Eneo IAM-6MC1001M0A User manual

EN
User Manual
Ethernet over Coax Transceiver
Data/Power supply 270Mbps,
57VDC power input
IAM-6MC1001M0A

Safety instructions
•Before switching on and operating the system, first read this safety advice and the operating instructions.
•Keep the operating instructions in a safe place for later use.
•Installation, commissioning and maintenance of the system may only be carried out by authorised individuals and in
accordance with the installation instructions - ensuring that all applicable standards and guidelines are followed.
•Protect the devices from water penetration and humidity, since these can cause lasting damage.
•Should moisture nevertheless enter the system, under no circumstance switch on the devices under these conditions,
instead send them for examination to an authorised specialist workshop.
•The system must never be used outside of the technical specifications, since this can destroy it.
• The device must be protected from excesses of heat, dust, humidity and vibration.
• When separating the system from the voltage supply, only ever use the plug to pull out the cable. Never pull directly on the
cable itself.
• Lay the connecting cables carefully and check that they are not mechanically stressed, kinked or damaged and that no
humidity can penetrate into them.
• In the event of a malfunction, please inform your supplier.
• Maintenance and repairs may only be carried out by authorised specialist personnel.
• The system must be isolated from the power supply before opening the housing.
• The device may only be opened by qualified service personnel. Unauthorised access invalidates any warranty claim.
• Connection cables should always be exchanged through Videor E. Hartig GmbH.
• Use only original spare parts and accessories from Videor E. Hartig GmbH.
• The housing should only be cleaned using a mild domestic cleaning agent. Never use solvents or petrol as these can
permanently damage the surface.
• During installation, it is essential to ensure that the seals provided are correctly installed and that they are not displaced
during installation. Damaged seals must not be installed and will invalidate any warranty.
• The installer is responsible for the maintenance of the enclosure as per the technical data, e.g. by sealing the cable outlets
with silicone.
• Wire end ferrules should be used when shortening the flexible connection cables.
• The devices may only be operated in the temperature range indicated in the data sheet and within the defined air humidity
range.
WEEE (Waste Electronical & Electronic Equipment)
Correct Disposal of This Product (Applicable in the European Union and other European countries with separate collection
systems).
This marking shown on the product or its literature, indicates that it should not be disposed
with other household wastes at the end of its working life. To prevent possible harm to the
environment or human health from uncontrolled waste disposal, please separate this from
other types of wastes and recycle it responsibly to promote the sustainable reuse of
material resources. Household users should contact either the retailer where they purchased this
product, or their local government office, for details of where and how they can take this
item for environmentally safe recycling. Business users should contact their supplier
and check the terms and conditions of the purchase contract. This product should
not be mixed with other commercial wastes for disposal.

1. Quick Installation Guide ................................................................................... 3
1.1. Package Contents ...........................................................................................................................3
1.2. Overview .........................................................................................................................................3
1.3. Features.........................................................................................................................................3
1.4. Hardware Overview ........................................................................................................................4
1.5. Product Installation Guide...........................................................................................................5
1.6. Product Application .....................................................................................................................5
1.8. LED Indicators .................................................................................................................................6
1.9. Specification ..................................................................................................................................6
1.10. Caution .......................................................................................................................................7
1.11. Warranty....................................................................................................................................7
2. Pre-field verification ......................................................................................... 8
2.1. Check transmission line .................................................................................................................8
2.2. Check grounding and potential difference ..............................................................................12
2.3. Site environment review ..............................................................................................................12
3. Equipment Installation Guide ........................................................................ 13
3.1. Selection of installation equipment ..........................................................................................13
3.2. Transmission rate / PoE output ..............................................................................................14
3.3. LED operating status .................................................................................................................15
3.4. Grounding and Potential Difference .....................................................................................16
3.5. Apply Surge Protector ...............................................................................................................16
4. Troubleshooting FAQ..................................................................................... 17
4.1. EPoC transmission equipment ...................................................................................................17
Contents

Quick Installation Guide — 3
1. Quick Installation Guide
1.1. Package Contents
EPoC Transceiver DC Cable &
DC Terminal Block Quick Installation Guide
Quick Start
Guide
1.2. Overview
This device is a High-Speed, long distance Ethernet & PoE extender that makes possible to transmit IP data up to
2.4Km and PoE up to 1.2Km through various analog cables in different situations.
It is cost-effective and time saving solution to migrate existing analog system to IP based system since EPoC
Transceiver supports easy installation utilizing the existing CCTV cable (Coax, UTP, 2wire & Etc.).
With long distance transmission feature, the device makes to overcome 100 meters distance limitation easily and
reduces the construction cost significantly compared with fiber optic configuration.
1.3. Features
•Ethernet and Power over coax (UTP, 2-Wire)
communication following IEEE1901 Standard
•Data + Power over Coax (or UTP, 2-wire)
•Data distance up to 2.4Km
•PoE distance up to 1.2Km
•Max. 270Mbps Bandwidth
•10/100/1000 Full Duplex
•128bit AES network encryption
•Supports Multi-connection (Daisy chain, Star, etc.)
•Supports UTP, Telephone (2 Pairs), 2-Wire
cable communication (Using BTE Series)
•Quality LED (Data & Power)
•Plug & Play
•Surge Protection
•12VDC output (for Non-PoE Camera)

Quick Installation Guide — 4
1.4. Hardware Overview
BNC connector
DC Power Jack
Status LED indicator
Join Button
DC OUT LED Terminal Block
Right
Left
EPoC Transceiver
EPoC Transceiver
RJ45 DC OUT
ON / OFF Switch
Note: The Join Button is currently disabled.

Quick Installation Guide — 5
1.5. Product Installation Guide
1. Set the IP address on the camera following the instruction manual of the camera.
hIf the camera IP is automatically assigned (DHCP, etc.), there is no need to set the camera IP
separately.
2. Connect BNC of the coaxial cable to each EPoC Transceiver.
3. Connect 56V DC power to EPoC Transceiver first and then to AC outlet.
4. When they are correctly connected, PWR/BNC Join/Quality PWR LED are on.
5. Fix up EPoC Transceiver where it should be placed.
6. Connect the UTP(LAN) cable between EPoC Transceiver and NVR first and then between EPoC Transceiver
and camera.
7. Connect DC Cable between camera and Terminal Block on EPoC Transceiver.
hMind the polarity (+/-) and tie up DC cable on the terminal block.
8. Ping test is recommended to confirm the whole network after installation.
9. Check the video signal on the monitor.
1.6. Product Application
12V DC OUT
Non-PoE IP
Camera
Coaxial
10/100 Ethernet
56V DC/1.2A
Power Supply
EPoC Transceiver
EPoC Transceiver
NVR
Network Switch

Quick Installation Guide — 6
1.8. LED Indicators
Indicator Color Function
BNC Join EPoC Devices connected
PWR 56VDC input connected
Quality
LINK Good data connection
Poor data connection
PWR Good power supply condition
Additional adapter required
Data Flashes when data is transferred
DC OUT DC OUT switch is ON
1.9. Specification
Model 1 Port Transceiver
Interface Coax 1 x 75Ω BNC (Female) - Ethernet over Coax (B-LinX)
Ethernet
1 x RJ45 - 10/100/1000 Base-T with Auto-detect MDIX
Transmission Rate 270Mbps Full Duplex (PHY: 500Mbps)
Transmission
Distance
Ethernet up to 2.4Km(RG-6)
PoE (PoC) up to 1.2Km (RG-6 / 7W camera)
LED Indication
Ethernet 1 x Data(Green)
EPoC 1 x BNC Join(Green)
Power 1 x PWR(Blue)
Link Quality 1 x Good(Green) / 1 x Bad(Red)
Power Quality 1 x Good(Green) : 40V~57V / 1 x Bad(Red) : 40V Under
12VDC out 1 x 12V DC OUT(Green)
Encryption 128-bit AES
Power
Input 57 VDC
DC Output DC12V / 2A
Mechanical Dimension 132(L) x 83(W) x 28(H)mm
Weight 198g
Environment
Operating Temp -20 ~ 60°C
Storage Temp -30 ~ 80°C
Relative Humidity
10% ~ 90%
Compliance Certification FCC, CE, KC, RoHS
Surge Protection
IEC 61000-4-5 4kV(1.2 / 50us), 2kA(8 / 20us)
Optional Accessories 56VDC / 1.2A External Power Supply

Quick Installation Guide — 7
1.10. Caution
•Please install the device following the installation guide.
•Do not touch the device and cable with wet hands.
•Keep away from moisture and shock.
•Do not install near any heat sources such as radiators, heat registers, stoves or other apparatus that produce
heat.
•Indoor use only.
•Do not use for other purposes. (i. e. Connecting analog camera to BNC connector)
•Do not disassemble or modify this device.
•Do not put any sticker or paint on it.
•If this device is defective or malfunctioning, please unplug the power adapter immediately and contact dealer or
service center.
•Use only rated 56V power adapter specified by the manufacturer. Connect DC power to ECP-2701 first and then
to AC outlet.
1.11. Warranty
•This device has passed the quality control and product inspection.
•Please install and use according to the installation guide.
•The warranty period for this product is 36 months from the date of purchase.
•Any damages or breakage from user’s abuse, accident, modification or natural disasters will not be covered
manufacturer’s warranty.

Pre-field verification — 8
2. Pre-field verification
2.1. Check transmission line
2.1.1. Transmission line type
█ EPoC (Ethernet over Coax) Applicable
Coaxial cable
3C, 5C, 7C, 10C, RG58, RG59,
RG6, RG11, KX6, KX100, etc.
Ethernet over
Coax Transceiver
2-Wire
UTP cable
EPoC Transceiver
+ IAM-4MU1001M0
A

Pre-field verification — 9
2.1.2. Check whether the cable is disconnected / shorted
█ Test cable opens
1. Make a short the conductor and shield of the one side of the coax.
2.
Take the testing probe and connect its cords to the specific ends of multimeter (red positive into the ‘+’ marked jack
and black negative into the ‘COM’ jack) and Set the measurement type dial of the multimeter to Ω.
3. Touch one of the leads to the outer metal part of the BNC and the second to the center pin on the another side and
check the value.
4. If the value is significantly high such as Mega Ohm, it means the cable might be open.
5. If the value is lower than the expected loop resistance value, the cable might be shorted. (Normal loop resistance of
the cable in case of RG59 is about 8~10 Ω / 100 meter)
OFF DCV
DCA
A
COM
VΩ
OFF DCV
DCA
COM
AVΩ
█ Test for shorted or open
1. Make both ends of the coax free by disconnecting it from the device
2. Take the testing probe and connect its cords to the specific ends of multimeter (red positive into the ‘+’ marked
jack and black negative into the ‘COM’ jack) and Set the measurement type dial of the multimeter to continuity test.
3. Touch one of the leads to the outer metal part of the BNC and the second to the center pin. If you don’t hear any
sound, then it means the coax is not shorted.
OFF DCV
DCA
A
COM
Ω
VΩ
OFF DCV
DCA
A
COM
Ω
VΩ

Pre-field verification — 10
█Cable Connection Precautions
•Be sure to use dedicated connector when connecting cables.
•It is not recommended to mix different types of cables.
-When 50Ω and 75Ω cable are used in combination or 50Ω BNC is applied to 75Ω cable, the impedance
between the lines is unmatched and this could affect performance of the device.

Pre-field verification — 11
2.1.3. Identify loop resistance
•By measuring the loop resistance of the cable, it is possible to check the condition and the quality of the cable
used for power transmission function of the EPoC device in advance.
1. Make a short the conductor and
shield on one side.
2. Measure the resistance (Ω) of the
conductor and shield on the other
side.
•In case of Copper-covered steel cable, the cable loop resistance can be significantly increased and It is strongly
recommended to check the cable loop resistance before installation because it can greatly affect the distance
performance of the devices
•The PoE transmission distance specified on the installation guide is the value when using RG-6 Coaxial cable with
10Ω or less / 200 meter.
•If accurate loop resistance is not measured, such as measuring KΩ, MΩ, etc. as result, check if the cable or BNC is
shorted or if there's power leakage on cable.

Pre-field verification — 12
2.2. Check grounding and potential difference
EPoC equipment is basically grounded through the power cord of the adapter, so there is no need to ground
separately.
However, EPoC equipment supports PoC (Power Over Coax) function and the transmitter is powered by the power
source connected to the receiver and the end-device is powered by the transmitter through the PoE output feature.
At this time, if there is a potential difference between the end-device and the transmitter, the transmitter may not
recognize the PD (Powered Device) of the end-device correctly, and the PoE output function of the transmitter may
not work properly.
Therefore, it is necessary to make sure that the end-device is normally grounded, and that there's the potential
difference between the end-device and transmitter.
2.3. Site environment review
•Check the environment in which EPoC device is installed.
•The cable between the EPoC devices must be installed apart from high-voltage power cable.
•In environments where cross-talking or signal interference occurs, separate settings may be required, such as
network grouping (See how to set Joining).
•In environments where power noise occurs (e.g. Installation on elevator), it is necessary to use a model
specifically designed to prevent noise.
•EPoC devices are for Indoor Use and must be installed in a separate watertight enclosure when installed
outdoors.
•Check that the environment is suitable for the operating temperature and operating humidity of the equipment.

Equipment Installation Guide — 13
3. Equipment Installation Guide
3.1. Selection of installation equipment
EPoC Solution Network Security
█ IP Video Surveillance
EPoC devices allow the coaxial cables from existing analogue CCTV system to be re-used for network
camera connection.
Reusing existing coax for IP cameras can cut installation costs and save installation time significantly.
Coaxial cable
AC / DC Adapter(12V)
DVR
D1 : 640 X 480
Analog Camera
Coaxial cable10/100 Ethernet
NVR
Full HD : 1920 x 1080
IP Camera
AC/DC Adapter
Transceiver
Transceiver

Equipment Installation Guide — 14
3.2. Transmission rate
█ Transceiver
•Transmission rate(Mbps) by product configuration
Daisy Chain
Distance
1:1 1:2 1:3 1:4 1:5 1:6 1:7 1:8
200m 257 126 76 55 41 31 25 20
600m 254 115 56 32 22 16 12 10
1,200m 140 60 30 15
1,800m 90 35 13
2,400m 22
3,200m 8

Equipment Installation Guide — 15
3.3. LED operating status
3.3.1. LED status
█ Transceiver
Indicator Color Function
BNC Join EPoC Devices connected
PWR 56VDC input connected
Quality
LINK Good data connection
Poor data connection
PWR Good power supply condition
Additional adapter required
Data Flashes when data is transferred
DC OUT DC OUT switch is ON

Equipment Installation Guide — 16
3.4. Grounding and Potential Difference
EPoC device is basically grounded through the AC power cord of the adapter, so there is no need to ground
separately.
If there is a potential difference between the camera(specially metal housing camera) and ground (metal surface), PSE
of the EPoC transmitter cannot detect camera’s PD correctly and PoE output will not operate properly. In this case, it
is necessary to check if there’s potential difference between the camera body or metal surface and EPoC transmitter.
If there's potential difference on the camera and DC ground of the EPoC transmitter, it is necessary to isolate camera
body from metal surface using insulated panel (Wood or Plastic) and insulated screw.
3.5. Apply Surge Protector
In case of general surge protector for analog video, the Maximum Continuous Operating Voltage is under DC5V and
this surge protector is not compatible with EPoC devices which transfer 57VDC power via cable.
When it is necessary to install surge protector, make sure that the maximum continuos operating voltage of the surge
protector should be over 57VDC.

Troubleshooting FAQ — 17
4. Troubleshooting FAQ
4.1. EPoC transmission equipment
Problem Action
What is EPoC?
Looking at the features,
First, when replacing analog cameras with high-resolution IP camera, you can
use the existing Coaxial cable without any special construction.
Second, you can supply PoE power or 12VDC to IP camera. As a result, there is
no additional power wiring work when installing IP cameras.
Third, it is possible to send signals over long distance by modulating and
demodulating digital signals into RF signals.
Fourth, you can apply transmission media that is suitable for your installation.
There are various types of transmission media, such as Coaxial, 2-wire and an
additional cable exchanger (BTE-04) is applicable.
Fifth, while the existing analog camera has the installation distance limitation,
EPoC is applied to IP camera and can be installed up to several hundred
meters away. Please refer to the installation distance for each product and
transmission medium.
What is the basic configuration? NVR ↔ Rx EPoC(ADC) ↔ Tx EPoC (DAC) ↔ IP camera are configured as one
set. Therefore you need two EPoCs (Tx, Rx) and adapter per IP camera.
What are the basic things to check
during the initial installation?
You need to check
-the transmission media (Coaxial, Twisted pair)
-the installation distance, - the rate of 48~57 VDC power adapter,
-the LED states of the device when applying power to the device.
You also need to check the operating environmental temperature/
humidity and grounding.
Does the initial installation require a
device setup?
Because of working Plug & Play method, any setting is not required, but it
depends on the situation. In a suspected interference environment between
lines, group joining of the device helps avoid cross-talking by changing
passwords between groups.
The connector of the 48-57 VDC
Adaptor purchased is not connected to
the DC IN terminal of the EPoC.
EPoC DC IN connector is different from the connector size of
48VDC Adapter.
Please note that the inner pin spec of DC IN connector is 2.18 mm.

Troubleshooting FAQ — 18
Problem Action
Can I use the 9 VDC, 12 VDC, and 24
VDC Adaptor?
You can use it if the EPoC can supply more power than the maximum power
consumption of the IP camera.
However, since the power of IP camera is reset when it is below the reference
value, please use 48~57VDC adapter.
Is it waterproof?
Since waterproof is not available, install it inside the terminal box when
installing it outdoors, so please do not let water get into the terminal box.
What are the temperature and
humidity in the operating
environment?
Temperature is -20 ℃ ~ 60 ℃, humidity is 10% ~ 90%.
I want to know what kind of
transmission medium is used in the
field.
Mostly, the coaxial cable is RG-59 / 5C-HFBT (75Ω), the twisted pair cable
is Cat.5e UTP.
I want to know how to connect to a
Coaxial cable.
The coaxial cable must be connected using the BNC and BNC-BNC coupler.
Connecting the conductor and the shield with a simple method can cause
problems such as signal interference because the connection point serves as a
single antenna.
Is it necessary to have an Impedance
Matching cable?
Differences in impedance between cables can affect the signal quality, and it
is recommended to connect using cables of the same impedance.
Is it possible to use a twisted pair
instead of a Coaxial between
EPoC?
Yes. Additional cable exchanger (IAM-4MU1001M0A) can be added to
EPoC. For reference, IAM-4MU1001M0A provides a physical
interface between BNC and RJ-45.

Troubleshooting FAQ — 19
Problem Action
IP camera video is blurred or mosaic
occurs. And the image is slow or
intermittently unavailable.
This occurs when the video signal is set to low resolution by IP camera.
Please check if IP camera supports high resolution, encoding method, FPS,
CBR / VBR, etc. EPoC does not affect video quality, only converting video
and control signals (DAC, ADC) between NVR and IP camera.
Can EPoC devices be used with Analog
cameras?
EPoC is designed to meet IP convergence requirements out of analog and
cannot be directly connected with an analog camera. Please note that
connecting to the BNC port of EPoC to the Video OUT terminal of the analog
camera may cause fatal damage to the analog camera. If you look closely at the
EPoC BNC terminal side, you will find the phrase No Analog camera.
PTZ control is not enabled on the IP
camera.
EPoC only converts the video and control signals sent and received
between the NVR and the IP camera (DAC, ADC). EPoC recognizes only
digital signals without distinction between video and control signals. If the
video signals are clearly visible, please check if the NVR supports IP
camera's PTZ control protocol.
The PTZ control for the analog
camera is not enabled.
Analog cameras require a separate PTZ controller device that looks like a
joystick. Also, RS-485 communication line must be connected between analog
camera and video encoder (or DVR).Please note that PTZ controls on analog
cameras are not related to EPoC at all.
The Power LED is blinking. 48 ~ 57VDC Power Adapter may be defective or damaged or please
check whether the cable is shorted.
The Power Quality LED is Red. Power supplies are measured at or below 40VDC.
The Link qualtity LED is red. The data throughput of data transmitted and received via BNC
(EPoC Signal) is not sufficient.
Other manuals for IAM-6MC1001M0A
1
This manual suits for next models
1
Table of contents
Other Eneo Transceiver manuals