6.0
0.0
001.Under volt
002. resetUnder volt
003. delayUnder volt
004.Over volt
005. resetOver volt
006. delayOver volt
007.Alternator charge warning
Unit
VZ
VZ
Sec
VZ
Sec
VZ
VZ
10.0
29.5
Under Volt Warning Set
Under Volt Warning Reset
Under Volt Warning Delay
Over Volt Warning Set
Over Warning ResetVolt
Over DelayVolt Warning
Charge Alternator Warning

14
Note: dis = disable
04.05.CANBUS ECU ( )Engine->CanBus ECU
001.Baud rate
002.J1939 ECU type
003.Device address
004.SPN version
Min Default UnitMax
07 4
31 dis
0 255 17
1 3 1
kBaud
005.ECU remote control
006.Speed control enable
007.Oil pressure control enable
008.Temperature control enable
ENABL
Device Address
0(dis)
SPN version
ECU Remote Control
Speed Control
Oil Pressure Control
Coolant Temperature Control
010.Speed correction 50
Speed Correction Value
%
0 100
009.Speed set point 1500
1500 1800/
Speed Set Point Selection
RPM
ENABL/DISBL
ENABL/DISBL
ENABL/DISBL
ENABL/DISBL
ENABL
DISBL
DISBL
J1939 ECU Type Selection:
0 - Disable
1 - Standard
2 - Volvo EMS1
3 - Volvo EMS2
4 - Volvo EMS2b
5 - Volvo EDC3
6 - Volvo EDC4
7 - Deutz EMR2
8 - Deutz EMR3
9 - Perkins 1300
10 - Perkins ADEM3
11 - Perkins ADEM4
12 - Scania S6
13 - MAN MFR
14 - Cummins ISB
15 - Cummins CM570
16 - Cummins CM850
17 - Cummins CM2150E
18 - Cummins CM2250
19 - Detroit DDEC
20 - John Deere
21 - MTU ADEC
22 - MTU ECU8
23 - MTU ECU8 SAM
24 - Yuchai
25 - Kubota
26 - Baudouin WISE10B
27 - Baudouin WISE15
28 - Perkins 1600
29 - Perkins A4E2
30 - Perkins A5E2
31 - Perkins A5E2v2
Baud Rate:
0: 20, 1: 50, 2: 100, 3: 125,
4: 250, 5: 500, 6: 800, 7: 1.000

15
Note: dis = disable
Min Default Unit
04.06.CANBUS ERROR SET ( )Engine->CanBus error set Max
Can Fault Actions:
0- Disable
1- Warning Non-Latching
2- Warning
3- Electrical Trip
4- Shutdown
0
0 2
0
0(dis) 4
002.CAN fault activation
001.CAN fault actions
SecCan Fault Delay 10
3 250
003.CAN fault delay
Can Fault Activation:
0- Active From Starting
1- Active From Safety On
2- Always Active
J1939 Amber Warning Lamp Actions:
0- Disable
1- Warning Non-Latching
2- Warning
3- Electrical Trip
4- Shutdown
2
0 2
0
0(dis) 4
005.Amber warning activation
004.Amber warning actions
SecJ1939 Amber Warning Lamp Delay 2
0 250
006.Amber warning delay
J1939 Amber Warning Lamp Activation:
0- Active From Starting
1- Active From Safety On
2- Always Active
J1939 Red Stop Lamp Actions:
0- Disable
1- Warning Non-Latching
2- Warning
3- Electrical Trip
4- Shutdown
2
0 2
0
0(dis) 4
008.Red stop activation
007.Red stop actions
SecJ1939 Red Stop Lamp Delay 2
0 250
009.Red stop delay
J1939 Red Stop Lamp Activation:
0- Active From Starting
1- Active From Safety On
2- Always Active

16
Note: dis = disable
Min Default
04.08.TEST MODE ( )Engine->Test mode Max Unit
001.Disable/enable select
ENABL
ENABL/DISBL
Test Mode Selection
Min Default
04.07.ENGINE MAINTENANCE ( )Engine->Maintenance Max
Running Hours Interval
Maintenance Date Interval
Engine Stop When Maintenance
Engine Running Hour
5000
0(dis) 9999
ENABL/DISBL
0
0 30000
DISBL
0(dis) 12 6
002.Maintenance date interval
003.Engine stop when maintenance
004.Engine running hour
001.Running hours interval
Unit
Hour
Month
Maintenance Okay NO
007.Maintenance okay YES/NO
Min Default
Max
Exercise Disable or Enable
Exercise Start Time on Monday
Exercise Stop Time on Monday
Exercise St Time onart Tuesday
Exercise Stop Time on Tuesday
Exercise St Time onart Wednesday
Exercise Stop Time on Wednesday
Exercise St Time onart Thursday
Exercise Stop Time on Thursday
Exercise Start Time on Friday
Exercise Start Time on Saturday
Exercise Start Time on Sunday
Exercise Stop Time on Friday
Exercise Stop Time on Saturday
Exercise Stop Time on Sunday
001.Disable/enable select
002.Start time on monday
003.Stop time on monday
004. art tuesdaySt time on
005. tuesdayStop time on
006. art wednesdaySt time on
007. wednesdayStop time on
008. art thursdaySt time on
009. thursdayStop time on
010. fridayStart time on
012. saturdayStart time on
014. sundayStart time on
011. fridayStop time on
013. saturdayStop time on
015. sundayStop time on
Unit
04.09.EXERCISE ( )Engine->Exercise
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
DISBL ENABL/ DISBL
Min Default Unit
04.10.ENGINE GENERAL ( )Engine->General Max
Engine Fuel Selection 1-DIESEL
Stop Solenoid Time 1 2099
Ignition Delay 1 599 Sec
Gas Valve Delay 1 599 Sec
Minimum Ignition Speed 10 2001500 RPM
001.Fuel selection
002.Stop solenoid time
003.Ignition delay
004.Gas valve delay
005.Minimum ignition speed
Sec
006.Choke time Choke Time Sec
0.0 0.830.0
0-GAS
1-DIESEL
2-GASOLINE

17
4.2.4 Inputs
Min Default Unit
05.01.SENDER INPUTS ( )Inputs->Sender inputs Max
Oil Press Input Typeure
Oil Press Pre-Alarmure 1.2
0.0 (dis) 30.0 BAR
1.4
2
0.0
0
30.0
250
BAR
Sec
1.0
0.0 30.0 BAR
0-Not Used (Disable)
1-Digital NC
2-Digital NO
3-VDO 5 BAR
4-VDO 7 BAR
5-VDO 10 BAR
6-DATCON 5 BAR
7-DATCON 7 BAR
8-MURPHY 7 BAR
9-User Configured
90
0 (dis) 300
88
0 300
95
0 300
High Temp Pre-Alarmerature
Oil Pressure Set
High Temp Seterature
C
C
C
008.Temperature sensor break
009.High temperature prealarm
010.High temp. prealarm reset
043.High temperature set
007.Temperature input type
039.Oil pressure set
004.Oil pressure prealarm reset
0 .38 Oil pressure prealarm delay
003.Oil pressure prealarm
002.Oil pressure input type
0 (dis) 70
Low Temp. Warning C
012.Low temperature warning
0 (dis)
0-Not Used (Disable)
1-Digital NC
2-Digital NO
3-
4- 5
5-DATCON
6-MURPHY
7-PT100
8-User Configured
VDO 120 ºC
VDO 1 0 ºC
0 (dis)
0 (dis)
Oil Press Uniture
001.Oil pressure unit BARBAR/PSI/KPA
Coolant Temp Uniterature
006.Temperature unit ºCºC/ºF
0 (dis)
0 (dis) 300 C
013.Heater control ON
0300 C
014.Heater control OFF
45
5
0 9999
Water Pump On Time
015.Water pump on time
09999
Water Pump Off Time Sec
016.Water pump off time
5
Sec
0 - Disable
1 - Enable From Safety
On (3min. delayed)
2 - Always Enable
0 (dis)
Coolant Heater Control Off
Coolant Heater Control On
Oil Press Pre-Alarm Reseture
Oil Press Pre-Alarm Delayure
Coolant Temp Input
Type
erature
High Temp. Pre-Alarm Reset
040. actionsOil pressure 0(dis) 3 3
Oil Pressure :
0- , 1- ,
2- , 3-
Actions
Disable Warning
Electrical Trip Shutdown.
0
0 250 Sec
0 . actions41 Oil pressure delay
Oil Press Actions Delayure
Coolant Temp Sensor
Break
erature
2
0 250 Sec
042.High temp. prealarm delay
High Temp. Pre-Alarm Delay
04 . actions4 High temperature 0(dis) 3 3
High Temperature Actions
Disable Warning
Electrical Trip Shutdown.
:
0- , 1- ,
2- , 3-
0
0 250 Sec
0 . actions45 High temperature delay
High Temp. Actions Delay
Note: dis = disable

18
0 (dis) 3000 %
018.Conf. AI1 type
019.Conf. AI1 low prealarm
017.Conf. AI1 unit
0 (dis)
0 (dis)
BAR/PSI/KPA/ºC/ºF/%/Lt
Conf. Analog Input-1 Unit
Conf. AI1 Low Prealarm
0-Not Used (Disable)
1-Digital NC
2-Digital NO
3-VDO OHM (10-180)
4-VDO TUBE (90-0)
5-US OHM (240-33)
6-EMS OHM (0-190)
7-FORD (73-10)
8-User Configured
9-J1939 Fuel Total
10-J1939 Oil Level
11-J1939 Coolant Level
12-J1939 Load At
Current Speed
13-J1939 Act. Eng Torq.
14-J1939 Pedal Position
Conf. Analog Input-1 Type
0%
75
026.Conf. AI1 control OFF
037.Conf. AI1 sens.break shutdown
3000
0 (dis)
0 (dis) 3000 %
025.Conf. AI1 control ON
3000
90
0 3000
022.Conf. AI1 high prealarm
0 (dis) 0 (dis) %
%
023.Conf. AI1 high prealarm reset
Conf. AI1 High Prealarm
Conf. AI1 High Prealarm Reset
Conf. AI1 Control ON
Conf. AI1 Control OFF
Conf. AI1 Sensor Break
Shutdown DISBL ENABL/ ENABL
3000 %
0
047.Conf. AI1 low set 0
Conf. AI1 Low Set
0 3000 %
60
020.Conf. AI1 low prealarm reset
Conf. AI1 PrealarmLow Reset
2
0 250 Sec
046.Conf. AI1 low prealarm delay
Conf. AI1 Low Prealarm Delay
048. actionsConf. AI1 low 0(dis) 3 3
Conf. AI1 Low Actions
Disable Warning
Electrical Trip Shutdown.
:
0- , 1- ,
2- , 3-
2
0 250 Sec
0 . actions49 Conf. AI1 low delay
Conf. AI1 Low Actions Delay
2
0 250 Sec
050.Conf. AI1 high prealarm delay
Conf. AI1 High Prealarm Delay
3000 %
0
0 .51 Conf. AI1 high set 0
Conf. AI1 High Set
0 . actions52 Conf. AI1 high 0(dis) 3 0 (dis)
Conf. AI1 High Actions
Disable Warning
Electrical Trip Shutdown.
:
0- , 1- ,
2- , 3-
2
0 250 Sec
0 . actions53 Conf. AI1 high delay
Conf. AI1 High Actions Delay
028.Conf. AI2 type
027.Conf. AI2 unit
0-Not Used (Disable)
1-Digital NC
2-Digital NO
3-
4- 5
5-DATCON
6-MURPHY
7-PT100
8-User Configured
VDO 120 ºC
VDO 1 0 ºC
9-J1939 Fuel Temp.
10-J1939 Oil Temp.
11-J1939 Intake Manif.
Temperature
0 (dis)
BAR/PSI/KPA/ºC/ºF/%/Lt
Conf. Analog Input-2 Type
Conf. Analog Input-2 Unit
0 (dis) 300
029. 2Conf. AI low prealarm 0 (dis)
Conf. AI2 Low Prealarm
0 300 60
030. 2Conf. AI low prealarm reset
Conf. AI2 PrealarmLow Reset
2
0 250 Sec
054. 2Conf. AI low prealarm delay
Conf. AI2 Low Prealarm Delay
ºC
%
ºC
ºC
Note: dis = disable

19
Note: dis = disable
0ºC
75
036.Conf. AI2 control OFF
300
0 (dis)
0 (dis) 300 ºC
035.Conf. AI2 control ON
300
90
0 300
032. 2Conf. AI high prealarm
0 (dis) 0 (dis) ºC
ºC
033. 2Conf. AI high prealarm reset
Conf. AI2 High Prealarm
Conf. AI2 High Prealarm Reset
Conf. AI2 Control ON
Conf. AI2 Control OFF
300
0
055. 2Conf. AI low set 0
Conf. AI2 Low Set
056. 2 actionsConf. AI low 0(dis) 3 0(dis)
Conf. AI2 Low Actions
Disable Warning
Electrical Trip Shutdown.
:
0- , 1- ,
2- , 3-
2
0 250 Sec
057. 2 actionsConf. AI low delay
Conf. AI2 Low Actions Delay
2
0 250 Sec
058. 2Conf. AI high prealarm delay
Conf. AI2 High Prealarm Delay
300 ºC
0
0 9. 25 Conf. AI high set 0
Conf. AI2 High Set
060. 2 actionsConf. AI high 0(dis) 3 0(dis)
Conf. AI2 High Actions
Disable Warning
Electrical Trip Shutdown.
:
0- , 1- ,
2- , 3-
2
0 250 Sec
061. 2 actionsConf. AI high delay
Conf. AI2 High Actions Delay
ºC

20
Min Default Unit
05.02.SENDER LINEARISATION ( )Inputs->Sender linearisation Max
15
31
49
66
85
101
117
132
149
178
579
404
342
250
179
136
103
77
67
63
10
30
50
70
90
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
10.0
28
35
40
50
60
70
80
90
95
98
0
11
22
33
44
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
BAR
BAR
BAR
BAR
BAR
BAR
BAR
BAR
BAR
BAR
ºC
ºC
ºC
ºC
ºC
ºC
ºC
ºC
ºC
ºC
%
%
%
%
%
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
30.0
30.0
30.0
30.0
30.0
30.0
30.0
30.0
30.0
30.0
300
300
300
300
300
300
300
300
300
300
3000
3000
3000
3000
3000
001.Oil pressure sender 1
003. 2Oil pressure sender
005. 3Oil pressure sender
007. 4Oil pressure sender
009. 5Oil pressure sender
011. 6Oil pressure sender
013. 7Oil pressure sender
015. 8Oil pressure sender
017. 9Oil pressure sender
019. 0Oil pressure sender 1
021.Temperature sender 1
023.Temperature 2sender
025.Temperature 3sender
027.Temperature 4sender
029.Temperature 5sender
031.Temperature 6sender
033.Temperature 7sender
035.Temperature 8sender
037.Temperature 9sender
039.Temperature 0sender 1
041.Conf. AI1 sender 1
043. 2Conf. AI1 sender
045. 3Conf. AI1 sender
047. 4Conf. AI1 sender
049. 5Conf. AI1 sender
002.Oil pressure 1
004. 2Oil pressure
006. 3Oil pressure
008. 4Oil pressure
010. 5Oil pressure
012. 6Oil pressure
014. 7Oil pressure
016. 8Oil pressure
018. 9Oil pressure
020. 0Oil pressure 1
022.Temperature 1
024.Temperature 2
026.Temperature 3
028.Temperature 4
030.Temperature 5
032.Temperature 6
034.Temperature 7
036.Temperature 8
038.Temperature 9
040.Temperature 01
042.Conf. AI1 value 1
044.Conf. AI1 value 2
046.Conf. AI1 value 3
048.Conf. AI1 value 4
050.Conf. AI1 value 5
Oil Pressure Sender Point-1
Oil Pressure Sender Point-2
Oil Pressure Sender Point-3
Oil Pressure Sender Point-4
Oil Pressure Sender Point-5
Oil Pressure Sender Point-6
Oil Pressure Sender Point-7
Oil Pressure Sender Point-8
Oil Pressure Sender Point-9
Oil Pressure Sender Point-10
Temperature Sender Point-1
Temperature Sender Point-2
Temperature Sender Point-3
Temperature Sender Point-4
Temperature Sender Point-5
Temperature Sender Point-6
Temperature Sender Point-7
Temperature Sender Point-8
Temperature Sender Point-9
Temperature Sender Point-10
Oil Pressure Point-1
Oil Pressure Point-2
Oil Pressure Point-3
Oil Pressure Point-4
Oil Pressure Point-5
Oil Pressure Point-6
Oil Pressure Point-7
Oil Pressure Point-8
Oil Pressure Point-9
Oil Pressure Point-10
Temperature Point-1
Temperature Point-2
Temperature Point-3
Temperature Point-4
Temperature Point-5
Temperature Point-6
Temperature Point-7
Temperature Point-8
Temperature Point-9
Temperature Point-10
Conf. Analog Input-1 Sender Point-1
Conf. Analog Input-1 Sender Point-2
Conf. Analog Input-1 Sender Point-3
Conf. Analog Input-1 Sender Point-4
Conf. Analog Input-1 Sender Point-5
Conf. Analog Input-1 Point-1
Conf. Analog Input-1 Point-2
Conf. Analog Input-1 Point-3
Conf. Analog Input-1 Point-4
Conf. Analog Input-1 Point-5
Other manuals for TRANS-SYNCRO
1
Table of contents
Other EMKO Control System manuals
Popular Control System manuals by other brands

Quanser
Quanser Q2-USB quick start guide

CALEFFI
CALEFFI 210510 Installation and commissioning manual

Crestron
Crestron 3 Series Do guide

Mitsubishi Electric
Mitsubishi Electric 700 Series Training manual

Clearwater Enviro Technologies
Clearwater Enviro Technologies SCALEBLASTER AG-100 Installation & operation manual

Roland
Roland R1000 series E20 manual

DMG
DMG CAPRICE COP ASSEMBLY & FIXING INSTRUCTIONS

Burkert
Burkert 8644 AirLINE operating instructions

Vaillant
Vaillant VR 90 OPERATING AND INSTALLATION Manual

quiko
quiko QK-CE24A user manual

heat-timer
heat-timer DiGi-SPAN Elite Series Installation and operation manual

Norac
Norac UC5 Topcon X30 installation manual