ENERGY FOCUS RedCap LEDFLT8-8 Series User manual

RedCap®
Emergency Lighting System
Item #: LEDFLT8-8xx-4xx-BBUF
Product Overview
The RedCap®acts as both a normal lamp as well as emergency battery backup lamp for emergency
egress lighting.
Direct Wire Mode: This product may be used as a direct-wire replacement of your current
fluorescent tube. Rewiring your fixture, replacing lampholders and removal of ballast is required for
this mode.
The “INPUT” end of the lamp, with white endcap, receives power from a standard MAINS power
to operate the lamp in normal mode, typically controlled through a wall switch. The “EM INPUT”
end of the lamp, with red endcap, is wired to “EMERGENCY MAINS,” power that is always on
except during a power outage. The EM INPUT provides power to charge to the integrated battery.
When power is present on the EM INPUT endcap, the lamp will act as a standard lamp. When
emergency power is removed from the red endcap, the lamp will enter emergency mode,
regardless of the state of the INPUT end.
REDCAP® PROVIDES
• Aluminum heatsinks and integrated driver designed to retrofit T8 fluorescent lighting.
• Full brightness in automated switch-over to emergency mode
with 1.5 hours minimum emergency run-time
• Test button and green LED indicator light to show operating status.
• Internal rechargeable lithium-ion battery
• Integrated battery charger and battery overcharge protection,
over discharge protection, and short circuit protection
• Over 500 cycles of standard charge and discharge
• Universal Input Voltage of 120-277VAC (50/60 Hz).
•Three lamp color temperatures offered: 3500K, 4000K or 5000K.
MODEL No. Input Voltage Power Lumens EM
Lumens
Emergency
Time
Color
Temp CRI
LEDFLT8-835-414-BBUF
100-277Vac,
50/60Hz 14W 1560 LM 960 LM 1.5Hr
3500K
>80LEDFLT8-840-414-BBUF 4000K
LEDFLT8-850-414-BBUF 5000K
This manual provides information for the functionality and proper installation of the Energy Focus RedCap®
Series Tubular LEDs (TLEDs). All servicing and installation of this product should be performed by qualified
and authorized service personnel.
This product is intended to be used indoors, with closed type (diffuser or lens/cover) or open type, 4ft.
fluorescent luminaires.
Green LED(Charging)
Test switch
Red LED(Emergency)

Page 2 of 5
32000 Aurora Road, Solon, OH 44139 •energyfocus.com •800.327.787743282 Rev 3
WARNING
:
RISK OF FIRE OR ELECTRIC SHOCK.
Please read all instructions and warnings thoroughly before beginning install.
This product shall be installed in accordance with the latest NEC and/or local authority
having jurisdiction. Installation shall be performed by a qualified electrician
understanding the construction and operation of this product and the electrical
requirements involved.
To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other
sharp objects.
S
afe
t
y
• READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
• ALWAYS DISCONNECT OR TERMINATE POWER TO LUMINAIRE PRIOR TO ANY
INSTALLATION OR REPLACEMENT OF PRODUCT. Failure to do so may result in
shock and/ or severe injury or damage to product. Always test circuits before
installation with voltage tester. Standard MAINS and EMERGENCY MAINS may be
provided by separate circuits.
• The RedCap® LED Lamp is intended for use in dry locations only. Do not use outdoors.
• Do not allow lampholder supply wires to touch hot surfaces. Do not mount the
Redcap®Lamp near gas or electric heaters. Equipment should be mounted in locations
and at heights where it will not readily be subjected to tampering by unauthorized
personnel. Max mounting height: 13ft.
• Do not use this equipment for other than its intended use. The use of accessory
equipment not recommended by Energy Focus may cause an unsafe condition.
• The standby power ratings as labeled on this equipment describes power
consumption at the Emergency Input end in watts when battery is charged and is not
intended to describe total or maximum power consumption. Install this equipment only
where the total power consumption does not exceed the input rating of the retrofitted
luminaire in accordance with the National Electrical Code, ANSI/NFPA 70.
• Bypass, remove, and properly dispose of fluorescent ballast and fluorescent battery backup
ballast.
• Do not make modifications to or alter luminaire housing, ballast enclosure, or electrical
components other than those required for proper installation.
• Included luminaire warning label must be affixed to luminaire in a visible
location after installation near the red endcap.
• The RedCap® Lamp will NOT operate with a dimmer switch.
• Lamp contains lithium-ion rechargeable batteries and must be recycled or disposed
of properly in accordance with local requirements.

Page 3 of 5
32000 Aurora Road, Solon, OH 44139 •energyfocus.com •800.327.787743282 Rev 3
FCC Vercan
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two
conditions: (1) this device may not cause harmful interference, and (2) this device must accept
any interference received, including interference that may cause undesired operation.
Warr
an
t
y
• Visit energyfocus.com for full standard warranty terms and conditions.
• Please note that the warranty may not be valid in case of improper installation (for example, not
turning off main power before installation), damage due to normal wear and tear, exceptional
operational conditions, or unauthorized modifications.
This Package Includes
:
• RedCap®LED lamp
• Luminaire warning label
• Installation Instructions
Dimensions:
CAUTION:
•
Please read thismanual carefully before installing the RedCap® LED Lamp
•
Turn OFF all AC Power before rewiring and installaon.
•
Ensure that L and N are properly connected tothePower Supplies.
Dimensions
1198mm
47.2"
37.8mm
1.49
28.9mm
1.14"
15mm
0.59"
7mm
0.27"
37.8mm
1.49" 1212mm
47.8"
1.49"x1.14"x47.8"(37.8mmx28.9mmx1212mm)

Page 4 of 5
32000 Aurora Road, Solon, OH 44139 •en ger yfocus.com •800.327.787743282 Rev 3
Wiring Instrucons:
Note,this lamprequirestwoAC Linesupplies. One switched line for normallamp use, andone alwaysON
connectedtotheEmergencyEnd inputofthe lampto recharge the lampbaeries.
Single Lamp Wiring Diagram:
Mulple Lamp Wiring Diagram:
Wiring Diagram
Wiring Diagram
Unswitched
EM Line
Switched
Line
Wall Switch
Neutral
EM Test
Switch
“EM INPUT”
Unswitched
EM Line
Switched
Line
Wall Switch
Neutral
LED tube
LED tube
EM Test
Switch
“EM INPUT”

Page 5 of 5
32000 Aurora Road, Solon, OH 44139 •energyfocus.com •800.327.787743282 Rev 3
Operan:
The RedCap® LEDlamprequirestwo AC Line supplies. One switchedsupply for normallampuse, and one
always ‘ON’connectedtotheEmergency End inputofthelamp,whichwill chargethebaery. Whenpower
is cut to bothends,thelamp fullywill remain illuminatedfor 90 minutes. The Green LED indicates thatthe
lampis charging. TheRedLampindicatesEMMode isON.
:Tesng
•
Withthe AC Power switchedON,pushthetest buon once. The GreenLED will turnOFF,andthe
RedLED will turnON for 3seconds.TheLampwill remainON andwill return to normal mode
automacally.
WithAC PowerOFF, pushthebuon twice to turnEM ModeON orOFF.
SAVE THESE INSTRUCTIONS.
•
AC Operation
Emergency Operation
Button operation instructions
Discharging Emergency mode Green light off
Red light flashing
X
AC Power
OFF
Charging
Green light on
Red light off
Turn on or turn off AC output by wall switch
0N
OFF
√
AC Power
on
Double-click the test switch The emergency mode on or off.
Click the test switch Emergency mode lasts 3S
√
AC Power
ON
This manual suits for next models
3
Table of contents
Other ENERGY FOCUS Lighting Equipment manuals
Popular Lighting Equipment manuals by other brands

PIPE LIGHTING
PIPE LIGHTING PIPE WIDE 84 User's manual guide

MAXLOAD
MAXLOAD 35710 quick start guide

MELINERA
MELINERA 972-F manual

AMP Lighting
AMP Lighting RenaissancePro ADL-2011-4-B-BZ Installation & maintenance guide

Monster
Monster MLB7-1030 Operation manual

Cameo
Cameo FLAT PRO SPOTIX CLFLATPROSP4 user manual

Wheelock
Wheelock CH90-24MCCH Series installation instructions

Patlite
Patlite LR4 Complete Operation Manual

EuroLite
EuroLite 51937095 user manual

Larson Electronics
Larson Electronics WDL-12-70W-LED-SFC-WCM instruction manual

Kulzer
Kulzer Translux Wave Instructions for use

Triton Blue
Triton Blue V 1200 user manual