  9. EMX IRB-325 User manual

EMX IRB-325 User manual

EMX Industries, Inc. Tech support: 216-834-0761 1/4
IRB-325_Rev2.0_102219 technical@emxinc.com
IRB-325™
UL325 Thru Beam Photoeye
Instruction Manual
The IRB-325 thru beam photoeye is an external entrapment protection device type B1, non-contact sensor
for use with automatic gates and doors. The photoeye provides a signal to the gate or door operator
that the beam is or is not obstructed. The IRB-325 operates up to 65 feet and is UL325 compliant
with operators that require normally closed (NC) monitoring.
Cautions and Warnings
This product is an accessory or part of a system. Install the IRB-325 according to
instructions from the gate or door operator manufacturer. Comply with all applicable codes
and safety regulations.
Specifications
Ordering Information
•IRB-325 Thru beam photoeye
•IRB-325-HD Protective hood, gray powder coated steel, set of two
•IRB-325-SP Liquid tight strain relief connector, nylon, set of two
•IRB-325-PT Mounting post, black powder coated steel, 2” x 2” x 2’
Operating Range
Up to 65 ft (20 m)
Power
12-24 VDC/AC
ononly)
Current
150 mA (relay activated)
Relay Contact Rating
1 A @ 30 VDC
Surge Protection
Thermal fuse
Relay Output
Form C contacts (NO, COM, NC)
Operating Temperature
-40° to 170°F (-40° to 77°C)
Dimensions (L x W x H)
3.2” (82 mm) x 3.06” (78 mm) x 5.03” (128
mm)
Environmental Rating
NEMA 4X
TM
EMX Industries, Inc. Tech support: 216-834-0761 2/4
IRB-325_Rev2.0_102219 technical@emxinc.com
Board Diagram
1. Detect LED (red)
Aligned or No Detection
off
Not Aligned or Beam Blocked
on
Imperfect Alignment
one on, one off
2. Power LED (green)
Power
on
No Power
off
3. Sensitivity Jumper
The IRB-325 has three sensitivity settings: high, medium or low. To adjust the sensitivity,
move both jumpers to the desired high, medium or low setting.
4. Terminal Block
The power inputs on both the receiver and transmitter are not polarity sensitive.
Receiver Terminal Block
Transmitter Terminal Block
Normally Closed
NC
12-24 VDC/AC
Power Input
Common
COM
12-24 VDC/AC
Power Input
Normally Open
NO
12-24 VDC/AC
Power Input
12-24 VDC/AC
Power Input
Receiver
Transmitter
EMX Industries, Inc. Tech support: 216-834-0761 3/4
IRB-325_Rev2.0_102219 technical@emxinc.com
Installation
•Determine the mounting location of the IRB-325 photoeye according to UL325 guidelines.
•Deactivate the gate or door during photoeye installation.
1. Thread all wires through a UL listed watertight fitting, such as a strain relief or watertight conduit
connector.
2. Connect 12-24 VDC/AC power to the “Power Input”terminals on the transmitter (marked “TX”)
and receiver (marked “RX”). The power input terminals are not polarity sensitive.
3. Wire the receiver’s relay contacts to the operator. For operators that require normally closed
contacts, connect terminals NC and COM to the designated terminals. For operators that require
normally open contacts, connect terminals COM and NO to the designated terminals.
4. Verify that the IRB-325 transmitter and receiver are aligned and apply power.
The green power LED should be on for both the transmitter and receiver.
5. The receiver and transmitter are aligned properly when both red LEDs on the receiver are off.
If necessary, adjust the sensitivity by moving the jumpers (J1 and J2) up to increase and
down to decrease. Both jumpers should be on the same high, medium or low setting.
A close but imperfect alignment will have one red LED turned on.
6. Mount the receiver and transmitter at
opposite ends of the detection zone using
the four holes on the housing.
After mounting, seal the housing using
the cover and the four plastic screws
provided to ensure a watertight seal.
7. Place an obstruction (ex. hand) between the IRB-325 transmitter and receiver. Both red LEDs on
the receiver will turn on. Check the operator control board and verify that the safety input is
recognized by the operator. Test the beam with an obstruction between transmitter and
receiver at multiple distances to confirm proper operation.
8. Remove the obstruction and both red LEDs will turn off.
If the IRB-325 is aligned but not detecting an obstruction, consider adjusting the sensitivity
on the receiver until an obstruction is detected. This may be applicable for installations
with a detection zone of less than 20 ft.
TIP:
TIP:
cover screws
mounting screws
EMX Industries, Inc. Tech support: 216-834-0761 4/4
IRB-325_Rev2.0_102219 technical@emxinc.com
Troubleshooting
Symptom
Possible Cause
Solution
Does not detect obstruction
Sensitivity is too high
Signal is reflecting off another
surface
Move jumpers J1 and J2 to a lower
position.
Check area for highly reflective
surfaces.
Red LEDs on
Sensitivity is too low
Transmitter does not have
power
Receiver does not “see”
transmitter
Move jumpers J1 and J2 to a higher
position.
Check power source to transmitter.
Make sure transmitter and receiver
are correctly aligned.
Receiver detects intermittently
with no obstruction present
Dirty power
Using the two ceramic disk caps
provided –
1. On the receiver, place a lead
from disk cap 1 into the first
power terminal.
2. Place a lead from disk cap 2
into the second power
terminal.
3. Connect the free leads of
disk caps 1 and 2 and attach
them to an earth ground.
Receiver activates but does not
transmit signal to operator
Faulty connection between
receiver and operator control
input
Verify all wire and terminal
connections.
Warranty
EMX Industries, Inc. products have a warranty against defects in materials and workmanship for a period
of two years from date of sale to our customer.

Other manuals for IRB-325

2

Other EMX Protection Device manuals

EMX PhotoeyeVault User manual

EMX

EMX PhotoeyeVault User manual

EMX IRB-RET User manual

EMX

EMX IRB-RET User manual

Popular Protection Device manuals by other brands

Arcteq AQ-T256 instruction manual

Arcteq

Arcteq AQ-T256 instruction manual

Kitronik MI:pro quick start guide

Kitronik

Kitronik MI:pro quick start guide

toscano vigilec zero V1Z user manual

toscano

toscano vigilec zero V1Z user manual

Intermatic PG1000 Series Installation instructions and operation manual

Intermatic

Intermatic PG1000 Series Installation instructions and operation manual

TFA 98.1114.02 instruction manual

TFA

TFA 98.1114.02 instruction manual

ABB RELION RET670 Applications manual

ABB

ABB RELION RET670 Applications manual

aidapt VA116S Usage and maintenance instructions

aidapt

aidapt VA116S Usage and maintenance instructions

SILENTex Natural User instructions

SILENTex

SILENTex Natural User instructions

Protecta REBEL manual

Protecta

Protecta REBEL manual

MULTISPAN MPD-192 quick start guide

MULTISPAN

MULTISPAN MPD-192 quick start guide

Intermatic IG3240FMP33 installation instructions

Intermatic

Intermatic IG3240FMP33 installation instructions

Energotest ZL-4A operating manual

Energotest

Energotest ZL-4A operating manual

LOVATO ELECTRIC RGK30 instruction manual

LOVATO ELECTRIC

LOVATO ELECTRIC RGK30 instruction manual

FireFlex TOTALPAC X Owner's operation and maintenance manual

FireFlex

FireFlex TOTALPAC X Owner's operation and maintenance manual

Seg MRD1-T manual

Seg

Seg MRD1-T manual

Sordin EXC-1 manual

Sordin

Sordin EXC-1 manual

3M 1450 quick start guide

3M

3M 1450 quick start guide

TZ SlideHandle 4267CF product manual

TZ

TZ SlideHandle 4267CF product manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.