ENTRYPASS EP.HIO User manual

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
Version: 1.04
Last Updated: 23-06-2016
EP.HIO WIRING GUIDE

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
Notes:
See http://www.entrypass.net/ for updates, revisions, and download the latest installation
manual
Platform1 version 3 support 6 and 10 digits format
For existing site, P1 will detect its card database to determine 6 or 10 digits; For new site, user
can change the digits as long as the card database is empty
Please refer to separate EntryPass Platform1 User Manual for detail operation help. The
Official EntryPass Platform1 User Manual can be downloaded from our website under
“Download” section

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
Technical Support
If you cannot find the answer to your question in this manual or in the Help files, we recommend you
contact your system installer. Your installer is familiar with your system configuration and should be able
to answer any of your questions.
Should you need additional information, please call our Technical Support Help desk, Monday to Friday
9:00 AM to 6:00 PM (GMT +8:00)
Method Details
Phone + 60 (3) -8068 1929
Fax + 60 (3) -8068 1922
Internet www.entrypass.net
Email support@entrypass.net
BEFORE YOU BEGIN

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
CAUTION
Battery may explode if mistreated. Do not recharge,
disassemble or dispose of in fire. To prevent a risk of explosion do
not pry the battery out with a metal or conductive tool.
Preparing Your EntryPass Controllers
EntryPass controller contains numerous delicate electronic circuits and components which can become
damaged as a result of electrostatic discharge (ESD). Thus, prior to installation, please follow the instruction
below:
•Observe precautions while handling the circuit board assembly by using proper grounding straps and handling
precautions at all
•Visually ensure no onboard parts is broken, damage or contains burn mark
•Do not turn on the power supply until you completed all wiring and external add on devices installations
Instances of Non-Warranty
•Damage due to natural disaster, accident or human cause.
•Damage as a result of violating the conditions recommended in the user manual
•Damage due to improper installation
•Damage due to use of uncertified components
•Damage due to use exceeding the permitted parameters
Considerations Prior to Installation

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
Communication Connector
Onboard Power LED (5V and 3.3V)
Heartbeat LED
Communication LED
Digital Input Connecter
Digital Output Connecter
Digital Output LED
Digital Input LED
Power Connector
Dip switch
32-Bits Processor
Power Connector For
Daughter Board
Expansion
Backup Battery
IDE Connector For
Daughter Board
Expansion
RJ-45 Network Port
Reset Button
Cold Start Button
Components Description

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
Digital Output LED
Digital Input LED
Expansion Board
Power Cables
Digital Input Connecter
Digital Output Connecter
With the expansion board attached to the HIO controller, the HIO now support 16 Digital Inputs and 16
Digital Outputs
Components Description (With Expansion Board)

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
ENTRYPASS
Power Supply Unit Specification:
•Switching Power Supply
•12V DC
•3 Amp (Minimum)
Power Supply Unit Specification

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
Ensure the dip
switch setting is
unique when
there is more
than 1 HIO
controller
C-
C+
RS 485: I000 meter (Maximum)
PCC
(Pc Communicator)
RS 232: 10 meter
EntryPass Platform1
Server Access
Control System
RS232
Power
Tx
Rx
HIO 16 HIO 2 HIO 1
C2 +C2- C2 +C2- C2 +C2-
When in RS485 mode, a total of 16 sets HIO controllers can be connected to
each bus/comport.
Connecting to the PC via RS485 Mode (Alarm Monitoring
Application)

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
ON
1 32 4 5
For HIO number 1
ON
1 32 4 5
For HIO number 2
ON
1 32 4 5
For HIO number 3
ON
1 32 4 5
For HIO number 4
ON
1 32 4 5
For HIO number 5
ON
1 32 4 5
For HIO number 6
ON
1 32 4 5
For HIO number 7
ON
1 32 4 5
For HIO number 8
ON
1 32 4 5
For HIO number 9
ON
1 32 4 5
For HIO number 10
ON
1 32 4 5
For HIO number 11
ON
1 32 4 5
For HIO number 12
ON
1 32 4 5
For HIO number 13
ON
1 32 4 5
For HIO number 14
ON
1 32 4 5
For HIO number 15
ON
1 32 4 5
For HIO number 16
If more than 1 HIO controller is connected to the PCC, the dip switch must be configure
according to the pattern shown above. The default dip switch configuration of the HIO
controller is 1 (ON)
HIO Dip Switch Setting (Alarm Monitoring Application)

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
Cat-5 Cat-5
Network Switch
EntryPass Platform1 Access
Control System
Default HIO controller network
setting:
1) IP address: 192.168.1.100
2) Subnet Mask: 255.255.255.0
3) Gateway: 0.0.0.0
4) Server IP address:
192.168.1.254
To change the network setting,
simply logon to the web server.
The distance from HIO controller to network switch should not more than 100
meter . Please ensure the jumper is inserted on JP1 3-4 for TCP/IP mode.
JP1
Connecting to the PC via Network (Alarm Monitoring
Application)

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
NC1 CM1 NO1 NC2 CM2
Output 1 Output 2
NC3 CM3 NO3 NC4 CM4 NO4
Output 3 Output 4
NO2 NC5 CM5 NO5 NC6 CM6
Output 5 Output 6
NC7 CM7 NO7 NC8 CM8 NO8
Output 7 Output 8
NO6
IN1 IN2 GND IN3 IN4 IN5 IN6 GND IN7 IN8 GNDGND
Input 1
Input 2
Input 3
Input 4
Input 5
Input 6
Input 7
Input 8
Digital Input:
Is a dry contact point and the input
can be configurable either close
trigger or open trigger to suits different
contact devices such as PIR,
magnetic sensor, vibration sensor,
smoke sensor and etc
Digital Output:
Selectable output either in normally
close or normally open connection.
HIO Digital Input and Digital Output Connector (Alarm
Monitoring Application)

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
C1-C1+
C2- C2+C2- C2+ C2- C2+
On-Board HIO
Unit Address: 1 HIO with Expansion Board
Unit Address: 2 HIO with Expansion Board
Unit Address: 9
……
RS485: 1000 Meter (Maximum)
Terminator
L3800 Board
The On-Board HIO is shipped in package with L3800
Is advisable to connect a resistor (100 Ohm) as terminator on last HIO
Other HIO boards must loop from ON-board HIO C2+/C2-
Connecting HIO to the L3800 Controller (Lift Application)

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
ON
1 32 4 5
For HIO number 1
ON
1 32 4 5
For HIO number 2
ON
132 4 5
For HIO number 3
ON
1 32 4 5
For HIO number 4
ON
1 32 4 5
For HIO number 5
ON
132 4 5
For HIO number 6
ON
1 32 4 5
For HIO number 7
ON
1 32 4 5
For HIO number 8
If more than 1 HIO controller is connected to the L1000 controller, the dip switch must be
configure according to the pattern shown above. The default dip switch configuration of the
HIO controller is 1 (ON)
HIO Dip Switch Setting (Lift Application)

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
1 2 3 4 5 6 7 8
NC1
CM1
NO1
NC2
CM2
NO2
NC3
CM3
NO3
NC4
CM4
NO4
NC5
CM5
NO5
NC6
CM6
NO6
NC7
CM7
NO7
NC8
CM8
NO8
You can select the HIO output either in normally open state (NO) or normally
close state (NC) and this HIO output connection is connected to the Lift
Controller (floor button location). Thus, 1 HIO (without expansion board) can
control up to 8 floors (Due to the 8 outputs available)
HIO Output Connector (Lift Application)

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
You can select the HIO output either in normally open state (NO) or normally
close state (NC) and this HIO output connection is connected to the Lift
Controller (floor button location). Thus, 1 HIO (with expansion board) can
control up to 16 floors (Due to the 16 outputs available)
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
NC9
CM9
NO9
NC10
CM10
NO10
NC11
CM11
NO11
NC12
CM12
NO12
NC13
CM13
NO13
NC14
CM14
NO14
NC15
CM15
NO15
NC16
CM16
NO16
HIO Output Connector With Expansion Board (Lift
Application)

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
Reset Button
Cold Start Button
Digital Input LED
JP1
Performing Cold Start
Steps of performing cold start:
1. Please ensure that the jumper is inserted on JP1 1-2
2. Press and Hold COLD switch
3. Press RESET Switch and Release RESET switch
4. Release COLD switches when all the inputs LED will turn to ‘Yellow’
5. When the process is complete, all the inputs LED will turn OFF

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
Reset Button
Cold Start Button
Digital Input LED
JP1
Factory Default will change the IP Address back to 192.168.1.100, Server IP to 192.168.1.254
and Port to 2020
Performing Factory Default
Steps of performing factory default:
1. Please ensure that the jumper is inserted on JP1 11-12
2. Press and Hold COLD switch
3. Press RESET Switch and Release RESET switch
4. Release COLD switches when all the inputs LED will turn to ‘Yellow’
5. When the process is complete, all the inputs LED will turn OFF

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
HIO 1
RS 485: 1000 meter (Maximum)
To L1000
HIO 2 HIO 8
C2+C2- C2+C2- C2+C2-
100 ohm resistor
It is advisable to insert a resistor value of 100 ohm on the last HIO controller for termination purpose if
installation involve long communication distance or multiple units of HIO
To PCC
HIO 16
Termination Setting

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
Communication Data Signal Max Distance Description
Computer to PC
Communicator RS 232 10m
(30 ft) 22 AWG, 2 Pairs, Shielded
PC Communicator to HIO RS 485 1000m
(3000 ft) 22 AWG, 2 Pairs, Shielded
Network Switch to HIO Network 100m
(300 ft) 24AWG, 4 Pairs
HIO digital input contact Contact 100m
(300 ft) 24 AWG, 1 Pairs
Cabling Information