ENTRYPASS TECHNICAL –WIRING GUIDE
Version: 1.02
Last Updated: 29-05-2017
BA3028 (V2) WIRING &
PROGRAMMING Guide

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
Technical Support
If you cannot find the answer to your question in this manual or in the Help files, we recommend you
contact your system installer. Your installer is familiar with your system configuration and should be able
to answer any of your questions.
Should you need additional information, please call our Technical Support Help desk, Monday to Friday
9:00 AM to 6:00 PM (GMT +8:00)
Method Details
Phone + 60 (3) -8068 1929
Fax + 60 (3) -8068 1922
Internet www.entrypass.net
Email support@entrypass.net
BEFORE YOU BEGIN

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
CAUTION
Battery may explode if mistreated. Do not recharge,
disassemble or dispose of in fire. To prevent a risk of explosion do
not pry the battery out with a metal or conductive tool.
Preparing Your EntryPass Controllers
EntryPass controller contains numerous delicate electronic circuits and components which can become
damaged as a result of electrostatic discharge (ESD). Thus, prior to installation, please follow the instruction
below:
•Observe precautions while handling the circuit board assembly by using proper grounding straps and handling
precautions at all
•Visually ensure no onboard parts is broken, damage or contains burn mark
•Do not turn on the power supply until you completed all wiring and external add on devices installations
Instances of Non-Warranty
•Damage due to natural disaster, accident or human cause.
•Damage as a result of violating the conditions recommended in the user manual
•Damage due to improper installation
•Damage due to use of uncertified components
•Damage due to use exceeding the permitted parameters
Considerations Prior to Installation

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
Power Supply Unit Specification:
•Switching Power Supply
•12V DC
•3 Amp (Minimum)
ENTRYPASS
Power Supply Unit Specification

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
BA3028 Wiring Diagram
HB0312

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
BA3028 Default Parameter Value and Jumper Setting
Default Parameter Value
Master Code 111111 (6 digits)
Local PIN 1234 (4 digits)
Force Entry Alarm Disable
Door Left Open Disable
Door Left Open Time 0 sec (00 = disable)
Lock Release Time 5 sec
Alarm Relay Active Time 10 sec (00 = non-stop alarm)
Door Sensor Status NO
Maximum Card Number 1-16777215
BA3028 Jumper Setting
Jumper Open Close
JP1 Reader Mode Access Control Mode
JP2 Wiegand 26/21 Bits Wiegand 44/41 Bits
JP3 Wiegand 6 Bits Wiegand 8 Bits
If you want to connect this reader to any Entrypass controllers, please remove jumper JP1

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
BA3028 Programming Mode
BA3028 (V2) QUICK PROGRAMMING GUIDE
(Default Master Code: 111111) 1000 Card Users
01. Cold Start (Reset)
-Off Power
-Press * and # (hold together)
-On power
-LED blinking & beeper sounded
-Release both keys
02. Clear All Memory Data
-Enter Master Code (6 digits)
-Press #
-Scan any user card
-Enter 99999999 + # (LED
blinking & beeper sounded)
-Press # (to exit operation)
03. Install Card (First Enroll)
-Enter Master Code (6 digits)
-Press #
-Press 4 + #
-Scan card
-Press # x 2 (to exit operation)
04. Install Card (Following Enroll)
-Enter Master Code (6 digits)
-Press #
-Scan any user card
-Press 4 + #
-Scan new card + #
-Enter 4 digits Personal PIN + # (Skip this if not PIN)
-continuous scan new card if more than one card
+ #
-Press # (to exit operation)
05. Delete Card
-Enter Master Code (6 digits)
-Press #
-Scan any user card
-Press 6 + #
-Scan card to be deleted + #
-continuous scan card if more than one
card + #
-Press # (to exit operation)

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
BA3028 Programming Mode
06. Delete Card (By Card Number)
-Enter Master Code (6 digits)
-Press #
-Scan any user card
-Press 6 + #
-Key in 8 digits card number + #
(continuous this step if more
than one card. The leading number
is ‘zero’can be omitted)
-Press # x 2 (to exit operation)
07. Card Only Mode
-Enter Master Code (6 digits)
-Press #
-Scan any user card
-Press * + 1
-Press # x 2 (to exit operation)
09. Card or PIN Mode
-Enter Master Code (6 digits)
-Press #
-Scan any user card
-Press * + 3
-Press # x 2 (to exit operation)
08. Card + PIN Mode
-Enter Master Code (6 digits)
-Press #
-Scan any user card
-Press * + 2
-Press # x 2 (to exit operation)
11. Change PIN
-Enter Master Code (6 digits)
-Press #
-Scan any user card
-Press *
-Enter new PIN number (4 digits)
-Press # x 2 (to exit operation)
10. Change Master Code
-Enter old Master Code (6 digits)
-Press #
-Scan any user card
-Press *
-Enter new Master Code (6 digits)
-Press # x 2 (to exit operation)

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
BA3028 Programming Mode
12. Lock Release Time
-Enter Master Code (6 digits)
-Press #
-Scan any user card
-Press 1
-Enter [01-99 sec] (2 digits)
-Press # x 2 (to exit operation)
15. Door Sensor Status (Def: NO)
-Enter Master Code (6 digits)
-Press #
-Scan any user card
-Press 861 (change to NC)
-Press # x 2 (to exit operation)
14. Door Left Open Time
-Enter Master Code (6 digits)
-Press #
-Scan any user card
-Press 3
-Enter [01-99 sec] (2 digits)
-Press # x 2 (to exit operation)
13. Door Left Open Alarm
-Enter Master Code (6 digits)
-Press #
-Scan any user card
-Press 881 (enable function)
-Press # x 2 (to exit operation)
17. Alarm Relay Active Time
-Enter Master Code (6 digits)
-Press #
-Scan any user card
-Press 2
-Enter [01-99 sec] (2 digits, 00-non
stop)
-Press # x 2 (to exit operation)
16. Force Entry Alarm
-Enter Master Code (6 digits)
-Press #
-Scan any user card
-Press 841
-Press # x 2 (to exit operation)

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
BA3028 Programming Mode
18. Install Card (By Card Number)
-Enter Master Code (6 digits)
-Press #
-Scan any user card
-Press 4 + #
-Key in 8 digits card number + # x 2
(continuous this step if more
than one card. The leading
number is ‘zero’can be omitted)
-Press # x 2 (to exit operation)

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
Advisable to
perform format
memory for the
first time you turn
on the power
To configure the
EP.MINI unit address
if there is more than 1
MINI controller
connected to the PC
communicator
Communication Data Signal Max Distance Description
Reader to HB0312 Wiegand 10m
(30 ft) 22 AWG, 3 Pairs, Shielded
HB0312 to Electro-
Magnetic Lock Power 30m
(100 ft) 18 AWG, 1 Pair
HB0312 to Push
Button Contact 30m
(100 ft) 22AWG, 1 Pair
HB0312 to Door
Sensor Contact 30m
(100 ft) 22AWG, 1 Pair
Cabling Information